3
1. Notice before start-up
FY series controller has got the CE approvals as below:
LDV
:
D/N
EN61010-1
EMC
:
EN 55 022 1994 /A1
:
1995/ A2
:
1997
EN 61 000-3-2
:
1995 / -3-3
:
1995
EN 61 000-4-2
:
1995 / -4-3
:
1996 / -4-5
:
1995 / -4-6
1996 / -4-8
:
1993 / -4-11
:
1996/ EN 50 204
:
1995
Please confirm the specification of controller is to totally with your requirement before
using it, also read this manual in detail.
Danger
1. Danger!
Electric
Shock!
DON'T touch AC power wiring terminals when controller has been
powered!
Keep the power off until all of the wirings are completed!
Warning
1. Please confirm
that
the AC power wiring to controller is correct, otherwise it
will
cause
serious
damage
to the
controller. (
uTC52
connect
ed
to
Pin 1 and 6,
uTC 62, 72, 42, 92 to
Pin 1 and 2).
2. Be sure to use the rated power supply (AC85~265V or DC24V), otherwise it would be
cause
serious
damage
to the
controller.
3. Please
use correct
wir
ing as per diagram for
(Input, Output
etc
).
4. Use M3 screw-compatible crimp-on terminals with an insulation sleeve, as shown
below
3.2mm
3.2mm
Torque : 0.4 N.m (4kgf.cm)
5. Avoid installing controller in following
environment
:
I.
A place where the ambient temperature may
exceed
the range
0 to 50
℃
II. A place where the ambient humidity may
exceed
the range
from 20 to 90% RH.
III. A place where the contro ller likely to come into contact with water, oil,
chemicals, steam and vapor.
IV. A place where the controller is subject to interface
from
static
electricity, magnetism
, excessive vibration
and
electrical
noise.
6. For thermocouple (TC) input, use shield
ed
compensating lead wire.
7. For RTD input, use shield
ed
wir
ing
which ha
s
low resistance and
a close
resistance
match
between the 3 wires.