background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

4

If a single port has more than 64 Controllers or is longer 

than 4000 ft., you will need a bus repeater (QD1011a) or 

QW1010a Zigbee wireless gateway (limit of 15 wireless 

units per wireless gateway). You will need an additional 

bus repeater for each wired group of 64 units.
For best results, on wired networks, we recommend that 

you segment the network into groups of approximately 

40 controllers (requires separate QD1010-USBs 

plugged into different comm/USB ports for each network 

segment). This ensures all devices on each network 

leg will be polled and reply during a single polling cycle 

(factory default is a 1 minute polling cycle). Although 

using a repeater will allow all devices on large networks 

to communicate and the network to function, you may 

find that it takes multiple polling cycles to communicate 

with every device.
When connecting controllers on a network, you may use 

any wiring configuration (i.e. "daisy chain", "star", etc.), 

as long as all "A" terminals are connected together, 

all "B" terminals are connected together and all “Ref” 

terminals connected together. The integrity of the "A", 

"B" and “REF” wiring runs must be maintained or the 

network will not communicate properly. Also, a 120 

ohm terminating resister should be installed at the 

farthest end of the network (one is already built-in on the 

QD2010a).

CAUTION:

 You must maintain proper polarity of "A", 

"B" and "REF" connections. All shields must be tied 

together, taped off to prevent any accidental connections 

then grounded at one end of the network. Caution 

should be taken to avoid running wire near power wires, 

frequency drives, fluorescent lights, ballasts, etc., which 

can all compromise the communications signal. Care 

should also be taken to leave as little wire exposed as 

possible. 

Critical:

 Avoid noise on the communications line by 

grounding the shield. The signal that passes information 

is 1 to 5 V. If you measure across A and B, you should 

get 0 VAC, and 1 to 4 VDC. There should be 0 VAC 

and 0 VDC between either A on B and the shield. If 

you are getting more than this, check for runs against 

high voltage, for exposed wires, to see if grounding at 

only one side, or that you have used dedicated power 

for the controllers or if you have reversed power on a 

Controller(s).

NOTE: By using wire cable consisting of one triple 

of twisted shielded wire and one pair of unshielded 

wire, you can run power to controllers and run 

communications wire in the same cable. Part # 

PM2000A
NOTE: Be sure to check any local codes to confirm 

the wire choice meets the code.
 

The QD2010a requires at least one QD1010-USB (USB/

RS485 communications converter) be attached directly 

to the USB port on the side of the unit.  The controller 

network wiring connects to the QD1010-USB as 

described above. Up to 3 controllers can be placed on 

the built-in USB port.

Setup Page                              

Once you have made connection and have logged in 

you are able to configure the operation of the unit by 

selecting the proper parameters for your application. All 

Ubiquity Application software and functionality is 

accessed by logging into the Central Server  

(

www.ubiquitysystems.net) 

NOT by using this setup 

page.

 

INSTALLATION INFORMATION

This section contains installer and site related 

information. The information entered here is sent along 

to the central server when a site initially comes online 

to help identify the site to link it to the correct Ubiquity 

site. For the most part, this information is for reference 

purposes only, except for the Site Time. The Site Time 

is used by the local network and QD2010a until the 

Ubiquity central server performs a time synchronization 

with the site. 

 

NOTE: Be sure to set the time 5 minutes ahead of 

the actual time. This allows the correct time to be 

used when the gateway next resets its time. 

 

NOTE: Be sure to set the correct Time zone so that 

the site will correctly adjust the time during future 

time synchronizations with the central server. 

 

Once you are finished entering information in this 

section, click the Update Installation Info button.

Содержание QD2010a

Страница 1: ...mory Integrated 10 100 Ethernet controller with firewall capabilities Interface into Ubiquity Interface for configurations Remotely upgradable firmware User definable communication cycles SSL Secure Socket Layer enabled web pages Integrated controller addressing Supports up to 3 TCS Basys Controls devices Contents Description 1 Features 1 Material List 1 Programming 2 Prior Connection to Network 2...

Страница 2: ...n of the QD2010a by simply connecting it to a laptop or desktop PC Caution The QD2010a comes programmed with a default setup mode and functions as a DHCP server When setting up the unit be sure it is not connected to another DHCP enabled network Components diagram casing removed Not used Initial Configuration Before connecting the QD2010a to a LAN or WAN you must first configure the unit for opera...

Страница 3: ...if you do not or you are unsure connect to a UPS PK3100 To connect the QD2010a to a LAN Ethernet connect an Ethernet cable not included to the RJ 45 connection on the side of the unit Connect the other end to the LAN network hub Power adapter QD1010 USB To RS485 Control Network SIDE A SIDE C SIDE D LAN Ethernet HDMI if applicable USB VGA output if applicable 5V Power ETHERNET HUB Crossover Cable s...

Страница 4: ... 5 V If you measure across A and B you should get 0 VAC and 1 to 4 VDC There should be 0 VAC and 0 VDC between either A on B and the shield If you are getting more than this check for runs against high voltage for exposed wires to see if grounding at only one side or that you have used dedicated power for the controllers or if you have reversed power on a Controller s NOTE By using wire cable cons...

Страница 5: ...and the drop down menu will be left at Disabled If a proxy is required you can select the correct type from the drop down and then enter all the related details in the fields that appear Once you are finished entering information in this section click the Update Commissioning Info button Unlike the other section updating this section may cause the unit to reboot automatically within 5 minutes of c...

Страница 6: ...ccess it once the unit is communicating with the central server In that case TCS Basys Controls technical support staff will instruct you on how to access this page UBIQUITY CONNECTION STATUS This section displays the status of the connection between the QD2010a and the central server You have 3 options for the message that will appear her 1 Error No Route to Host this means the unit does not curr...

Страница 7: ...cted if this method is being used You will also need to reconfigure the COM port when finished NOTE When using this second method for changing addresses ALL controllers connected to that COM port will be given the same address So there must only be ONE controller connected to the network NETWORK CHANGE LOG In this subsection you will be able to view all address changes performed using the QD2010a ...

Страница 8: ...010a 2 Apply power 3 If the QD2010a has not been pre programmed it can be programmed at this time 4 The unit is now ready for operation TROUBLESHOOTING No Communications with Controllers on the network Make sure the baud rate selection for the QD2010a is set to match the baud rate of all the controllers on each port network All controllers on the network must have a unique address excluding the ad...

Отзывы: