11.3 Examples of repairing
11.3.1 Display E1 or E2
Reasons:
1) The sensor connection terminal loose or not plugged in.
Wall type
Cassette type/Duct type
Solution:
Check the connecter of sensor and slot (CN6, CN6-1, CN6-2), if loose or not plugged in,
please connect again.
2) Room temperature sensor (IRT) and Indoor pipe (coil) temperature sensor (IPT) damage (short or
broken).
Solution:
check the resistance of the sensor wall type R (25
℃
)
=
5 kΩ, cassette and duct type R
(25
℃
)
=
5 kΩ, if short or broken please replace it.