background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

4

METER 2 P/REV: 

                4.00

meter 2 Pulse Per revoltion screen. 

Enter the value for the Pulses per revolt-

ion for meter input 2 (this value should be 

provided on the CT or Energy Meter from 

the Utility). This screen does not show if 

NO was selected in step 11.

METER 2 CONSTANT: 

                1.00

meter 2 Constant Value screen. 

Enter the value for the constant for meter 

input 2 (this value is provided from utility 

company). This screen does not show if 

NO was selected in step 11.

METER 2 CU FT/P: 

                5.00

meter 2 Cubic Feet Per Pulse screen. 

Enter the value for Cubic Feet per pulse. 

This only applies to 

water

gas

 and 

Btu

 (this value is provided from utility 

company). This screen does not show if 

NO was selected in step 11.

METER 2 MULT:  

                1.00

meter 2 multiplier screen. 

Enter the multiplier for meter input 2 (this 

value is provided from utility company).  

This screen does not show if NO was 

selected in step 11.

SETUP METER 3:

                NO

meter 3 setup screen. 

Select either Yes or No to program Meter 

input two. If no is selected skip to step 25.

METER 3 TYPE: 

                ELEC  1  PH

meter 3 type screen. 

Select either ELEC 1 PH, BTU, WATER, 

GAS, ELEC 3 PH. This screen does not 

show if NO was selected in step 18.

METER 3 CT VALUE: 

                0.60

meter 3 Ct Value screen. 

Enter the value for the CT wired to Meter 

input 3 (this value should be provided on 

the CT or Energy Meter from the Utility). 

This screen does not show if NO was 

selected in step 18 or if BTU, Water or 

Gas was selected in step 19.

METER 3 P/REV: 

                4.00

meter 3 Pulse Per revoltion screen. 

Enter the value for the Pulses per revolt-

ion for meter input 3 (this value should be 

provided on the CT or Energy Meter from 

the Utility). This screen does not show if 

NO was selected in step 18.

METER 3 CONSTANT: 

                1.60

meter 3 Constant Value screen. 

Enter the value for the constant for meter 

input 3 (this value is provided from utility 

company). This screen does not show if 

NO was selected in step 18.

14.

15.

16.

17.

18.

19.

20.

21.

22.

METER 3 CU FT/P: 

                5.00

meter 3 Cubic Feet Per Pulse screen. 

Enter the value for Cubic Feet per pulse. 

This only applies to Water, GAS and BTU 

(this value is provided from utility com-

pany). This screen does not show if NO 

was selected in step 18.

METER 3 MULT:  

                1.00

meter 3 multiplier screen. 

Enter the multiplier for meter input 3 (this 

value is provided from utility company).  

This screen does not show if NO was 

selected in step 18.

SETUP METER 4:

                NO

meter 4 setup screen. 

Select either Yes or No to program Meter 

input two. If no is selected skip to step 32.

METER 4 TYPE: 

                ELEC  1  PH

meter 4 type screen. 

Select either ELEC 1 PH, BTU, WATER, 

GAS, ELEC 3 PH.  This screen does not 

show if NO was selected in step 25.

METER 4 CT VALUE: 

                0.60

meter 4 Ct Value screen. 

Enter the value for the CT wired to Meter 

input 4 (this value should be provided on 

the CT or Energy Meter from the Utility). 

This screen does not show if NO was 

selected in step 25 or if BTU, Water or 

Gas was selected in step 26.

METER 4 P/REV: 

                4.00

meter 4 Pulse Per revoltion screen. 

Enter the value for the Pulses per revolt-

ion for meter input 4 (this value should be 

provided on the CT or Energy Meter from 

the Utility). This screen does not show if 

NO was selected in step 25.

METER 4 CONSTANT: 

                1.60

meter 4 Constant Value screen. 

Enter the value for the constant for meter 

input 4 (this value is provided from utility 

company). This screen does not show if 

NO was selected in step 25.

METER 4 CU FT/P: 

                5.00

meter 4 Cubic Feet Per Pulse screen. 

Enter the value for Cubic Feet per pulse. 

This only applies to 

water

gas

 and 

Btu

 (this value is provided from utility 

company). This screen does not show if 

NO was selected in step 25.

METER 4 MULT:  

                1.00

meter 4 multiplier screen. 

Enter the multiplier for meter input 4 (this 

value is provided from utility company).  

This screen does not show if NO was 

selected in step 25.

23.

24.

25.

26.

27.

28.

29.

30.

31.

Содержание SE1000

Страница 1: ...3 Operation 5 Checkout Troubleshooting 6 LED Description 7 Communicating Controls Description The SE1000 is a microprocessor based pulse monitor ing interface designed to monitor up to four pulse inp...

Страница 2: ...K y Z K y Z Wiring The SE1000 uses terminal designations for wiring See diagram below Powering the sE1000 The SE1000 is powered from 24 VAC 20 If wiring for communications dedicated power must be use...

Страница 3: ...nstant Screen Enter the value for the constant for meter input 1 this value is provided from utility company This screen does not show if NO was selected in step 4 METER 1 CU FT P 5 00 Meter 1 Cubic F...

Страница 4: ...the constant for meter input 3 this value is provided from utility company This screen does not show if NO was selected in step 18 14 15 16 17 18 19 20 21 22 METER 3 CU FT P 5 00 Meter 3 Cubic Feet Pe...

Страница 5: ...formula Pulses KW 3600 multiplier Second In general the SE1000 calculates electric meter con sumption and demand as follows R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 608 836 9044 www tcsb...

Страница 6: ...SE1000 is not retrieving a pulse signal Verify the pulse signal is being generated at the meter or CT and check the input wiring Troubleshooting No Display Check for 24 VAC on terminals R and C Incor...

Страница 7: ...Demand units will vary based on type of meter selected METER 4 COUNT 0 Meter 4 Count Screen Displays Current Consumption units will vary based on type of meter selected CONSUMPTION 0 00 kWh Meter 4 Co...