Configuration of display values via DIP switches and jumpers if it is required
to switch between multiple display values via an external switch (Save mode)

The required display values are configured and saved sequentially.

1. Set DIP-switch 10, 11 and 12 to OFF position.
2. Connect supply voltage.
3. Set the display value with jumpers at J4-J6 according to table "display value”,

column “Save mode".

4. Set DIP switch 10 to ON position.
5. Set   upper   scale   caption   for   the   first   display   value   with   DIP   switches   1-9

(see “Configuration of the upper scale caption”).

6. Set time base for graphical historic data display (optional, see “Other settings”).
7. Set DIP switch 10 to OFF position.
8. "Saved” appears on the display. The configuration of the first display value is

now completed.

9. When using multiple display values repeat steps 3-8 until all required display

values are configured. The time base does not need to be set again, as it is used
for all display values.

10. In operation, the display values can be changed with a switch at J4-J6 according

to table "display value”, column “Save mode".

Configuration of the upper scale caption

The upper scale caption is binary coded using DIP switches 1-9. Possible values are
1  to   500.  Switch   1   corresponds  to   256,  switch   2  corresponds   to  128,  switch   3
corresponds to 64,  etc.,  switch  9 corresponds to  1.  For configuration, proceed as
follows:

1. Connect supply voltage.
2. Set DIP switches 1-9 to OFF position.
3. Set DIP switch 10 to ON position.
4. Start with 1st switch.
5. Set switch to ON position.
6. If the displayed value is greater than the desired value, set the switch back to

OFF position.

7. If the displayed value is less than the desired value, leave the switch in ON

position and move on to the next switch.

8. Repeat steps 5 to 7 until the desired value is displayed.

----- 

5

 -----

Содержание Digalox DPM72-PP

Страница 1: ...device hazardous voltages must not be connected to the device The device must not be used as the only protective device or protective shutdown Read instruction manual carefully before operating the d...

Страница 2: ...ion display style pointer tachometer bar graph and more splash image thresholds for alarm output hysteresis and more Recorded measurement values can be read and a continuous transmission of the actual...

Страница 3: ...Digalox Load Shunt U 50 V max 200 mV Ilow Ihigh Uhigh Ulow L N Legend Current source e g active sensor or sensor with voltage supply WARNING The device may only be operated in one of the connection o...

Страница 4: ...display value or the one that is selected by the jumpers J4 J6 or the DIP switches 11 12 respectively see table display value Scaling via DIP switches If the scaling to represent the correct display v...

Страница 5: ...lues repeat steps 3 8 until all required display values are configured The time base does not need to be set again as it is used for all display values 10 In operation the display values can be change...

Страница 6: ...2 3 4 5 6 7 8 9 1 0 1 1 1 2 Table display value factory preset can be changed by software Display value Display Scale Manual mode Save mode 60 mV DC scaled shunt Ampere DC Upper scale caption ON 1 2 3...

Страница 7: ...sec When first opening and closing J1 the current time base is displayed For each subsequent opening and closing the time base changes to the next setting In order to save the setting permanently DIP...

Страница 8: ...mpere 20 mA AC DC max 100 mA 10 500 Hz Accuracy ampere 0 5 true RMS Internal resistance ampere 6 2 Measuring value update 5 Hz 32 kHz sampling rate Recording of measurement 36 seconds to 14 days 180 i...

Отзывы: