background image

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

2

Wiring                                    

The SZ1024 and SZ1033 use standard terminal desig-

nations for wiring. See diagram below.

REMOTE TEMPERATURE SENSOR WIRING

Use 18 AWG shielded twisted-pair grounded at the sen-

sor mounting location. Sensor wiring runs of up to 250 

feet are attainable if properly shielded wire is used and 

the installation environment is free of electrical noise. 

Sensor wire should be kept at least five feet away from 

line voltage wiring.
The SZ1024 accepts two remote temperature sensors 

and the SZ1033 accepts three.  Consult the TS3000 

Series Remote Temperature Sensor Submittal Data 

sheet for a complete listing of packaging and application 

styles. When using TCS Basys Controls three-wire sen-

sors, use the black and red leads and either clip or twist 

off the white lead. Make sure that the dip switches are 

set for the sensors you are using.

POWERING THE SZ1024 and SZ1033

Superstats are powered from 24 VAC +/- 20%. 

If wiring for communications, dedicated power must be 

used to power the Superstat. Several “S” Series ther-

mostats may be powered from the same transformer, 

provided that the transformer has sufficient power.   

(Superstats require 8W @ 24 VAC.)

Caution: 

 Do not connect to 120 VAC.  When multiple 

TCS Basys Controls devices are using a single 

transformer, the polarity of the power wiring 

must be maintained because all TCS devices 

are half-wave rectified and have common return 

paths.
When the Superstat is used as a stand-alone 

thermostat without communications, the unit transformer 

may be used to power it. To do this, install a jumper 

between the “R” and “+24” terminals.  The “24-” terminal 

must then be connected to the common side of the unit 

transformer.

1

For communication wiring, use twisted, 

shielded 

18 

AWG.  Must be run separately.

 

Dry momentary contact.  Must not be powered. 

Dry contact.  Must NOT be powered.

*

 Not available with the SZ1024.

2

24 VAC transformer.

See Powering Instructions. 

3

4

Sensor input wiring 

18 

AWG, twisted, 

shielded pair.

5

Up to nominal 

28 

VAC from equipment 

transformer. 

6

R W1 W2 Y1 Y2

B

or

 

O

Time Clock

 

 

   Output

Packaged Heat Pump Terminations

3

4

4

G

4

Remote

Zone/Return

Air Temp.

5

5

5

Outside

 Air Temp.

Discharg

e

 Air Temp.

R    W1    W2    Y1     Y2     G     B/O            A2     A1   

2

*

 

When multiple TCS devices are 

using a single transformer, the 

polarity of the power wiring must 

be maintained because all TCS 

devices are half-wave rectified 

and have common return paths. 

!

!

6

R

EF

   

 A

   

  B

   

 

A

B

1

REF

R

Содержание SZ1024

Страница 1: ...ch is accessible for adjusting its settings Caution Remove power from thermostat prior to mounting Product Manual Description The SZ1024 and SZ1033 are microprocessor based programmable thermostats de...

Страница 2: ...r must be used to power the Superstat Several S Series ther mostats may be powered from the same transformer provided that the transformer has sufficient power Superstats require 8W 24 VAC Caution Do...

Страница 3: ...ir sensor only Using remote room sensor with both discharge and outdoor air sensors SZ1033 only KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order to lock the user...

Страница 4: ...m setup SET UNOCCUPIED FAN MODE AUTO 11 program setup SET OCCUPIED FAN MODE ON 10 program setup USER ACCESS TO FAN MODE YES 9 program setup SET SYSTEM MODE AUTO 7 program setup USER ACCESS TO SYSTEM M...

Страница 5: ...int for this occupied period Occupied Cool Setpoint Screen Set the cool setpoint for this occupied period Occupied Cool Setpoint Screen Set the cool setpoint for this occupied period Occupied Cool Set...

Страница 6: ...y P or add a time factor P I Time Clock Output Screen Choose whether the auxiliary output will be OPEN during occupied periods and closed during unoccupied periods or CLOSED during occupied periods an...

Страница 7: ...4 33 SZ1022 31 Compressor 1 Becomes Cool 1 Compressor 2 Becomes Cool 2 Aux Heat 1 Becomes Heat 1 Aux Heat 2 Becomes Heat 2 Emergency Heat Mode does not exist Aux Heat 1 Must be enabled Step 24 for hea...

Страница 8: ...bled using the software the override also activates in occu pied mode and takes the thermostat into unoccupied mode In either case you are able to view the time remaining in the override period both w...

Страница 9: ...ges will be turned off and will remain off until the discharge air temperature falls 3 below that limit If the LOW LIMIT is reached the fan and cooling stages will be turned off and will remain off un...

Страница 10: ...IARY OUTPUT An auxiliary relay output is available to output a signal based on the occupancy status It is commonly used with an economizer minimum position control or to signal an outdoor air damper t...

Страница 11: ...e reading Press the WARMER up button The setpoint adjustment screen should now be showing Press the WARMER button until the heating setpoint is greater than the current temperature by at least five de...

Страница 12: ...the wiring Short terminals R to W1 W2 Y1 Y2 or B O and see if the heating or cooling comes on This is a check for a mechanical relay failure Both Heating and Cooling Are On If this occurs there are t...

Страница 13: ...fan O ccupied Heating Cooling Fan Serv ice Program CO OLER W ARM ER Data switch service status system switch program setup clock setup override 11 19 01 Main Monitoring Screen Press the service butto...

Страница 14: ...s described in the setup section User s Guide Inside the hinged door of the thermostat is the SuperstatTM User s Guide This guide is designed to assist the installer in explaining to the user how to o...

Отзывы: