Installation
Three-Wire Network Wiring
Follow this wiring diagram for all three-wire systems
(this is common).
NOTES:
In the middle of the network, all network wiring shields should be twisted together and taped off to prevent acci
-
dental grounding. More than one ground on the network wiring can result in communication failure.
A maximum of two terminating resistors can be used.
Three-Wire Diagram
QD2040c at end of the network.
QD2040c in the middle of the
network.
1
3
2
Shielded, twisted three-conductor com-
munications wiring with one end earth
grounded. (120 Ω balancing resistors
provided.)
Shielded, twisted three-conductor com-
munications wiring with one end earth
grounded. (120
Ω
balancing resistors
provided.)
4
NOTES:
1. If using more than 64 controllers,
use the second RS-485 port or
additional QD1010 adapters.
2. Each controller must use the
same baud rate and be assigned
a unique address.
A
B
REF
Shield
A
B
REF
A
B
REF
Earth Ground
Only at one end
Drain
Wire
Last in Daisy Chain
120Ω
Terminating
Resistor
COM 1
REF
A
B
Drain
Wire
120Ω
Terminating
Resistor
A
B
REF
A
B
REF
A
B
REF
Last in Daisy Chain
Shield
Last in Daisy Chain
Earth Ground
Only at one end
120Ω
Terminating
Resistor
A
B
REF
A
B
REF
A
B
REF
Shield
Drain
Wire
COM 1
REF
REF
A
A
B
B
120Ω
Terminating
Resistor
1
2
3
3
4
4
4
COM 1
REF
A
B
COM 1
REF
A
B