background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 •  (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

8

timer. If each occupancy period is about the same length 

of time, (theaters, meetings) another option is to set the 

DI3 to external override, and use the timed override but-

ton to put the unit in occupied mode.  (This function uses 

a virtual DI, see Note on page 6 for details.)
To make the unit always occupied, set DI3 to external 

time clock and short the DI3 terminal to ground. (This 

function uses a virtual DI, see Note on page 6 for details.)

DiSChArge Air temPerAture SenSing 

The SZW123 accepts a remote discharge air sensor for 

monitoring purposes. (See setup instructions for dipswitch 

placement for this option.) 
Choose YES in programming screen #27 only if you are 

using a discharge air sensor and you want to enable the 

discharge air temperature high and low limit functions. If 

NO is chosen, the discharge air will still be monitored. 
When the function is enabled, a HIGH LIMIT and LOW 

LIMIT are entered in steps #29 and #28. If the HIGH 

LIMIT is reached, the fan and heating stages will be 

turned off and will remain off until the discharge air tem-

perature falls 3° below that limit. If the LOW LIMIT is 

reached, the fan and cooling stages will be turned off and 

will remain off until the discharge air rises 3° above that 

limit. When either limit is reached, the service LED will be 

on until normal operation resumes. 
The discharge air span is 0°F to 150°F (-17.8°C to 

65.6°C). 

outDoor Air temPerAture SenSing 

The SZW123 accepts a remote 1000 

 outdoor tempera-

ture sensor for monitoring purposes. (See setup instruc-

tions for dipswitch placement for this option.)
Choose YES in programming screen #30 only if you are 

using an outdoor air sensor and you want to enable the 

outdoor air heating and cooling lockout functions. If NO is 

chosen, the outdoor air will still be monitored. 
When the function is enabled, a COOLING LOCKOUT 

TEMP and HEATING LOCKOUT TEMP are entered in 

steps #31 and #32. If the outdoor temperature falls below 

the COOLING LOCKOUT TEMP, all cooling stages will 

be locked out and will remain locked out until the outdoor 

air temperature rises 2° above the lockout temperature. 

If the outdoor temperature rises above the HEATING 

LOCKOUT TEMP, all heating stages will be locked out 

and will remain locked out until the outdoor air tempera-

ture falls 2° below the lockout temperature. 
The outdoor air span is -40°F to 160°F (-40.0°C to 

71.1°C). 

FAn ProVing 

The SZ1009 allows DI1 to be set for fan proving to pro-

tect equipment on fan failure. To utilize this function, input 

a pressure or current switch which tells when the fan is 

running. If the thermostat closes its fan contact, and the 

DI1 is not closed after thirty seconds, the system will go 

to OFF, disabling all outputs, the fan LED will turn off, and 

the service LED will be lit until the system is manually 

reset by switching the system to a mode other than OFF. 

(This function uses a virtual DI, see Note on page 6 for 

details.)

Di2 SetPoint ShiFt

The SZ1009 allows DI2 to be set for setpoint shift for 

energy demand setback. This is enabled by setting DI2 

to the MONITOR mode. A digital contact that closes 

when setback is needed should be wired into DI2. You 

may specify a number of degrees such that, when the 

thermostat is operating in the occupied mode, and DI2 

is closed, the heating setpoint will be lowered this num-

ber of degrees, and the cooling setpoint will be raised 

this number of degrees. The fan will continue to operate 

according to its occupied setting. If you are using DI2 as 

monitor for another purpose, make sure to set this value 

to zero. (This function uses a virtual DI, see Note on 

page 6 for details.)

StAge outPut PArAmeterS 

For each stage of heating and cooling, you may specify 

an offset and a differential value. This allows you to 

adjust the operation of the thermostat to fit your equip-

ment to the building load. The offset value is the amount 

away from the setpoint a stage will turn off. By assign-

ing a stage a value other than zero, you “anticipate” 

that the residual heat or cooling in the duct or the other 

stages will bring the temperature back to setpoint. In 

most cases, the first stage is set to zero. The differential 

value is the difference between the on and off points. 

This value depends on the load and on the equipment 

size. If the equipment is large for the load, you may want 

to make this value as high as 5 to prevent equipment 

cycling. If the equipment is small compared to the load, 

or if tight control is desired, you may want to make this 

value as low as 1. 
The fact that the stages are configurable allows unused 

stages to be set to activate physical alarms if desired.

heat Setpoint

Cool Setpoint

on

on

on

on

oFF

oFF

oFF

oFF

Differential

Differential

offset

offset

Differential

Differential

In summary, unlike most other multi-stage program-

mable thermostats, the Superstat allows independent 

adjustments of “offsets” and “differentials” for stages of 

heating and cooling. The offset settings can be viewed 

as setpoints for the second and third stages and are 

programmed in the Superstat in the number of degrees 

(i.e. 1,2,3 ... ) beyond the heating and cooling setpoints 

(temperatures to be maintained). 

Содержание SUPERSTAT SZW123

Страница 1: ...it or Celsius temperature display Convertible to heat pump mode in programming Uses ZigBee protocol IEEE 802 15 4 compliant Self healing plug play mesh network 100mW output at 2 4 GHz 150 to 500 feet...

Страница 2: ...the installation environment is free of electrical noise Sensor wire should be kept at least five feet away from line voltage wiring The SZW123 accepts three Consult the TS Series Temperature Sensor S...

Страница 3: ...outdoor air sensor only Using remote room sensor with both discharge and outdoor air sensors Keypad Access The dipswitches in the thermostat cover shown above must be set in order to lock the user out...

Страница 4: ...K 9 6K and 19 2K Display Type Screen Choose between FAHRENHEIT and CELSIUS for tem perature indication Controller Type Screen Choose Conventional or Heat Pump mode Unit will reset the screen will mome...

Страница 5: ...for dipswitch settings which must also be set Discharge Air Low Limit Screen Enter a discharge air low limit value This screen will not appear if the discharge air sensor function is disabled Discharg...

Страница 6: ...ot be changed Main Monitoring Screen HEAT PUMP MODE CONVERSION TABLE Cool 1 Becomes Compressor Heat 1 Becomes Reversing Value Everything else not mentioned here remains same as if it is in conventiona...

Страница 7: ...overridden is set from 0 to 255 minutes in the programming screen This override behaves differently depending on the mode the thermostat is operating in occupied or unoccupied and the options that ha...

Страница 8: ...to pro tect equipment on fan failure To utilize this function input a pressure or current switch which tells when the fan is running If the thermostat closes its fan contact and the DI1 is not closed...

Страница 9: ...the next stage is allowed to turn on as well as when one stage turns off until the next stage is allowed to turn off DELAY ON POWER UP The SZW123 has an adjustable delay on power up When several ther...

Страница 10: ...prob lems poor connections opens or shorts If the tem perature is at a minimum or maximum reading check that the sensor dipswitch positions are correct as shown in the Setup section of this document A...

Страница 11: ...nge the occupied heating and cooling setpoints 5 F by factory default This setpoint change will remain until the end of the current occupied period at which time the program reverts to the setpoints d...

Страница 12: ...controllers are communicating 5 If any controller s is are not communicating it may require a QW1011 wireless repeater nearby to connect to the ZigBee network 2800 LAURA LANE MIDDLETON WI 53562 800 28...

Страница 13: ...multi device supports up to 32 hard wired controllers devices SW Superstat Series ZigBee wireless thermostat SZ10xxW series SW133 ZigBee wireless thermostat SW244 ZigBee wireless unit board Input SZ...

Отзывы: