background image

HR150, 200; ER150, 200 FRESH AIR VENTILATION SYSTEMS

68-0269

8

Balancing Airflow

Balancing the airflow verifies that the Fresh Air Ventilation 

System is delivering the intended airflow and energy 

performance. Use the Airflow Balancing instructions in the 

Installation section to check and balance the airflow.

Controls

Remote Override Switch Functions On/Off Control

If continuous ventilation is not required, an on/off control can 

be used to activate the ventilator when it is switched to 

Standby. Controls that can be used for this function include 

dehumidistats, timers and wall switches. If moisture control in 

bathrooms is a primary function of the system, a dehumidistat 

can be used to switch the ventilator from a Low or Standby 

setting to the High setting. Moisture removal throughout the 

entire home can only be achieved when the outside air 

contains less moisture than the inside air (typically during cold 

weather conditions).

Digital Fan Timer

The ventilator controls are compatible with the Digital Fan 

Timer. If more than one timer is activated, each runs 

independently with the ventilator running at high speed until all 

timers have timed out. Up to four timers can be installed in a 

system. For complete instructions on the operation of the 

Digital Fan Timer, refer to the instructions packed with the 

timer.

Moisture Control

When a building is new, there is excess moisture in the wood, 

plaster, cement and other construction materials. When the 

new building is occupied, the activities of the occupants also 

increase the moisture level. There can also be high levels of 

formaldehyde and other chemicals that were used in the 

building materials. Running the ventilation system on high 

speed provides optimum indoor air pollutant reduction. High 

speed also provides maximum moisture removal when the 

outside air contains less moisture than the inside air. 

(Typically during cold weather conditions.) 

Operating Damper Frost Control

Some models have an electronically-controlled damper frost 

control mechanism. When the outside temperature drops 

below 27°F (-3°C), the defrost timer is activated. At the end of 

the 17 minute run cycle, when the core can experience some 

nominal frost buildup, the timer activates a motor-driven 

damper door that simultaneously opens the defrost port and 

closes off the supply air port.

INSTALLATION

When Installing this Product…

1.

Read these instructions carefully. Failure to follow these 

instructions could damage the product or cause a haz-

ardous condition.

2.

Check the ratings on the product to make sure the prod-

uct is suitable for your application.

3.

Installer must be a trained, experienced service techni-

cian.

4.

After installation is complete, check out product opera-

tion as provided in these instructions.

CAUTION

Electrical Shock Hazard. 

Can cause personal injury or equipment damage.

Disconnect power supply to prevent electrical shock or 

equipment damage.

Unpacking Fresh Air Ventilation System

Check that all the components are included. The Fresh Air 

Ventilation System is shipped assembled. The carton contains 

the following:

• Fresh Air Ventilation System.

• Vibration isolation straps (4).

• Drain fittings (2) and T fitting (1).

• Literature package.

Except for the mounting hardware and drain fittings, the 

ventilator is ready for installation. Wiring, drain connections 

and ducting are required to complete the installation. 

Mounting

Suspended from Floor Joists

1.

Mount the four vibration isolation straps (provided) to 

the side of the ventilator using the mounting screws 

located on the cabinet. See Fig. 2 and 3.

2.

Securely fasten the other ends of the straps to the floor 

joists with wide-head nails (not supplied), making sure 

the unit is level. The straps are designed to reduce 

noise, resonance or harmonics; therefore, using the full 

length of the strap between the ventilator and the floor 

joists is recommended.

NOTE: Removal of the door and core reduces the 

weight of the ventilator, making it easier to lift 

into place.

Floor Mounting

The mounting hardware included is not needed for floor 

mounting. 

1.

Use 2 x 4 in. wood pieces to build a frame to support the 

ventilator along the bottom edge. The frame must hold 

the ventilator at least 10 in. up from the floor to allow 

clearance for the drain line. 

2.

Set the frame back approximately 2 in. from the front-

edge to avoid interference with the hinged door.

3.

Place the ventilator on the frame. Secure the ventilator 

to the frame using screws and a strip of wood or metal; 

screw into the side walls of the ventilator within 1 in. of 

the bottom.

4.

Connect the drain lines to a drain; see Installing Drain 

Line and P-Trap section.

5.

Connect the ventilator to the ducts.

Installing Drain Line and P-Trap

There are two holes at the bottom of the ventilator for the 

drain pan connectors. 

1.

Insert the connectors through the hole in the drain pan 

and the bottom of the unit.

2.

Place the washer and nut on the connector.

3.

Hand tighten the nut. See Fig. 9.

Содержание HR150

Страница 1: ...verride Integral balancing dampers for quick installation Provides ventilation that helps contractors meet ASHRAE 62 89 4 speed fan control Automatic economical built in frost control for operation to...

