14.2 Calibration
:
SET 2.2 = 1
ANL1=0
ANH1=5000
LSPL=0
USPL=5000
Adjusts "ANL1" until PV Display = 0
Inputs 4mA
Inputs 20mA
Adjusts "ANH1" until PV Display = 5000
Inputs 4mA to CHECK LOW
Inputs 20mA to CHECK HIGH
OK ?
Set the range you want
:
LOW =
LSPL
,
HIGH =
USPL
Ex
:
Low = -20.0
,
High = 50.0
SET
LSPL
= -20.0
,
USPL
= 50.0
,
DP
:
000.0
To display ANL1 &
ANH1
at
INPUT
Level
Return
User
Level to view
the changing of PV
YES
NO