![TCS Basys Controls SZ1017a Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/tcs-basys-controls/sz1017a/sz1017a_product-manual_3897249010.webp)
2800 LAURA LANE
❘
MIDDLETON, WI 53562
❘
(800) 288-9383
❘
FAX (608) 836-9044
❘
www.tcs-basys.com
10
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
DISCHARGE AIR
30d.
29d.
ENABLE DISCHARGE
AIR SENSOR?
SETPOINT
28d.
UNOCCUPIED ACTION
26d.
MODULATING
MODULATING OUT
25d.
OUTPUT ACTION:
.
DIRECT
23d.
MODULATING OUT
IS:
24d.
program
setup
PROPORTIONAL
27d.
RANGE:
4-20mA
BAND:
5F
OFFSET:
01F
LOW LIMIT:
45F
YES
COOL
Modulating Output Define Screen.
Choose whether the modulating output
will be used for COOL, HEAT or AQUA-
STAT. With DI2 set to AQUASTAT, the
analog output will be used for cooling
with DI2 open and heating with DI2
closed.
Modulating Output Action Screen.
Choose whether the output will be direct
or reverse acting. (When DI2 is set to
AQUASTAT, the output will automatically
reverse action when DI2 is closed.)
Modulating Output Range Screen.
Choose whether the modulating output
range will be 0-20 mA or 4-20 mA.
Unoccupied Action Screen. Choose
whether the unoccupied action will be
modulating, 0 mA, 4 mA, or 20 mA.
Modulating Output Proportional Band
Screen. Enter the number of degrees
away from the setpoint that the valve or
damper will be fully open.
Analog Output Setpoint Offset
Screen. Enter a setpoint offset. This is a
value below the heating setpoint or
above the cooling setpoint where the
analog output begins to modulate.
Discharge Air Sensor Function Screen.
Choose whether or not you are using a dis-
charge air sensor function. To monitor only,
select NO. See setup instructions for dip-
switch settings which must also be set.
Discharge Air Low Limit Screen. Enter
a discharge air low limit value. This
screen will not appear if the discharge
air sensor function is disabled.
DISCHARGE AIR
31d.
HIGH LIMIT:
120F
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
HEATING LOCKOUT
37d.
TEMP:
70F
COOLING LOCKOUT
36d.
TEMP:
65F
ENABLE OUTDOOR
35d.
AIR SENSOR?
YES
RESET RATIO
34d.
2F
FACTOR:
33d.
DISCHARGE AIR
SETPOINT:
90F
32d.
CONTROL BASED
ON:
SPACE
Go to #45, p. 6
Discharge Air High Limit Screen.
Enter a discharge air high limit value.
This screen will not appear if the dis-
charge air sensor function is disabled.
Discharge Air Reset Screen. Choose
whether to control based on DIS-
CHARGE air reset or SPACE tempera-
ture. This screen will not appear if the
discharge air sensor function is dis-
abled.
Discharge Air Setpoint Screen. Enter
a value at which the discharge air set-
point is to be controlled. This screen will
not appear if the control is based on
space temperature.
Reset Ratio Factor Screen. Enter a
reset ratio factor. This is the number of
degrees that the discharge air setpoint
is raised when the space temperature
falls by 1 degree for heating, or the
number of degrees that the discharge
air setpoint is lowered when the space
temperature rises by 1 degree for cool-
ing.
Outdoor Air Sensor Function Screen.
Choose whether or not you are using
an outdoor air sensor function. To moni-
tor only, select NO. See setup instruc-
tions for dipswitch settings which must
also be set.
Cooling Lockout Screen. Enter an
outdoor air cooling lockout temperature.
This screen will not appear if the out-
door air sensor function is disabled.
Heating Lockout Screen. Enter an
outdoor air heating lockout temperature.
This screen will not appear if the out-
door air sensor function is disabled.