program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

DISCHARGE AIR

30d.

29d.

ENABLE DISCHARGE

AIR SENSOR?

SETPOINT

28d.

UNOCCUPIED ACTION

26d.

MODULATING

MODULATING OUT

25d.

OUTPUT ACTION:

.

 DIRECT

23d.

MODULATING OUT

IS:

24d.

program

setup

PROPORTIONAL

27d.

RANGE:

4-20mA

BAND:

5F

OFFSET:

01F

LOW LIMIT:

45F

YES

COOL

Modulating Output Define Screen.
Choose whether the modulating output
will be used for COOL, HEAT or AQUA-
STAT. With DI2 set to AQUASTAT, the
analog output will be used for cooling
with DI2 open and heating with DI2
closed.

Modulating Output Action Screen.
Choose whether the output will be direct
or reverse acting. (When DI2 is set to
AQUASTAT, the output will automatically
reverse action when DI2 is closed.)

Modulating Output Range Screen.
Choose whether the modulating output
range will be 0-20 mA or 4-20 mA.

Unoccupied Action Screen. Choose
whether the unoccupied action will be
modulating, 0 mA, 4 mA, or 20 mA.

Modulating Output Proportional Band
Screen. 
Enter the number of degrees
away from the setpoint that the valve or
damper will be fully open. 

Analog Output Setpoint Offset
Screen. 
Enter a setpoint offset. This is a
value below the heating setpoint or
above the cooling setpoint where the
analog output begins to modulate.

Discharge Air Sensor Function Screen.
Choose whether or not you are using a dis-
charge air sensor function. To monitor only,
select NO. See setup instructions for dip-
switch settings which must also be set.

Discharge Air Low Limit Screen. Enter
a discharge air low limit value. This
screen will not appear if the discharge
air sensor function is disabled.

DISCHARGE AIR

31d.

HIGH LIMIT:

120F

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

HEATING LOCKOUT

37d.

TEMP:

70F

COOLING LOCKOUT

36d.

TEMP:

65F

ENABLE OUTDOOR

35d.

AIR SENSOR?

YES

RESET RATIO

34d.

2F

FACTOR:

33d.

DISCHARGE AIR

SETPOINT:

90F

32d.

CONTROL BASED

ON:

SPACE

Go to #45, p. 6

Discharge Air High Limit Screen.
Enter a discharge air high limit value.
This screen will not appear if the dis-
charge air sensor function is disabled.

Discharge Air Reset Screen. Choose
whether to control based on DIS-
CHARGE air reset or SPACE tempera-
ture. This screen will not appear if the
discharge air sensor function is dis-
abled.

Discharge Air Setpoint Screen. Enter
a value at which the discharge air set-
point is to be controlled. This screen will
not appear if the control is based on
space temperature.

Reset Ratio Factor Screen. Enter a
reset ratio factor. This is the number of
degrees that the discharge air setpoint
is raised when the space temperature
falls by 1 degree for heating, or the
number of degrees that the discharge
air setpoint is lowered when the space
temperature rises by 1 degree for cool-
ing.

Outdoor Air Sensor Function Screen.
Choose whether or not you are using
an outdoor air sensor function. To moni-
tor only, select NO. See setup instruc-
tions for dipswitch settings which must
also be set.

Cooling Lockout Screen. Enter an
outdoor air cooling lockout temperature.
This screen will not appear if the out-
door air sensor function is disabled.

Heating Lockout Screen. Enter an
outdoor air heating lockout temperature.
This screen will not appear if the out-
door air sensor function is disabled.

Содержание SZ1017a

Страница 1: ...nt monitoring inputs and indication External time clock input Access to programming or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Contents Description 1 Features 1 Mounting 1 Wiring 2 Setup 4 Programming 5 Setting Clock Schedule 11 Operation 11 Checkout Troubleshooting 14 LED Description 15 Limiting Occupant Access 16 User s Guide...

Страница 2: ...S Basys Controls devices are using a single transformer the polarity of the power wiring must be maintained because all TCS devices are half wave rectified and have common return paths When the Superstat is used as a stand alone thermostat with out communications the unit transformer may be used to power it To do this install a jumper between the R and 24 terminals The 24 terminal must then be con...

Страница 3: ... B R 1 G Y1 or W1 Y2 or W2 6 Time Clock Output 7 Output Wiring for the SZ1017a A B 1 6 7 Output Wiring for the SZ1041 A B R 1 G Y1 or W1 Y2 or W2 Time Clock Output 6 6 7 Output Wiring for the SZ1051 A B R 1 G Y1 or W1 Y2 or W2 Time Clock Output CWV 6 HWV 6 7 Output Wiring for the SZ1053 ...

Страница 4: ...nly Using remote room sensor with both discharge and outdoor air sensors KEYPAD ACCESS The dipswitches in the cover shown above connected with ribbon cable must be set in order to lock the user out of pro gramming and or to set the clock and schedule Use the guide below to set these dipswitches for your application User access may also be limited with an access code set in pro gramming The fan and...

Страница 5: ...ing 248 Communication Baud Rate Screen If using a PC to access the thermostat all controllers on a network must be set to the same baud rate Choose between 2 4K 4 8K 9 6K and 19 2K program setup program setup program setup program setup program setup program setup program setup 11 UNOCCUPIED HEAT SETPOINT OCCUPIED HEAT 10 SETPOINT SET UNOCCUPIED FAN MODE 9 8 SET OCCUPIED FAN MODE USER ACCESS TO FA...

