SERVICE SCREENS

Continually pressing the service status button allows more

extensive monitoring. The screens are shown on the following

page.

Heating or Cooling Does Not Come On

At least one stage of heating is on whenever the  heating LED

is on, and at least one stage of cooling is on whenever the

cooling LED is on. If heating or cooling should be on but the

heating or cooling LED is off, check the fan and system

switch modes. Also, check the heating and cooling setpoints,

offsets and differentials, and the room temperature to be sure

heating or cooling should be on. If using outdoor air heating

and cooling lockouts, or discharge air high and low limits,

check their values to be sure heating or cooling is allowed. If

heating or cooling is off, but the corresponding LED is on,

check the wiring. Short terminals “R” to “Y/W1” or “Y/W2”

and see if the heating or cooling comes on. This is a check for

a mechanical relay failure. 

Wrong Temperature Display

If any of the temperatures are reading slightly high or low, there

are three adjustment pots located in the cover to adjust them.

“T1” is for the room temperature, “T2” is for the discharge air

temperature, and “T3” is for the outdoor air temperature. If the

temperature is at a minimum or maximum reading, check the sen-

sor dipswitch positions. (See setup instructions.) Check for wiring

problems (opens or shorts). A remote 1000 

sensor  should read

108 to 109 

at room temperature. 

Service LED is On

If the service LED is on, it may be for monitoring purposes or

it may indicate a critical problem. The first monitoring screen

accessed by pressing the service status button will display why

the light is on.

Outputs Will Not Shut Off

First check the room temperature and the setpoints and deter-

mine whether the output should be on. There are delays and

minimum on and off times for the fan and heating and cooling

stages. Also, check the service status menus to verify that the

outputs are on. Turning the system to “off” will instantly turn

all outputs off. The thermostat can be reset by pressing the

system switch button and the service status button simultane-

ously.  

Analog Output Not Working Properly

Check wiring. A separate transformer should be used for the

SZ1017a, SZ1041, SZ1051 or SZ1053, and a separate trans-

former should be used for the motor(s). Check to make sure

that the analog output is programmed correctly.
Check the Service Menu. The Mod Out Screen will tell you

what the SZ1041 or SZ1051 is trying to put out. Compare this

with the actual position on the heating or cooling device.
There are two conditions that must be met before the econo-

mizer analog output will modulate. First, there must be a call

for cooling. Second, the outdoor air temperature must be less

than the setting set in programming step #31b (for the

SZ1041) or #30a (for the SZ1051).
Put the SZ1041 or SZ1051 into occupied mode. You should be

able to adjust the output by going to programming step #35b

(for the SZ1041) or #34a (for the SZ1051) and varying the

minimum position setting. You need to exit programming

before the change will take effect.

MON

72F

12:00 AM

DISCHARGE AIR

55F

OUTDOOR AIR

OVERRIDE

178 MINUTES

75F

SERVICE STATUS

OK

TEMP

1.

2.

3.

4.

5.

TEMP

HEAT STAGE 2

service

status

service

status

service

status

service

status

service

status

service

status

HEAT STAGE 1

COOL STAGE 1

6b.

7b.

COOL STAGE 2

OUTDOOR AIR

DI1

service

status

service

status

MOD OUT  1

6a.

7a.

OUTDOOR AIR

FAN STATUS

service

status

service

status

11-19-01

ON

OFF

OFF

25%

25%

OK

ON

OFF

100%

OPEN

Main Monitoring Screen. Press the ser-
vice button to access the following
screens. (Date not shown on SZ1017a.)

Service Screen. This message may be
followed by any or all of the following:
CHECK FILTER, CHECK FAN, DIS-
CHARGE HIGH, DISCHARGE LOW, or
CHECK DI2.

]Discharge Air Temperature Screen.
Shows discharge air temperature if sen-
sor is used. 

Outdoor Air Temperature Screen.
Shows outdoor air temperature if sensor
is used. 

Override Status Screen. Shows
whether the override is active and if so,
how many minutes remaining.

Heat or Cool Stages Status Screen.
Shows the status of the first and second
stages of heating or cooling. 

