TCS TrainSpeed 4 Скачать руководство пользователя страница 9

 

a train over the sensor (or left this manual lying over it) the 
unit will begin scanning the sensor as soon as the error 
condition is corrected, though this display will not change.  
The unit will work correctly for the sensors listed in this 
display, so you may test the overall functionality of the 
TrainSpeed 4 if you want to before troubleshooting a bad 
sensor.  As a test, try tripping the sensors with your finger 
exactly 1 second apart.  The display should then read 36 if you 
are using the 1/50 of a mile sensor spacing (72 for 1/25, 18 for 
1/100 and 9 for 1/200).  If the speed is off a bit you need to 
check your own ‘timing’.  When the first sensor is tripped the 
display will show which sensor is activated in the first digit of 
the display with the rest of the display blank.  Once the second 
sensor is tripped you will see the scale speed displayed on the 
unit.   

2. 30

 

This shows that sensor #2 was activated and the train (or 
finger) was doing 30 Mph.  The speed will remain in the 
display until either this sensor or another sensor is triggered.  
If this test works you are ready to start running trains!   
 
The unit is capable of reading only one sensor pair at a time.  
So, if you are running a multi-track layout and two trains hit 
the sensors at almost the same time then the first train to trip 
the sensors will be the one has its speed measured.  The other 
train will be ignored.  It should also be noted that a sensor pair 
will be disabled for about 2 seconds after the train has passed 
it before it will be able to measure another train’s speed.  This 
was done to avoid false triggering as the spaces between cars 
in a train cross the sensors. 

 
 

Содержание TrainSpeed 4

Страница 1: ...TrainSpeed 4 Four separate train speed indicators Model Railroad Speedometer Operating Manual TCS Inc 215 453 9145 Main Number 215 257 0735 Tech Number www tcsdcc com SKU 1548...

Страница 2: ...ng with four 4 screw clearance holes If you are using a clear plexiglass control panel then you can mount the unit behind a clear window instead of cutting a hole in the panel The layout for these hol...

Страница 3: ...99 11 49 5 75 cm OO 76 1315 78 52 62 26 31 13 16 6 58 cm O 48 2083 33 83 34 41 67 20 83 10 42 cm S 64 1562 50 62 5 31 25 15 63 7 81 cm G 24 4166 67 166 66 83 33 41 67 20 83 cm TT 120 833 33 33 34 16 6...

Страница 4: ...chosen spacing watch out for switch machines and the like under the layout when choosing the location of the sensors Make sure that the edges of the holes are clean especially on the bottom as this w...

Страница 5: ...old the cables in place as they can cut the insulation and cause shorts If you must anchor the cables to the benchwork staple a cable tie to the benchwork and then wrap the cable tie around the sensor...

Страница 6: ...wall transformer specifications The unit needs at least 6V to operate correctly and the supply voltage should not exceed 18V AC or DC The unit requires less then 100ma current to function The wires f...

Страница 7: ...7 6v 18v AC or DC Input polarity does not matter Figure 1 Sensor 1 Pin 1 Sensor 2 Pin 1 Sensor 3 Pin 1 Sensor 4 Pin 1 Power Connector J5 Test jumper Option Jumpers...

Страница 8: ...talled then there is a problem with that sensor pair For example if sensor pair 2 was not connected or connected incorrectly the display would look like this 43 1 At power up the unit will scan the fo...

Страница 9: ...t digit of the display with the rest of the display blank Once the second sensor is tripped you will see the scale speed displayed on the unit 2 30 This shows that sensor 2 was activated and the train...

Страница 10: ...ut two minutes on the 1 100 jumper setting for this message to be displayed The unit will display normal speed for the next train whenever any of these errors occur If the message Er 1 is displayed it...

Страница 11: ...e you will need to power down and power up the TrainSpeed board to initialize it correctly One common occurrence with the connector used is that only one row of pins is covered by the connector If you...

Страница 12: ...y H the display would look like this L3H When a sensor is covered in the dark the test display for that sensor should read H When the sensor is lit you should see an L in the test display For the unit...

Страница 13: ...ensor in question as outlined above and cover the sensor completely and tightly with a dark opaque material usually a hand pressed down firmly will do If you see a change in the display from L to H th...

Страница 14: ...P x followed by Sn E then one of the sensor cables has been damaged Plug them in one at a time until you isolate the problem cable Inspect this cable for damage and contact TCS Inc for a replacement i...

Страница 15: ...he connector Wall transformers Radio Shack AC adaptors NTE 57 9D 600 4 or NTE 57 9D 600 2 will work with this unit Cut the circular connector off that comes with the adapter strip and tin the wires an...

Страница 16: ...16 TCS Inc 215 453 9145 Main Number 215 257 0735 Tech Number www tcsdcc com...

Отзывы: