5. Configuration
The device can be configured via DIP switches and jumpers manually or with the
corresponding software “Digalox
®
Manager” via USB interface. When configuring via
DIP switches and jumpers the basic settings can be made computer-independent.
The configuration with the software “Digalox
®
Manager” allows full functionality.
Configuration via USB interface with software “Digalox
®
Manager”
For configuration with software set DIP switch 10 to OFF position.
Connect the device to the computer via USB. After the automatic installation of the
driver, connect the device to the "Digalox
®
Manager". Settings can then be made on
the various tabs and saved in the device.
After restart, the device always shows the first display value
or the one that is selected by the jumpers J4-J6 or the
DIP switches 11-12 respectively (see table “display value”).
Scaling via DIP switches
If the scaling to represent the correct display value (e.g. for 60 mV DC via shunt or
for analogue signal) is set via DIP switches the upper scale caption corresponds to
the primary value of the shunt or the maximum display value of the analogue signal.
Examples:
upper scale caption = 250 = primary value shunt
upper scale caption = 100 = maximum display value of analogue signal
Configuration of display value via DIP switches and jumpers if only one
display value is required (Manual mode)
1. Set DIP switch 10 to ON position.
2. Set display value with jumpers at J4-J6 according to table "display value”,
column “Manual mode".
3. Set upper scale caption for the first display value with DIP switches 1-9
(see “Configuration of the upper scale caption”).
4. Connect supply voltage.
-----
4
-----