Air Conditioner Service Manual
40
10. Installation manual
10.1 Installation Details
Connecting pipe length
Model
Pipe size(Inch)
Liquid
Gas
9K
1/4
3/8
12K
1/4
3/8
18K
1/4
1/2
Mode
Standard length: m
Refrigerant piping
Max. length: m
A
Additional refrigerant
Calculation: ×g=20g/m(A-5m)
9K
5.0
20
15g/m
12K
5.0
20
15g/m
18K
5.0
20
20g/m
Connecting cables
The power cord should be selected according to the following specifications sheet.
Appliance Amps
Wire Size
5
AWG21/0.75 mm2
10
AWG18/1.0 mm2
13
AWG15 /1. 5 mm2
18
AWG14/1.6 mm2
25
AWG12/2.0 mm2
30
AWG10/2.5 mm2
Outdoor unit
In door uni t
Pipe length is
20 meters Max.
be
le
ss
th
an
1
0m
H
ei
gh
t
sh
ou
ld
Outdoor unit
Indoor unit
Pipe length is
20 meters Max.
be
le
ss
th
an
1
0m
H
ei
gh
t
s
h
ou
ld