PI_PZF5000_Art0017793.doc 4 A
2d
Delete
data record
for a predetermined memory
location
Entry:
* 3 # SpNr #
SpNr = 1 to 10
(Transmits door opener protocol with AS address, R-contact
switches and data record inactive)
2e
Enter AS address
Entry:
* 4 # AS-Adresse #
AS address =
0 bis 63
(WE = 0)
2f
Define options
Entry:
* 5 # option # value #
Option: Value:
0 Transmit light switching protocol
0 = No,
1 = Yes
(WE = 1)
1 Accept door opener protocols
0 = No,
1 = Yes
(WE = 1)
2 Rest position R-contact
0 = Off,
1 = switched
(WE = 0)
3 Acoustic feedback buttons
0 = Off,
1 = On
(WE = 1)
4 Programming mode possible only
after programming mode of the
system has been switched on at
the power supply and control unit.
0 = No,
1 = Yes
(WE = 0)
!
ATTENTION: Factory settings apply for standalone operation.
In order to increase the security, option 4 should be activated
in BUS operation (i.e. set value = 1), so that the programming
requires access to the power supply and control unit.