Страница 2: ...0 cfm aluminum core manual control and frost control HR200B 200 cfm aluminum cross flow core manual con trol and frost control ER150B 150 cfm moisture transferring core manual con trol and frost contr...

Страница 3: ...ET SUPPLY AIR FLOW HR150 ER150 VENTILATION PERFORMANCE 0 GROSS SUPPLY GROSS EXHAUST 0 0 2 0 4 0 6 0 8 1 1 2 1 4 1 6 1 8 2 50 150 100 200 250 300 350 400 M6562A cfm L s n x 0 4719 in wg Pa n x 248 8 1...

Страница 4: ...at is transferred from one airstream to the other as the air passes through the opposite sides of the heat transfer core See Fig 4 Fig 3 Duct connections and airflow 14 3 4 375 31 787 19 483 SERVICE C...

Страница 5: ...ain line from the ventilator to a drain Use an existing electrical outlet with the appropriate current rating or install one close to the ventilator power cord Allow space for the drain line by placin...

Страница 6: ...IALLY BASEMENTS FORCED AIR FURNACE COMBUSTION OR ELECTRIC M20854 RETURN AIR OUTDOORS NOTES 1 2 3 4 FURNACE BLOWER NEED NOT OPERATE TO PROVIDE GOOD AIR DISTRIBUTION QUALITY WITH THIS SYSTEM IF FURNACE...

Страница 7: ...TO AND OUT OF THE HOUSE FRESH AIR SUPPLY HOOD STALE AIR EXHAUST HOOD FLEXIBLE INSULATED DUCTING WITH A VAPOR BARRIER VENTILATOR EXHAUSTS FROM KITCHEN AND OR BATHROOMS OR OTHER CENTRAL LOCATIONS TO OUT...

Страница 8: ...1 Read these instructions carefully Failure to follow these instructions could damage the product or cause a haz ardous condition 2 Check the ratings on the product to make sure the prod uct is suita...

Страница 9: ...confirm the proper polarity use a voltmeter or test lamp to make sure there is no power after the switch when the door is open Check between that point and ground on the cabinet This process must be...

Страница 10: ...MOTOR DETAILS DEFROST DETAILS 205 ONLY DEFROST DETAILS 150 ONLY FAN MOTOR DIRECT MOUNTED CAPACITOR R E D W H I T E BLACK GREEN YELLOW ORANGE WHITE T9 T6 C A P PCB PLUG IN PLUG IN CONNECTOR RED RED ORA...

Страница 11: ...KOUT After installation is complete check to be sure system is working correctly On units with microprocessor control select ventilation speed by touching fan control pad on base module until desired...

Страница 12: ...e exhaust and fresh air supply hoods are not blocked or restricted by leaves grass or snow In winter be sure snow does not block hoods and frost does not accumulate on wire mesh bird screen IMPORTANT...

Страница 13: ...conden sationappears on windows Dehumidistat is set too high Set dehumidistat lower Undersized ventilator hot tub indoor pool etc Cover pools and hot tubs when not in use Lifestyle of occupants Avoid...

Страница 14: ...entilator drain lines Ensure O ring on drain nozzle adjusted correctly Look for kinks in line Ventilator is not level Level ventilator Drain lines are obstructed Check water drain connections Ventilat...

Страница 15: ...r Foam Prefilter 11 Circuit Board for Damper Motor 12 208514 208514 Drain Spout 13 208515 208515 Drain T Fitting 14 208516 208516 Duct Collar Red 15 208517 208517 Duct Collar Blue 16 H Channel 24 3 4...

Страница 16: ...wo 10 209722 209722 Clip for Foam Prefilter 12 208514 208514 Drain Spout 13 208515 208515 Drain T Fitting 14 208516 208516 Duct Collar Red 15 208517 208517 Duct Collar Blue 16 32002113 001 32002113 00...

Страница 17: ...cting Elbow 4 in plastic 3 208373 Diffuser 4 in diameter 4 208374 Diffuser 5 in diameter 5 208375 Diffuser 6 in diameter 6 208379 Installation Parts Kit 7 272813 Flow Measuring Station 6 in 8 208372 A...

Страница 18: ...FRESH AIR VENTILATION SYSTEMS 68 0269 18 Fig 12 HR150 and HR200 shown with manual control exploded view of parts keyed to HR Parts List 3 M15511B 1 2 4 5 6 7 25 8 8 12 13 14 15 23 22 24 21 28 16 17 1...

Страница 19: ...R150 200 FRESH AIR VENTILATION SYSTEMS 19 68 0269 Fig 13 ER150 and ER200 shown with manual control exploded view of ER Parts List 3 M11889A 1 2 4 5 6 7 25 8 8 12 13 14 15 23 22 24 21 28 16 17 18 19 20...

Страница 20: ...om yourhome Automation and Control Solutions Honeywell Honeywell Limited Honeywell Limit e 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 HR150 200 ER150...

Отзывы: