Air Conditioner Service Manual
42
To install, proceed as follows:
10.2.1 Installation of the mounting plate.
Wall split type:
1) By using a level, put the mounting plate in a
perfect square position vertically and horizontally.
2) Drill 32mm deep holes in the wall to fix the plate.
3) Insert the plastic anchors into the hole.
4) Fix the mounting plate by using the provided
tapping screws.
5) Check that the mounting plate is correctly fixed.
Note: The shape of the mounting plate may be
different from the one above, but installation
method is similar.
Cassette and Duct type:
Wooden construction
Put the square timber over the roof beam, then install the
hanging screw bolts.
Timber over the beam
Roof beam
Hanging Screw
Ceili ng
B olt
For finished concrete bricks
Install the hanging hook with expansible bolt into the
concrete deep to 45~50mm to prevent loose.
New Concrete Bricks
Inlaying or embedding the screw bolts.
(Blade shape (Slide insertion)
insertion)
(Pipe hanging and embedding screw bolt)
Steel roof beam structure
Install the supporting angle steel.
Overhanging the indoor unit
Adjust the gasket (down side) to 90mm over the
ceiling.
Install the hanging bolt into T groove of the hanging
tool. Overhang the indoor unit and ensure it is level
using a level indicator.
300mm
500m
m
2000mm
300mm
50
0mm
Steel bar
Embedding screw bolt
Hanging screw bolt
Hanging bolts
Supporting
angle steel
Hanging Bolt
Nut (Up Side)
Gasket (Up Side)
Installing Ear
Nut (Down Side)
Down sid e of the ceiling
Gasket (Down Side)
90
m
m
Содержание TACM2O-14HIA
Страница 14: ...Air Conditioner Service Manual 13 6 Wiring diagram INDOOR UNIT Wall split type Cassette Duct type...
Страница 15: ...Air Conditioner Service Manual 14 OUTDOOR UNIT ONE TO 2 TYPE ONE TO 3TYPE...
Страница 16: ...Air Conditioner Service Manual 15 ONE TO 4 TYPE...
Страница 23: ...Air Conditioner Service Manual 22 CASSETTE TYPE INDOOR UNIT...
Страница 30: ...Air Conditioner Service Manual 29 OUTDOOR UNIT 10 11 12 8 9 7 6 5 17 13 14 16 15 19 18 20 21 23 4 3 2 1 22 24...