Страница 6: ... the auxiliary output will be OPEN during occupied periods and closed during unoccupied periods or CLOSED during occupied periods and open during unoccupied periods program setup program setup program setup program setup 48 DI3 USED FOR FILTER SERVICE 47 ENABLE SMART YES RECOVERY SET DI2 SETPOINT 02F SHIFT 46 DELAY ON POWERUP 60 SECONDS DI2 USED FOR MONITOR DI3 USED FOR FILTER SERVICE 45 DI1 USED ...

Страница 7: ...P 70F COOLING LOCKOUT 28b TEMP 65F ENABLE OUTDOOR AIR SENSOR 27b YES program setup program setup program setup program setup program setup program setup program setup program setup ECON CONTROL 37b ACTION DIRECT 36b ECON OUTPUT RANGE 4 20mA OUTDOOR DAMPER MIN POSITION 35b 10 DSCHRGE AIR ECON 34b PROP BAND DSCHRGE AIR ECON 33b DSCHRGE AIR ECON 32b SETPOINT 55F 31b OUTDOOR AIR ECON SETPOINT 65F 30b ...

Страница 8: ...nsor function is disabled Discharge Air Economizer Screen Set the discharge air setpoint This screen will not appear if the discharge air sensor function is disabled program setup DSCHRGE AIR ECON 33a 32a program setup COOL STAGE 1 OFFSET 0F DSCHRGE AIR ECON program setup program setup COOLING LOCKOUT 38a 37a 36a ENABLE OUTDOOR AIR SENSOR 35a ECON CONTROL 34a ACTION program setup program setup DI3...

Страница 9: ...t also be set program setup program setup program setup MO 1 DISCHARGE 38c 37c 36c MOD OUT 2 BASED ON 35c MOD OUT 1 BASED 34c ON program setup program setup DI3 USED FOR FILTER SERVICE 39c MO 2 DISCHARGE SETPOINT program setup program setup program setup 43c COOLING LOCKOUT TEMP 60F 42c ENABLE SMART YES RECOVERY ENABLE OUTDOOR YES AIR SENSOR 41c DELAY ON POWERUP 60 SECONDS MO 2 RESET RATIO DI3 USE...

Страница 10: ...ir Low Limit Screen Enter a discharge air low limit value This screen will not appear if the discharge air sensor function is disabled DISCHARGE AIR 31d HIGH LIMIT 120F program setup program setup program setup program setup program setup program setup program setup HEATING LOCKOUT 37d TEMP 70F COOLING LOCKOUT 36d TEMP 65F ENABLE OUTDOOR 35d AIR SENSOR YES RESET RATIO 34d 2F FACTOR 33d DISCHARGE A...

Страница 11: ...ay still be activated SET OCCUPIED A 08 00 TO 12 00 4 5 TIMES MONDAY B 13 00 TO 17 00 SET OCCUPIED 6 TIMES TUESDAY The following screens are repeated for Wed Thurs Fri Sat and Sun Holiday 1 and 2 COPY MON FOR TUE 7 8 A 08 00 TO 12 00 B 13 00 TO 17 00 clock setup override clock setup clock setup clock setup override MON 72F 12 00 AM SET DATE 11 19 01 3 1 clock setup ENTER ACCESS SET TIME DAY MON 12...

Страница 12: ... econ omizer On the SZ1051 analog output one is used to control the heating or cooling in a space while analog output two is used to control an economizer ANALOG OUTPUTS DISCHARGE AIR RESET SZ1017a SZ1053 The analog output on the SZ1017a is used to control the heat ing or cooling in a space The analog outputs on the SZ1053 are used to control the heating and cooling in a space To use the discharge...

Страница 13: ... cooling ANALOG OUTPUT PARAMETERS Use programming steps 23d through 28d for the SZ1017a or 23a through 28a for the SZ1051 or 23c through 32c SZ1053 to program the operating parameters for the analog output Select whether the analog output is set for heating cooling or aquastat SZ1017a and SZ1051 Select direct or reverse action Select whether you want the analog output to modulate from 4 to 20mA or...

Страница 14: ... rated at 24 VAC For loads that exceed this use an external relay It may be set to be open NO or closed NC when the thermostat is operating in the occupied mode and will be the opposite during the unoccupied mode BUILT IN DELAYS The SZ1017a SZ1041 SZ1051 and SZ1053 have delays built into the programming sequences to protect equipment The fan has a minimum on and off time of 30 seconds When the fan...

Страница 15: ...sequence off The fan will turn off 2 minutes after the last heating stage 8 Press the cooler button until the cooling setpoint is less than the current temperature by at least five degrees The fan will come on The cooling stage s will sequence on after 2 min utes 9 Press the warmer button until the cooling setpoint is greater than the current temperature by one degree The cooling stage s will sequ...

Страница 16: ...tput Not Working Properly Check wiring A separate transformer should be used for the SZ1017a SZ1041 SZ1051 or SZ1053 and a separate trans former should be used for the motor s Check to make sure that the analog output is programmed correctly Check the Service Menu The Mod Out Screen will tell you what the SZ1041 or SZ1051 is trying to put out Compare this with the actual position on the heating or...

Страница 17: ...l monitoring is available by continually pressing the service key FOR THE SZ1053 FOR THE SZ1017a Occupied Heating Cooling Fan Service Program Data Limiting Occupant Access SETPOINT ADJUSTMENT The occupant may temporarily change the occupied heating and cooling setpoints 5 F by factory default This setpoint change will remain until the end of the current occupied peri od at which time the program r...

Страница 18: ...e is designed to assist the installer in explaining to the end user how to operate their new thermo stat as well as serve as a handy future reference for the end user We recommend that the installer fill out the appropriate pages and explain to the user how the thermostat operates what settings may be changed and how the time clock sched ules are used S U P E R S T A T TM Rev 0900 ...