Modulating Output 1 and 2 Status
Screen. 
Shows the percentage of modu-
lating output 1 and 2. 

DI1 Status Screen. Shows the status of
the fan interlock or DI1.

Cool Stages Status Screen. Shows the
status of the first and second stags of
cooling.

Damper Position and DI1 Status
Screen. 
Shows the position of the
damper output and the status of the fan
interlock if DI1 is set for fan interlock.

FOR THE SZ1051

FOR THE SZ1041

Содержание SZ1017a

Страница 1: ...nt monitoring inputs and indication External time clock input Access to programming or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Contents Description 1 Features 1 Mounting 1 Wiring 2 Setup 4 Programming 5 Setting Clock Schedule 11 Operation 11 Checkout Troubleshooting 14 LED Description 15 Limiting Occupant Access 16 User s Guide...

Страница 2: ...S Basys Controls devices are using a single transformer the polarity of the power wiring must be maintained because all TCS devices are half wave rectified and have common return paths When the Superstat is used as a stand alone thermostat with out communications the unit transformer may be used to power it To do this install a jumper between the R and 24 terminals The 24 terminal must then be con...

Страница 3: ... B R 1 G Y1 or W1 Y2 or W2 6 Time Clock Output 7 Output Wiring for the SZ1017a A B 1 6 7 Output Wiring for the SZ1041 A B R 1 G Y1 or W1 Y2 or W2 Time Clock Output 6 6 7 Output Wiring for the SZ1051 A B R 1 G Y1 or W1 Y2 or W2 Time Clock Output CWV 6 HWV 6 7 Output Wiring for the SZ1053 ...

Страница 4: ...nly Using remote room sensor with both discharge and outdoor air sensors KEYPAD ACCESS The dipswitches in the cover shown above connected with ribbon cable must be set in order to lock the user out of pro gramming and or to set the clock and schedule Use the guide below to set these dipswitches for your application User access may also be limited with an access code set in pro gramming The fan and...

Страница 5: ...ing 248 Communication Baud Rate Screen If using a PC to access the thermostat all controllers on a network must be set to the same baud rate Choose between 2 4K 4 8K 9 6K and 19 2K program setup program setup program setup program setup program setup program setup program setup 11 UNOCCUPIED HEAT SETPOINT OCCUPIED HEAT 10 SETPOINT SET UNOCCUPIED FAN MODE 9 8 SET OCCUPIED FAN MODE USER ACCESS TO FA...

Страница 6: ... the auxiliary output will be OPEN during occupied periods and closed during unoccupied periods or CLOSED during occupied periods and open during unoccupied periods program setup program setup program setup program setup 48 DI3 USED FOR FILTER SERVICE 47 ENABLE SMART YES RECOVERY SET DI2 SETPOINT 02F SHIFT 46 DELAY ON POWERUP 60 SECONDS DI2 USED FOR MONITOR DI3 USED FOR FILTER SERVICE 45 DI1 USED ...

Страница 7: ...P 70F COOLING LOCKOUT 28b TEMP 65F ENABLE OUTDOOR AIR SENSOR 27b YES program setup program setup program setup program setup program setup program setup program setup program setup ECON CONTROL 37b ACTION DIRECT 36b ECON OUTPUT RANGE 4 20mA OUTDOOR DAMPER MIN POSITION 35b 10 DSCHRGE AIR ECON 34b PROP BAND DSCHRGE AIR ECON 33b DSCHRGE AIR ECON 32b SETPOINT 55F 31b OUTDOOR AIR ECON SETPOINT 65F 30b ...

Страница 8: ...nsor function is disabled Discharge Air Economizer Screen Set the discharge air setpoint This screen will not appear if the discharge air sensor function is disabled program setup DSCHRGE AIR ECON 33a 32a program setup COOL STAGE 1 OFFSET 0F DSCHRGE AIR ECON program setup program setup COOLING LOCKOUT 38a 37a 36a ENABLE OUTDOOR AIR SENSOR 35a ECON CONTROL 34a ACTION program setup program setup DI3...

