program
setup
COOL STAGE 2
2F
DIFF:
MO 1 PROPORTIONAL
program
setup
program
setup
program
setup
29c.
MOD OUT 2
ACTION:
MOD OUT 1
28c.
ACTION:
MO 2 PROPORTIONAL
BAND:
program
setup
30c.
MOD OUT 1
RANGE:
program
setup
program
setup
program
setup
MOD OUT 2 UNOCC
33c.
MOD OUT 1 UNOCC
32c.
ACTION:
31c.
MOD OUT 2
RANGE:
program
setup
COOL STAGE 1
OFFSET:
0F
ENABLE DISCHARGE
program
setup
program
setup
MO 2 SETPOINT
MO 1 SETPOINT
OFFSET:
BAND:
5F
5F
OFFSET:
1F
1F
DIRECT
DIRECT
4-20mA
4-20mA
MOD
ACTION:
MOD
AIR SENSOR?
YES
Modulating Output 1 Proportional Band
Screen. Enter the number of degrees away
from the heating setpoint that the valve or
damper will be fully open.
Modulating Output 2 Proportional Band
Screen. Enter the number of degrees away
from the cooling setpoint that the valve or
damper will be fully open.
Modulating 1 Setpoint Offset Screen. Enter an
offset value for modulating output 1. This is the
number of degrees below the heating setpoint
before the output begins to modulate.
Modulating 2 Setpoint Offset Screen. Enter an
offset value for modulating output 2. This is the
number of degrees above the cooling setpoint
before the output begins to modulate.
Modulating 1 Output Action Screen.
Choose whether modulating output 1 will be
direct or reverse acting.
Modulating 2 Output Action Screen.
Choose whether modulating output 2 will be
direct or reverse acting.
Modulating Output 1 Range Screen.
Choose whether the modulating output 1
range will be 0-20 mA or 4-20 mA.
Modulating Output 2 Range Screen.
Choose whether the modulating output 2
range will be 0-20 mA or 4-20 mA.
Modulating Output 1 Unoccupied Action
Screen. Choose whether the modulating output 1
unoccupied action will be 0mA, 4mA, 20mA or
MODulating.
Modulating Output 2 Unoccupied Action
Screen. Choose whether the modulating output 2
unoccupied action will be 0mA, 4mA, 20mA or
MODulating.
Discharge Air Sensor Function Screen.
Choose whether or not you are using a dis-
charge air sensor function. To monitor only,
select NO. See setup instructions for dip-
switch settings which must also be set.
program
setup
program
setup
program
setup
MO 1 DISCHARGE
38c.
37c.
36c.
MOD OUT 2 BASED
ON:
35c.
MOD OUT 1 BASED
34c.
ON:
program
setup
program
setup
DI3 USED FOR:
FILTE R SERVICE
39c.
MO 2 DISCHARGE
SETPOINT:
program
setup
program
setup
program
setup
43c.
COOLING LOCKOUT
TEMP:
60F
42c.
EN ABLE SM AR T
YES
R EC OVER Y?
ENABLE OUTDOOR
YES
AIR SENSOR?
41c.
DELAY ON POW ERUP
60 SEC ON DS
MO 2 RESET RATIO
D I3 U SED FOR :
FILTER S ERV IC E
40c.
MO 1 RESET RATIO
program
setup
program
setup
COO L S TAG E 2
O FFSET:
2F
DISCHARGE AIR
COO L S TAG E 1
2F
DIFF:
DISCHARGE AIR
program
setup
44c.
HEATING LOCKOUT
70F
TEMP:
LOW LIMIT:
45F
Go to #45, p 6
HIGH LIMIT:
120F
SPACE
SPACE
SETPOINT:
90F
65F
FACTOR:
2F
FACTOR:
5F
Discharge Air Low Limit Screen. Enter
a discharge air low limit value. This
screen will not appear if the discharge air
sensor function is disabled.
Discharge Air High Limit Screen. Enter
a discharge air high limit value. This
screen will not appear if the discharge air
sensor function is disabled.
Modulating Output 1 Control Screen.
Choose whether to control based on DIS-
CHARGE air reset or SPACE tempera-
ture.
Modulating Output 2 Control Screen.
Choose whether to control based on DIS-
CHARGE air reset or SPACE tempera-
ture.
Modulating Output 1 Discharge Air
Setpoint Screen. Enter a value at which
the discharge air setpoint is to be con-
trolled for heating.
Modulating Output 2 Discharge Air
Setpoint Screen. Enter a value at which
the discharge air setpoint is to be con-
trolled for cooling.
Modulating Output 1 Reset Ratio
Factor Screen. Enter a reset ratio factor.
This is the number of degrees that the
discharge air setpoint is raised when the
space temperature falls by 1 degree.
Modulating Output 2 Reset Ratio
Factor Screen. Enter a reset ratio factor.
This is the number of degrees that the
discharge air setpoint is lowered when
the space temperature rises by 1 degree.
Outdoor Air Sensor Function Screen.
Choose whether or not you are using an
outdoor air sensor function. To monitor
only, select NO. See setup instructions
for dipswitch settings which must also be
set.
Cooling Lockout Screen. Enter an out-
door air cooling lockout temperature.
This screen will not appear if the outdoor
air sensor function is disabled.
Heating Lockout Screen. Enter an out-
door air heating lockout temperature.
This screen will not appear if the outdoor
air sensor function is disabled.