HGP Kit Manual
4.0 Installation
11
Filter Wire Sizing
Wire Sizing
Wires need to be sized based on current to be carried, wire insulation temperature rating, panel
temperature rating, bundling of wires, and appropriate codes and standards. Wire size between the
power source and the filter line reactor, as well as the line reactor and the drive input, are based
rated filter line current. Wire size in the branch circuit is based on rated tuned circuit current. If the
capacitor wiring is split into separate capacitor branches, the current each branch carries is
proportional to the value of capacitance in each branch.
Table 3 – 208 V, 60Hz, HGP
HGP Rating (HP) Tuned Circuit Current (A)
Line Current (A)
5
10.3
16.7
7.5
17.1
24.2
10
25.7
30.8
15
34.4
46.2
20
42.9
59.4
25
51.5
74.8
30
68.6
88
40
103
114
60
129
169
75
154
211
100
205
273
150
310
396
200
412
528
250
515
660
300
641
792
Table 4 – 240 V, 60Hz, HGP
HGP Rating (HP) Tuned Circuit Current (A)
Line Current (A)
5
10.3
15.2
7.5
13.7
22
10
17.1
28
15
25.7
42
20
34.4
54
25
42.9
68
30
51.5
80
40
68.6
104
50
77.0
130
60
103
154
75
129
192
100
154
248
125
205
318
150
257
360
200
308
480
250
410
604
300
513
722
400
641
954