Страница 9: ...t also be set program setup program setup program setup MO 1 DISCHARGE 38c 37c 36c MOD OUT 2 BASED ON 35c MOD OUT 1 BASED 34c ON program setup program setup DI3 USED FOR FILTER SERVICE 39c MO 2 DISCHARGE SETPOINT program setup program setup program setup 43c COOLING LOCKOUT TEMP 60F 42c ENABLE SMART YES RECOVERY ENABLE OUTDOOR YES AIR SENSOR 41c DELAY ON POWERUP 60 SECONDS MO 2 RESET RATIO DI3 USE...

Страница 10: ...ir Low Limit Screen Enter a discharge air low limit value This screen will not appear if the discharge air sensor function is disabled DISCHARGE AIR 31d HIGH LIMIT 120F program setup program setup program setup program setup program setup program setup program setup HEATING LOCKOUT 37d TEMP 70F COOLING LOCKOUT 36d TEMP 65F ENABLE OUTDOOR 35d AIR SENSOR YES RESET RATIO 34d 2F FACTOR 33d DISCHARGE A...

Страница 11: ...ay still be activated SET OCCUPIED A 08 00 TO 12 00 4 5 TIMES MONDAY B 13 00 TO 17 00 SET OCCUPIED 6 TIMES TUESDAY The following screens are repeated for Wed Thurs Fri Sat and Sun Holiday 1 and 2 COPY MON FOR TUE 7 8 A 08 00 TO 12 00 B 13 00 TO 17 00 clock setup override clock setup clock setup clock setup override MON 72F 12 00 AM SET DATE 11 19 01 3 1 clock setup ENTER ACCESS SET TIME DAY MON 12...

Страница 12: ... econ omizer On the SZ1051 analog output one is used to control the heating or cooling in a space while analog output two is used to control an economizer ANALOG OUTPUTS DISCHARGE AIR RESET SZ1017a SZ1053 The analog output on the SZ1017a is used to control the heat ing or cooling in a space The analog outputs on the SZ1053 are used to control the heating and cooling in a space To use the discharge...

Страница 13: ... cooling ANALOG OUTPUT PARAMETERS Use programming steps 23d through 28d for the SZ1017a or 23a through 28a for the SZ1051 or 23c through 32c SZ1053 to program the operating parameters for the analog output Select whether the analog output is set for heating cooling or aquastat SZ1017a and SZ1051 Select direct or reverse action Select whether you want the analog output to modulate from 4 to 20mA or...

Страница 14: ... rated at 24 VAC For loads that exceed this use an external relay It may be set to be open NO or closed NC when the thermostat is operating in the occupied mode and will be the opposite during the unoccupied mode BUILT IN DELAYS The SZ1017a SZ1041 SZ1051 and SZ1053 have delays built into the programming sequences to protect equipment The fan has a minimum on and off time of 30 seconds When the fan...

Страница 15: ...sequence off The fan will turn off 2 minutes after the last heating stage 8 Press the cooler button until the cooling setpoint is less than the current temperature by at least five degrees The fan will come on The cooling stage s will sequence on after 2 min utes 9 Press the warmer button until the cooling setpoint is greater than the current temperature by one degree The cooling stage s will sequ...

Страница 16: ...tput Not Working Properly Check wiring A separate transformer should be used for the SZ1017a SZ1041 SZ1051 or SZ1053 and a separate trans former should be used for the motor s Check to make sure that the analog output is programmed correctly Check the Service Menu The Mod Out Screen will tell you what the SZ1041 or SZ1051 is trying to put out Compare this with the actual position on the heating or...

Страница 17: ...l monitoring is available by continually pressing the service key FOR THE SZ1053 FOR THE SZ1017a Occupied Heating Cooling Fan Service Program Data Limiting Occupant Access SETPOINT ADJUSTMENT The occupant may temporarily change the occupied heating and cooling setpoints 5 F by factory default This setpoint change will remain until the end of the current occupied peri od at which time the program r...

Страница 18: ...e is designed to assist the installer in explaining to the end user how to operate their new thermo stat as well as serve as a handy future reference for the end user We recommend that the installer fill out the appropriate pages and explain to the user how the thermostat operates what settings may be changed and how the time clock sched ules are used S U P E R S T A T TM Rev 0900 ...

Отзывы: