DC Inverter Air
Recharging Amount: R (Kg) = (L1‐L2)×A/m)
Where, L1— actual length of liquid pipe
(m);
L2— actual standard length for delivery
(m) (see the Recharging label of the
outdoor unit)
A—The refrigerant to be added for pipe m, see the following table.
Pipe specification
φ6.4
φ9.5
φ12.7
φ15.9
φ19.1
φ22.2
Add R410A for an increase
of one meter
22
65
110
170
250
350
(g/m)
C. Correctly measure the refrigerant using the scale and filler tank;
D. Connect the filler tank, instrument manifolds and maintenance valve of liquid pipe of outdoor unit (at
high‐pressure side) and charge the refrigerant in its liquid state. The air in the hose and manifold
must be removed by the refrigerant before the recharging operation.
E. After completing the recharging operation, check whether there is refrigerant leakage at the flare
positions of indoor/outdoor units;
F. Record the adding amount of refrigerant onto the refrigerant indicator nameplate of outdoor
unit; G. The recharged amount shall be measured by the electronic scale.
9. Heat Insulation Works
9.1. Insulation Materials and Thickness
1) Insulation Materials
The insulation materials shall use the materials that can withstand the temperature of pipes: the
withstand pressure at high‐pressure side shall not be less than 70
℃
and at low‐pressure side shall
not be less than 120
℃
.(no such a requirement at the low‐pressure side for single‐cold unit) For
example: heat‐pump type – heat‐resisting polyethylene foam (over 120
℃
)
Single‐cold type – foaming polyethylene (over 100
℃
).
2)Thickness selection of insulation materials:
Pipe diameter (mm)
Thickness of Insulation Materials
Refrigerant Pipe
Φ6.4‐Φ25.4
10mm
Φ28.6‐Φ38.1
15mm
Drain Pipe
Inner diameter Φ20‐Φ32
10mm
9.2. Heat Insulation of Refrigerant Pipes
1)
Operation Sequence
A. The non‐welded or non‐connected positions shall be subject to the heat‐insulation treatment prior
to the laying of pipes;
74
/
113
Содержание TCA-18HRA/DVO
Страница 1: ...Technical Manual for DC Inverter Air Conditioner 1 113...
Страница 13: ...DC Inverter Air 1 4 Electrical Wiring Diagram 13 113...
Страница 14: ...DC Inverter Air 1 5 Air Velocity and Temperature Distributions Airflow velocity 14 113...
Страница 22: ...DC Inverter Air 22 113...
Страница 28: ...DC Inverter Air 2 3 Service Space 2 4 Wiring Diagrams 28 113...
Страница 41: ...DC Inverter Air 3 2 Wirin g Diagra ms 41 113...
Страница 42: ...DC Inverter Air A irflow velo city Discharge angle 60 FLOOR 42 113...
Страница 43: ...DC Inverter Air Airflow velocity Temperature 43 113...
Страница 64: ...DC Inverter Air 7 2 Electrical Wiring Diagram 2 1 TCA 36HRA DV 64 113...
Страница 65: ...DC Inverter Air 2 2 TCA 48H RA DV3 TCA 60HRA DV3 65 113...
Страница 66: ...DC Inverter Air 2 2TCA 18HRA DVO TC A 24HRA DVO 66 113...
Страница 82: ...DC Inverter Air 82 113...