Configuration

Clicking the green button with the arrow on it on the right side of the Ubiquity Connection Status title bar will refresh the 

connection status.

Controller View

This section allows you to see what controllers have been found by the QD2040c and view each controller’s address, mod-

el, and communication status. The state field will show AUTO-DETECTED initially when found by the unit and CONFIRMED 

once the controller has been recognized by the Ubiquity Cloud Server. This information allows the installer to verify that 

each controller has been found by the QD2040c and is communicating with the local network. Clicking the green Refresh 

button on the right side of the Controller View title bar will refresh each controller’s status.

System Commands
This section describes how to set up system flags for the QD2040c. “Reboot Unit” sets a flag which will shut off and 

restart the QD2040c within a five-minute cycle. “Check for Update” contacts the Ubiquity Cloud Server for any updates 

relevant to its particular model number and software version. Once the update has been downloaded, it is automatically 

applied, and the unit will reboot if necessary.

NOTE: 

The “Check for Update” command requires that the QD2040c have Internet access to retrieve the update patch.

Gateway Configuration via CLI

When you connect to the QD2040c using a a keyboard and monitor (See 

“Appendix C: Monitor and Keyboard” on page 

27

), you can configure the Gateway parameters for your site by using the built-in CLI. 

1. 

To establish a connection to the CLI, you must enter a login user name and password. If you have not changed the 

user name and password, you must enter the default credentials. 

NOTE: 

If you do not have the default credentials for this unit, contact TCS Technical Support at 800-288-9383 ext. 2 for 

assistance.)
2. 

Once logged in, type in “tcssetup.” This will open the CLI (see 

“Command Line Interface Screens” on page 

16

).

3. 

Scroll to each field that you want to change by pressing the “Enter” button.

4. 

Type in new values on any field as needed. Pressing “Enter” will save new value, or keep current value, and advance 

to the next field.

5. 

Once the final “Secure Mode” section is finalized, the unit will automatically apply the new configuration and update 

the unit within five minutes.

NOTE: 

After you have finished configuring the Gateway, you can revert your laptop back to its original DHCP settings, if 

desired. See 

“Appendix B: Revert Back to DHCP Settings” on page 24. 

Содержание QD2040c

Страница 1: ...562 800 288 9383 fax 608 836 9044 www tcsbasys com v 2108 Installation Manual The QD2040c Ubiquity Cloud Building Manager connects the site controller network with the Ubiquity Cloud servers QD2040c U...

Страница 2: ...rk Wiring 5 Two Wire Network Wiring 6 Startup 7 Troubleshooting 7 Power LED Does Not Light Up 7 No Communications with Controllers on the Network 7 No LAN Link to the Internet 7 No Communication with...

Страница 3: ...crew holes in each unit It may also be set on a shelf or table If mounting on a wall do not allow the mounting screws to touch the circuit board inside the enclosure When selecting a location to mount...

Страница 4: ...ch that all A wires are connected to A wires all B wires are connected to B wires and all REF wires are connected to REF wires NOTE A refers to the negative RS 485 connection and B refers to the posit...

Страница 5: ...hielded twisted three conductor com munications wiring with one end earth grounded 120 balancing resistors provided Shielded twisted three conductor com munications wiring with one end earth grounded...

Страница 6: ...g more than 64 controllers use the second RS 485 port or additional QD1010 adapters 2 Each controller must use the same baud rate and be assigned a unique address Two Wire Network Wiring Follow this w...

Страница 7: ...o Communications with Controllers on the Network Make sure the baud rate selection for the QD2040c is set to match the baud rate of all the controllers on each port net work the default communication...

Страница 8: ...ds Verify each port is also optically isolated which cleans up the signal and protects the unit from taking stray voltage off the RS 485 lines A set of LEDs on each of the RS 485 ports on the QD2040c...

Страница 9: ...gin and password which is supplied to customers upon request It is the customer s responsibility to configure a custom login and password Contact TCS Technical Support 800 288 9383 ext 2 for informati...

