background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 •  (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

1

        Communicating Thermostats

        Communicating Thermostats

SZW123

Wireless Conventional Heating & Cooling 

Thermostat with Heat Pump Mode

Product Manual          

Description                             

The SZW123 is a microprocessor-based programmable 

thermostat designed for conventional heating and cool-

ing applications with optional heat pump mode. The 

SZW123 features a 7-day time clock. 

Features                                 

•   Stand-alone or network operation

•   Adjustable delay on power-up and start-up for soft 

starts

•   P+I control option

•  Smart Recovery

•   No battery backup required

•   Built-in HVAC equipment protection

•   32 character LCD display

•   6 status LEDs

•   Remote room sensing capability

•   User setpoint adjustment limits

•   Local and remote override capability 

•   System and fan switching with access lockouts

•   Equipment monitoring inputs and indication

•   External time clock input 

•   Access to programming or schedule may be locked 

out or limited with the use of an access code

•  Fahrenheit or Celsius temperature display

•  Convertible to heat pump mode in programming

•  Uses ZigBee protocol, IEEE 802.15.4 compliant

•  Self-healing, "plug & play" mesh network

•  100mW output at 2.4 GHz

•  150 to 500 feet typical in building range

Contents                                  

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2

Setup  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Setting Clock & Schedule. . . . . . . . . . . . . . . . . . . . . . . 6

Program Options & Operating Features. . . . . . . . . . . . 6

Checkout & Troubleshooting  . . . . . . . . . . . . . . . . . . . . 9

LED Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11

Limiting Occupant Access  . . . . . . . . . . . . . . . . . . . . . .

11

User’s Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11

Mounting                                 

The SZW123 is designed for wall mounting using two 

#6-32 machine screws sheet metal screws, either over 

a horizontally installed 2” x 4” junction box, or directly to 

block or drywall. 

For best results, the thermostat should be mounted on 

an interior wall which reflects normal room environment, 

at a height of approximately five feet from the floor. 

Avoid areas exposed to direct sunlight, unusual heat 

or cool sources, open doors and windows, unventilated 

locations and hot or cold air from diffusers.
If using a remote room sensor, it should be mounted in 

the manner described above.  The thermostat may then 

be mounted in an area which is accessible for adjusting 

its settings. 

Caution

:  Remove power from thermostat 

prior to mounting.

Содержание SUPERSTAT SZW123

Страница 1: ...it or Celsius temperature display Convertible to heat pump mode in programming Uses ZigBee protocol IEEE 802 15 4 compliant Self healing plug play mesh network 100mW output at 2 4 GHz 150 to 500 feet...

Страница 2: ...the installation environment is free of electrical noise Sensor wire should be kept at least five feet away from line voltage wiring The SZW123 accepts three Consult the TS Series Temperature Sensor S...

Страница 3: ...outdoor air sensor only Using remote room sensor with both discharge and outdoor air sensors Keypad Access The dipswitches in the thermostat cover shown above must be set in order to lock the user out...

Страница 4: ...K 9 6K and 19 2K Display Type Screen Choose between FAHRENHEIT and CELSIUS for tem perature indication Controller Type Screen Choose Conventional or Heat Pump mode Unit will reset the screen will mome...

Страница 5: ...for dipswitch settings which must also be set Discharge Air Low Limit Screen Enter a discharge air low limit value This screen will not appear if the discharge air sensor function is disabled Discharg...

Страница 6: ...ot be changed Main Monitoring Screen HEAT PUMP MODE CONVERSION TABLE Cool 1 Becomes Compressor Heat 1 Becomes Reversing Value Everything else not mentioned here remains same as if it is in conventiona...

Страница 7: ...overridden is set from 0 to 255 minutes in the programming screen This override behaves differently depending on the mode the thermostat is operating in occupied or unoccupied and the options that ha...

Страница 8: ...to pro tect equipment on fan failure To utilize this function input a pressure or current switch which tells when the fan is running If the thermostat closes its fan contact and the DI1 is not closed...

Страница 9: ...the next stage is allowed to turn on as well as when one stage turns off until the next stage is allowed to turn off DELAY ON POWER UP The SZW123 has an adjustable delay on power up When several ther...

Страница 10: ...prob lems poor connections opens or shorts If the tem perature is at a minimum or maximum reading check that the sensor dipswitch positions are correct as shown in the Setup section of this document A...

Страница 11: ...nge the occupied heating and cooling setpoints 5 F by factory default This setpoint change will remain until the end of the current occupied period at which time the program reverts to the setpoints d...

Страница 12: ...controllers are communicating 5 If any controller s is are not communicating it may require a QW1011 wireless repeater nearby to connect to the ZigBee network 2800 LAURA LANE MIDDLETON WI 53562 800 28...

Страница 13: ...multi device supports up to 32 hard wired controllers devices SW Superstat Series ZigBee wireless thermostat SZ10xxW series SW133 ZigBee wireless thermostat SW244 ZigBee wireless unit board Input SZ...