Ludwig-Rinn-Str. 10-14
D - 35452 Heuchelheim
Phone: +49-(0)641-96284-0
Fax: +49-(0)641-96284-28
www.tci.de
Seite 29 von 40
3.6 KNX/EIB Interface (Optionally)
Purpose
This board is used to establish a connection between ambiento
and the installation bus EIB/KNX. The USB connector has a
galvanic separation from the EIB/KNX bus. The circuit is
compatible with KNX medium TP1 (EIB), the firmware supports
protocol EMI1.
For manual changing of the KNX adress you can
download under
knxtool.ambiento.de
a software tool
Assignment connectors
USB jack (K1)
Connection of USB plug (B
series)
USB connector (K2)
1: AVCC Supply USB +5V
2: D- Data line USB
3: D+ Data line USB
4: AGND Ground USB
Connector LEDs and learning button (K3)
1: LED learning mode
Connection of external learning LED to ground, multiplier
(2,2 kOhm) equipped onboard, identical function as learning LED on
board;
2: Button for learning mode
Connection of external learning button to ground, no pull up resistor
required, identical function as learning key on board;
3: LED USB
Connection of external LED for signalling state of USB
LED steady light: USB supply is present, no communication;
LED flickers: Communication over USB;
LED off: Supply failed over USB, controller is not operating;
4: GND
Ground USB controller
Connector signalling state
1: GND KNX Ground EIB/KNX bus
EIB/KNX bus (K4)
2: LED KNX Connection of external LED for signalling state of
EIB/KNX bus
LED on: Supply over EIB/KNX present;
LED off: EIB/KNX bus not connected;
Connector EIB/KNX bus
Standard connector, grid dimension 2,54 mm
small (K5)
1: - Ground EIB/KNX bus
2: + Supply / communication EIB/KNX bus
Connector EIB/KNX
Connector EIB/KNX (Type 5.1, Wago)
bus large (K6)
· 1: - Ground EIB/KNX bus
· 2: + Supply / communication EIB/KNX bus