4.7 Other Connections

4.7.1 Auxiliary output contact

Two groups of auxiliary output contact are available on Energier Apollo. The default setting of this 
auxiliary output contact is battery low voltage. It will activate once the voltage has been detected 
dropping to preset level. This auxiliary output contact can be used for load management or other 
function. 
However the contact can be programmed for all kinds of other applications, for example as a starter 
relay for a generator, user can set programmable relay as AGS on Rapconfig software with PC. Also 
the auxiliary output contact can be configured to control external cooling fan with programmed for 
“Fan running”.
Through LCD panel or Rapconfig, other functions can be configured for these contacts. The 
maximum contact load is: 30VDC 2A

4.7.2 Dry input

The Auxiliary input is connected by default with a short-circuit wire for EPO (emergency power off) 
control. After the wire is removed, Energier Apollo stops working. If there is no special case, do not 
remove the wire. Auxiliary input can be connected an external normal closed switch for EPO.

Dry In

NC2

COM2

NO2

NC1

COM1

NO1

Auxiliary in

Auxiliary out

Содержание Energier Apollo CH2.0M

Страница 1: ...lo all in one inverter User Manual CH2 0M 24V 2000W 40A MPPT 100V 60A CH2 0S 48V 2000W 20A MPPT 150V 60A CH3 0S 48V 3000W 30A MPPT 150V 60A CH4 0S 48V 4000W 40A MPPT 150V 60A TBB POWER Co Ltd A1 1 www...

Страница 2: ......

Страница 3: ...cidental which might arise out of the use of such information TBB offers standard warranty with its products taking no responsibility for direct or indirect loss due to equipment failure This manual d...

Страница 4: ...a view 3 2 2 Wiring area view after remove upper service panel 1 2 Precaution regarding battery operation 1 1 General Index 1 1 3 4 4 5 6 7 7 8 10 10 13 13 13 14 14 15 4 Installation 4 1 Pre installat...

Страница 5: ...ystem information 5 4 4 System alarm 5 4 5 System setting 5 4 6 System control 5 4 7 Statistical information for PV production 5 4 8 Event logs 5 5 Performing equalization charging 6 1 Buttons functio...

Страница 6: ...t AGS function 6 9 How to restore factory setting 6 10 Configurations by computer tool Rapconfig 7 Trouble shooting table 8 Maintenance 9 Technical data 6 7 How to program trigger source of dry output...

Страница 7: ...panel to PV input of the inverter 6 Please use the shortest cable to connect and ensure the secure connection 7 While connecting please secure the connection and avoid short cut between positive termi...

Страница 8: ...sidual Current Monitor RCM device is used for protection in case of direct or indirect contact only a RCD or RCM of Type B is allowed on the supply side of this product This manual contains informatio...

Страница 9: ...utions should be observed when working on batteries a Remove watches rings or other metal objects b Use tools with insulated handles c Wear rubber gloves and boots d Do not lay tools or metal parts on...

Страница 10: ...ht gauge and being connected well and tightly Smaller diameter and broken cables are not allowed to use Warning to avoid fire make sure to keep Energier Apollo far from inflammable and explosive subst...

Страница 11: ...r choosing Energier Apollo of which can be used to compose various hybrid power system The product is delivered with following equipments 2 Description of main function Energier Apollo Battery Voltage...

Страница 12: ...in accordance with the setting Energier Apollo series consists of matrix LCD display function user can monitor Energier Apollo operation status on LCD interface also user can use LCD interface to rese...

Страница 13: ...llo is suitable for heavy inductive load like fridge coffee maker microwave power tools air conditioner etc High surge power capability In the event of a grid failure or shore generator power being di...

Страница 14: ...erature is a key factor in correct charging the charging formula must be adjusted automatically and in real time according to the actual battery temperature to ensure that batteries are fully charged...

Страница 15: ...This will result in a weak cell which can reduce the overall capacity of battery in turn To improve the life and performance of these types of battery Energier Apollo includes a manual equalization pr...

Страница 16: ...r Apollo will switch off in case of load is less than preset level and will resume after the power reach the preset level The entry level of power save mode can be programmed through LCD display and s...

Страница 17: ...er through running the configuration software Complete system protection Energier Apollo is being protected against many failures through hardware and software including overload protection overheat p...

Страница 18: ...lar Mode solar energy provides power to the AC loads as first priority If solar energy is not sufficient to power all connected AC loads battery will supply power to the load at same time Grid provide...

Страница 19: ...Energier Apollo User Manual 13 3 Structure 3 1 Product drawing 144 00 275 00 117 8 514 00...

Страница 20: ...on Kinergy data logging stick installation position Grand for PV cable Main switch 1 3 2 Output circuit breaker Input circuit breaker Gland for BTS VS etc communication cable 5 6 4 No 7 9 8 11 12 10 G...

Страница 21: ...nal 13 15 14 RS485 terminal AC output 2 terminal N PE L from left to right AC input terminal N PE L from left to right 17 18 16 No 19 21 20 23 24 22 Battery terminal VS terminal VS VS from left to rig...

Страница 22: ...ose as possible to the battery bank These should be a clear space of at least 20 cm around the equipment for cooling Working temperature 20 60 derating above 25 Storage temperature 40 85 Relative Humi...

Страница 23: ...as the 230V external mains or a generator The neutral of this equipment cannot be connected to the earth Otherwise the equipment will be burned or user will get electric shocked in case of reversed co...

Страница 24: ...ing the battery Maximum torque of battery terminals 12Nm Avoid shorting the battery cables Reverse polarity connection to and to will cause damage to the product Proceed as following to connect the ba...

Страница 25: ...he battery polarity positive BAT and the minus BAT see section 3 2 wiring area description Reverse polarity connection to and to will cause damage to the product Secure the nuts tightly in order to re...

Страница 26: ...This is a Safety Class I product supplied with a protective grounding terminal Uninterruptible protective grounding must be provided at the AC input and or output terminals and or chassis grounding po...

Страница 27: ...arth leakage circuit breaker and a fuse or circuit breaker rated to support the expected load must be included in series with the output and cable cross section must be sized accordingly On AC OUTPUT2...

Страница 28: ...s the model you install the wrong PV panel voltage can destroy equipment and it is out of warranty Please double confirm polarity of PV input And ensure PV max current does not exceed rated PV chargin...

Страница 29: ...etic circuit breaker and cable cross section must be sized accordingly Battery Voltage 36 cells Voc 23V 54 cells Voc 34V 24V Battery Voltage 24V 48 cells Voc 31V 60 cells Voc 38V 4 2 max best max best...

Страница 30: ...elay for a generator user can set programmable relay as AGS on Rapconfig software with PC Also the auxiliary output contact can be configured to control external cooling fan with programmed for Fan ru...

Страница 31: ...d the positive of voltage sensor should be connected to the positive of service battery Wrong connection will damage Energier Apollo Please secure the sensor on battery terminal 4 7 4 Battery Voltage...

Страница 32: ...nal Notice to avoid damage of Kinergy Energier Apollo should be switched off before inserting or removing it At the bottom of the enclosure there is a Kinergy port See section 3 2 wiring area descript...

Страница 33: ...p to indicate the situation Energier Apollo has built in with power backup and solar mode working mode The default working mode is power backup mode Upon AC input is resumes and matches the quality re...

Страница 34: ...tor Description Bypass Status Extinguish Illuminate Extinguish AC input is not present AC load is powered by AC input Inverter Flash Illuminate Inverter is work on power save mode Inverter is switched...

Страница 35: ...time operation status In the meantime the LCD screen provides basic system information history records allows user to set up system and execute equalization charge Button Description of function Setti...

Страница 36: ...age up and page down button to check working status and real time data such as following 5 4 2 Status Note indicates the power flow Booting Main AC IN 55 6V 230V 230V PV 100 110V LOAD AC input 220VAC...

Страница 37: ...rmation and user can clear event logs 5 4 4 System alarm System setting includes normal setting General and advanced setting Advanced please refer Chapter 6 for details 5 4 5 System setting From syste...

Страница 38: ...ogs Enter 2019 08 19 14 39 10 Battery under voltage protection 1000 2000 Though the statistics sub menu of history user can find statistical information of PV production such as daily and monthly and...

Страница 39: ...battery type During equalization the battery generates potentially flammable gases Follow all the battery safety precautions listed in this guide Ventilate the area around the battery thoroughly and...

Страница 40: ...onnection of RS485 USB converter The default setting of max equalization time is 30 minutes Step 4 Enable equalization through LCD interface Step 5 Energier Apollo will start a routine charging cycle...

Страница 41: ...second Energier Apollo will return to main menu from any sub menu page Press page down and page up button to switch between the items then press enter button Note the password is 1234 Possibly the st...

Страница 42: ...C Lead acid 43 2VDC LFP 46 5VDC Descriptions To configure load power source priority details as chapter 5 2 Power backup Solar mode AGM GEL traction semi traction flooded LFP lead carbon AGM 50AH Powe...

Страница 43: ...g GEL 10 30 15 AGM 10 30 Traction 10 30 Semi traction 10 30 Flooded 10 30 LFP 10 100 Lead carbon 10 60 LFP 28 2VDC 53 2VDC 28 2VDC 56 4VDC Flooded 30 4VDC 60 8VDC Semi traction 29 4VDC 58 8VDC Tractio...

Страница 44: ...ld Enable or disable the alarm of AC input voltage abnormal Enable disable Enable AGS Battery Low Fan running Inverter Fault Output short Over charge Overload Over temperature AC input connect Battery...

Страница 45: ...ollowing terms I charging rate x C the battery capacity you choose multiply by charging rate Or Max Charger Capacity of the model you choose For example for model CH2 0S with AGM battery capacity of 2...

Страница 46: ...the right setting General Advanced Enter ESC Page down x 10 Page up Rated voltage 230V Inverter to grid threshold 48V Ambient temperature 25 C Discharge current VS discharge time curve Terminal voltag...

Страница 47: ...g figure is the relationship between discharge depth and cycle life of a GEL battery for reference Ambient temperature 25 C The depth of discharge critically affects the number of cycles which a batte...

Страница 48: ...y for reference General Advanced Enter ESC Page down x 11 Page up Rated voltage 230V Grid to inverter threshold Bulk finished Continuous current voltage charge characteristic Charged volume Charging t...

Страница 49: ...nced Enter ESC Page down x 3 Page up 6 4 2 AC input current limit setting When Energier Apollo is connected to current limited source for example15A MCB the AC input current shall be set to match the...

Страница 50: ...rging parameters should be complied with battery datasheet otherwise battery may be damaged 2 The temperature compensation function is only suitable for lead acid battery The compensation coefficients...

Страница 51: ...exact measure of the battery SOC is almost impossible with only electrical parameter It may vary according to discharge current battery healthy etc Through low voltage setting items you can configure...

Страница 52: ...g AGS generator condition For example as a starter relay for a generator user can set programmable relay as AGS on Rapconfig software with PC 6 8 How to get AGS function For restore factory setting pl...

Страница 53: ...e changed with LCD interface see section 6 2 default setting For changing settings with the computer the following is required Rapconfig software or the appropriate Assistant s can be downloaded free...

Страница 54: ...ight up check LCD alarm interface for detail The DC input is under voltage AC input wire loose connection Secure the connection Wrong connection of N and PE of AC input Change to weak grid Gen mode wi...

Страница 55: ...lue Adjust the float voltage to the correct value A defective battery The battery is too small Replace the battery Reduce the charging current or use a battery with a higher capacity The battery is to...

Страница 56: ...ry connection Replace battery fuse Check PV voltage The battery is not fully charged Large ambient temperature difference between charger and battery Make sure that ambient conditions are equal for ch...

Страница 57: ...AC settable 50Hz 0 05 50 60Hz settable Output voltage Total harmonic distortion 3 14 17 20 14 3 5 3 5 4 5 5 Zero load power W Zero load power PS mode W Typical transfer time Transfer switch A AC input...

Страница 58: ...l settable 40 85 20 60 CH2 0S CH3 0S CH4 0S X2 programmable Storage temperature range Mechanical Data AC charger Solar charger MPPT 35 40 20 30 40 60 60 60 60 100 80 90 100 Solar charger type Nominal...

Страница 59: ......

Страница 60: ...TBB POWER Co Ltd Web www tbbpower com Tel 86 592 5212299 Fax 86 592 5796070 Email service tbbpower com...

Отзывы: