background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 •  (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

10

less than the current temperature by at least five 

degrees. The fan will come on. The cooling stage(s) 

will sequence on after 30 seconds. 

9. Press the warmer button until the cooling setpoint is 

greater than the current temperature by one degree. 

The cooling stage(s) will sequence off.  The fan will 

turn off 2 minutes after the last cooling stage.

10. Go back to programming step #14 and set the set-

point adjust limit back to the desired value.  Make any 

other changes in programming, clock, and schedule. 

Set the fan and system modes to their desired set-

tings. 

11. If using remote sensors, verify that the reading is 

correct. If not, see 

Wrong Temperature Display 

in the 

troubleshooting

 section.

trouBleShooting
no Display

Check for 24 VAC on terminals “+24” and “-24”.  Check 

ribbon cable connecting the cover to the base for a good 

connection.

Fan Does not Come on

The fan is on whenever the fan LED is on.  If the 

fan should be on, but the fan LED is off, check 

the fan (FAN SWITCH button) and system modes 

(SYSTEM SWITCH button), and the unoccupied fan 

mode in programming.  If the fan is off but the fan LED 

is on, check wiring.  Short terminals “R” to “G” and see 

if the fan comes on.  This is a check for a mechanical 

relay failure. 

heating or Cooling Does not Come on

At least one stage of heating is on whenever the heating 

LED is on, and at least one stage of cooling is on when-

ever the cooling LED is on.  If heating or cooling should 

be on but the heating or cooling LED is off:
1. Check the fan and system switch modes. 
2. Check the heating and cooling setpoints.
3. Check the room temperature to be sure heating or 

cooling should be on. 

4. Check the offsets and differentials.
5. If using outdoor air or discharge air high and low lim-

its, check their values to be sure heating or cooling is 

allowed. 

If heating or cooling is off, but the corresponding LED is 

on, check the wiring.  Short terminals “R” to “W1”,  “Y1”, 

or “G” and see if the heating, cooling, or fan comes on. 

This is a check for a mechanical relay failure. 

wrong temperature Display

Initially, verify the wiring connections to check for prob-

lems (poor connections, opens, or shorts). If the tem-

perature is at a minimum or maximum reading, check 

that the sensor dipswitch positions are correct as shown 

in the Setup section of this document. Also, verify the 

resistance reading for the sensor in question. A remote 

sensor should read 1080 to 1090 ohms at room temper-

ature. The built-in sensor should read 108 to 109 ohms 

at room temperature. If any of the temperatures are still 

reading slightly high or low, you can add in a tempera-

ture offset (calibration) using Ubiquity or TCS Insight. 

In Ubiquity, you can edit the calibration offset for each 

temperature input (room, discharge, outdoor air, etc.) on 

the controller's programming page. For example, if the 

room temperature is reading 2 degrees high, you would 

subtract 2 from the existing offset in the room tempera-

ture calibration offset field and submit the page. In TCS 

Insight, the process is similar. Refer to the Calibrate 

Using TCS Insight Tech Bulletin # 1019 for details. As 

a last resort and only when directed to do so by TCS 

technical support, you may be able to use the on-

board adjustment pots. Refer to the Thermostat Sensor 

Calibration Tech Bulletin # 1005 for details.

T1

T2
T3

1  2

1  2  3  4  5

adjust display contrast

outputs will not Shut off

First check room temperature and setpoints to determine 

whether the output should be on.  There are delays and 

minimum on and off times for the fan and heating and cool-

ing stages.  Also, check the service status menus to verify 

that the outputs are on.  Turning the system to “off” will 

instantly turn all outputs off.  The thermostat can be reset 

by pressing the system switch button and the service status 

button simultaneously.  

Service leD is on

service

status

If the service LED is on, it may be for monitor-

ing purposes or it may indicate a critical prob-

lem.  The first monitoring screen, which is 

used to indicate why the light is on, can be 

accessed by pressing the SERVICE STATUS 

button.

SerViCe SCreenS

Through repeated pressing of the SERVICE 

 

STATUS button, the service screens (shown below) are dis-

main monitoring Screen.  

Press the 

service button to access the following 

screens.  

   

 

Service Screen.  

This message may 

be followed by any or all of the follow-

ing: CHECK FILTER, CHECK FAN, 

DISCHARGE HIGH, DISCHARGE LOW, 

or CHECK DI2.

service

status

MON

12:00AM 

72F

service

status

SERVICE STATUS

OK

1.

Содержание SUPERSTAT SZW123

Страница 1: ...it or Celsius temperature display Convertible to heat pump mode in programming Uses ZigBee protocol IEEE 802 15 4 compliant Self healing plug play mesh network 100mW output at 2 4 GHz 150 to 500 feet...

Страница 2: ...the installation environment is free of electrical noise Sensor wire should be kept at least five feet away from line voltage wiring The SZW123 accepts three Consult the TS Series Temperature Sensor S...

Страница 3: ...outdoor air sensor only Using remote room sensor with both discharge and outdoor air sensors Keypad Access The dipswitches in the thermostat cover shown above must be set in order to lock the user out...

Страница 4: ...K 9 6K and 19 2K Display Type Screen Choose between FAHRENHEIT and CELSIUS for tem perature indication Controller Type Screen Choose Conventional or Heat Pump mode Unit will reset the screen will mome...

Страница 5: ...for dipswitch settings which must also be set Discharge Air Low Limit Screen Enter a discharge air low limit value This screen will not appear if the discharge air sensor function is disabled Discharg...

Страница 6: ...ot be changed Main Monitoring Screen HEAT PUMP MODE CONVERSION TABLE Cool 1 Becomes Compressor Heat 1 Becomes Reversing Value Everything else not mentioned here remains same as if it is in conventiona...

Страница 7: ...overridden is set from 0 to 255 minutes in the programming screen This override behaves differently depending on the mode the thermostat is operating in occupied or unoccupied and the options that ha...

Страница 8: ...to pro tect equipment on fan failure To utilize this function input a pressure or current switch which tells when the fan is running If the thermostat closes its fan contact and the DI1 is not closed...

Страница 9: ...the next stage is allowed to turn on as well as when one stage turns off until the next stage is allowed to turn off DELAY ON POWER UP The SZW123 has an adjustable delay on power up When several ther...

Страница 10: ...prob lems poor connections opens or shorts If the tem perature is at a minimum or maximum reading check that the sensor dipswitch positions are correct as shown in the Setup section of this document A...

Страница 11: ...nge the occupied heating and cooling setpoints 5 F by factory default This setpoint change will remain until the end of the current occupied period at which time the program reverts to the setpoints d...

Страница 12: ...controllers are communicating 5 If any controller s is are not communicating it may require a QW1011 wireless repeater nearby to connect to the ZigBee network 2800 LAURA LANE MIDDLETON WI 53562 800 28...

Страница 13: ...multi device supports up to 32 hard wired controllers devices SW Superstat Series ZigBee wireless thermostat SZ10xxW series SW133 ZigBee wireless thermostat SW244 ZigBee wireless unit board Input SZ...

Отзывы: