![TCL u Series Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/tcl/u-series/u-series_operation-manual_824568027.webp)
26
8.5.2
Description of operation
1. There are 2 patterns can be used
,
each pattern contains 8 segments.
2. Terminologies
Pattern
:
A program consists of some steps.
Ramp status
:
The status with changing SV.
Soak status
:
The status with fixed SV.
3. Operating
I.
"KEY" function (no changing parameter)
(RUN)
:
Start program procedure
,
PRO
LED in panel start flicking.
(HOLD)
:
Suspend program procedure
,
PRO
LED in panel will stop
flicker but still light on.
+
SET
(JUMP)
:
Jump to previous segment.
+
SET
(RESET)
:
Reset program procedure
,
PRO
LED in panel will off.
II. Alarm
Function
:
ALD1
= “07”(Segment end alarm)
,
AL1
=“2”(It means when segment 2 end,AL1 will act)
,
ALT1
=“00:10”(Relay on time is 10 seconds).
*
In this case
,
when program proceeds to segment 2 end
,
the relay of AL1 will
be on 10 seconds.
III. END
function
:
The Controller doesn’t have END order, so if program procedure is less than 8
segments, please set the last segment’s OUT to “0”. Program will end in this
segment. Otherwise
,
it will proceed 8 or 16 segments.
IV. Linking
Function
:
PTN
=1 proceed pattern 1
,
contains 8 segments.
PTN
=2 proceed pattern 2
,
contains 8 segments.
PTN
=0 linking proceed pattern 1 and 2 totally 16 segments.
(Please set PTN1 and PTN2 at first
,
and then set PTN to 0)
V. Other
function(
*
refer to LEVEL 4)
SET 8_1=1 Program repeats.
SET 8_2=0 No power failure function.
SET 8_2=1 Enable power failure function.
(When power shut down and on again
,
the controller will start from the
segment which is near PV)
SET 8_3=0 Program starts from 0.
SET 8_3=1 Program starts from PV.
SET 9_2=0 Timer Unit = “Hour : Minute”
SET 9_2=1 Timer Unit = “Minute : Second”