Страница 10: ...iquity Cloud Server Application Options You must select a Network Polling Cycle Time for the QD2040c This is the time interval that the unit will poll the entire network of controllers on all ports Yo...

Страница 11: ...r SSL requires port 443 to be open Protocol Select the communications protocol being used on each port TCSbus is selected by default Baud Rate This is the data transmission speed on the network The Ba...

Страница 12: ...address settings are automatically assigned when communication is established MTU Adjustments Adjusting the MTU down may allow gateways to communicate with smaller TCP packet sizes This may be useful...

Страница 13: ...asys com 13 Configuration Security Information Commissioning Tools You can access a separate page containing various commissioning tools by clicking the Commissioning Tools button at the bottom of the...

Страница 14: ...rror No Route to Host The unit does not currently have an Ethernet connection 2 Connected The unit is able to communicate to the Ubiquity Cloud Server BUT is not being matched up with a spe cific site...

Страница 15: ...and software version Once the update has been downloaded it is automatically applied and the unit will reboot if necessary NOTE The Check for Update command requires that the QD2040c have Internet ac...

Страница 16: ...53562 800 288 9383 fax 608 836 9044 www tcsbasys com 16 2800 Laura Lane Middleton WI 53562 800 288 9383 fax 608 836 9044 www tcsbasys com 16 Configuration Command Line Interface Screens Gateway Confi...

Страница 17: ...ne Middleton WI 53562 800 288 9383 fax 608 836 9044 www tcsbasys com 17 2800 Laura Lane Middleton WI 53562 800 288 9383 fax 608 836 9044 www tcsbasys com 17 Configuration Proxy Options Extended Applic...

Страница 18: ...ith a hardwired Network Interface Card NIC 2 Ethernet cable Connection Setup Ethernet Cable Connect one end of the Ethernet cable to the Local Management Ethernet Port on the QD2040c see QD2040c Power...

Страница 19: ...44 www tcsbasys com 19 Appendices Change adapter options 3 On the Network Connections panel locate the Ethernet interface that is connected to the cable Right click on the item and select Properties P...

Страница 20: ...2800 Laura Lane Middleton WI 53562 800 288 9383 fax 608 836 9044 www tcsbasys com 20 2800 Laura Lane Middleton WI 53562 800 288 9383 fax 608 836 9044 www tcsbasys com 20 Appendices TCP IPv4...

Страница 21: ...on WI 53562 800 288 9383 fax 608 836 9044 www tcsbasys com 21 Appendices 5 On the Internet Protocol Version 4 TCP IPv4 Properties change the IP schema to IP Address 10 248 248 2 Subnet Mask 255 0 0 0...

Страница 22: ...288 9383 fax 608 836 9044 www tcsbasys com 22 Appendices 7 Launch any web browser and type in the following address https 10 248 248 1 Device address 8 Depending on your browser s configuration you m...

Страница 23: ...Lane Middleton WI 53562 800 288 9383 fax 608 836 9044 www tcsbasys com 23 Appendices 10 Click on the Proceed link to take you to the next screen Proceed Screen 11 Enter the Login user name and passwor...

Страница 24: ...configuration See Appendix A Local Management Port on page 18 and wish to revert back to its previous configuration follow the steps below Windows 10 1 Search for Ethernet Settings and click the Open...

Страница 25: ...tcsbasys com 25 2800 Laura Lane Middleton WI 53562 800 288 9383 fax 608 836 9044 www tcsbasys com 25 Appendices Properties 4 On the Ethernet Properties panel locate the Internet Protocol Version 4 TCP...

Страница 26: ...53562 800 288 9383 fax 608 836 9044 www tcsbasys com 26 Appendices 5 On the Internet Protocol Version 4 TCP IPv4 Properties General tab 6 Click on the Obtain an IP address automatically radio button...

Страница 27: ...board Connection Setup 1 Connect the cable to the monitor and to the QD2040c matching up the corresponding ends HDMI DP See QD2040c Power and Communication Connections on page 4 Power on the monitor a...

Отзывы: