The AC input cable can be connected to the terminal block “AC INPUT”. From left to right: “N”
(neutral), “PE” (earth) and “L” (phase).
The AC input must be protected by a fuse or magnetic circuit breaker, and cable cross section
must be sized accordingly. If the input AC supply is rated at a lower value, the fuse or magnetic
circuit breaker should be down sized accordingly.
The AC output1 cable can be connected directly to the terminal block “AC OUTPUT1”. From left
to right:“L” (phase), “PE” (earth) and “N” (neutral).
An earth leakage circuit breaker and a fuse or circuit breaker rated to support the expected load
must be included in series with the output, and cable cross section must be sized accordingly.
On AC OUTPUT2 terminal, equipment is connected that only operate if AC voltage is present on
AC INPUT, e.g. an electric boiler or an air conditioner.
The AC output2 cable can be connected directly to the terminal block “AC OUTPUT2”. From left
to right: “N” (neutral), “PE” (earth) and“L” (phase).
AC INPUT
AC OUTPUT1
AC OUTPUT2
The terminal blocks can be found on the printed circuit board, see section 3.2 wiring area description.
Do not invert neutral and phase when connecting the AC cables.
Procedure
AC OUTPUT1
AC INPUT
L
PE
N
L
PE
N
L
PE
N
AC OUTPUT2