X4 AC Drive User’s Manual
Chapter 7: X4 Parameters
1428D-0607
- 79 -
© 2007 TB Wood’s All Rights Reserved
programmed into this parameter can be from 0 to 65,535, and can represent time, pulse counts,
analog voltage thresholds, analog current thresholds, or digital comparison values.
Table 7-6: Seq Count Definition Based on Cntl Parameter Configuration
Bits
4,5,6 of
Seq Cntl
Description of Seq Count Function
000
Time Base - The current sequencer state will last for a time interval equal to the number “Seq Count
X” multiplied by the time base configured in the Seq Appl parameter.
Seq Appl Setting
Time to Advance
Maximum Sequence Time
1 sec Base
(1 sec) * (Seq Count X)
18.2 hours
.1 sec Base
(0.1 sec) * (Seq Count X)
1.82 hours
0.1 sec Base
(0.01 sec) * (Seq Count X)
10.92 minutes
001
Pulse Count - The current sequencer state will last until the number of pulses programmed into “Seq
Count X” is detected on terminal Vin1.
010
Low Analog Voltage Threshold - The active sequencer state lasts until the voltage signal applied to
terminal Vin2 is < a value programmed into “Seq Count X.” The value programmed into “Seq Count
X” should be the percentage of input after span and offset are applied (where 100.00% = 10000).
Note: The % of analog input after span and offset can be read in parameter 912, Vin2 Status.
011
High Analog Voltage Threshold - The active sequencer state lasts until the voltage signal applied to
terminal Vin2 is > a value programmed into “Seq Count X.” The value programmed into “Seq Count
X” should be the percentage of input after span and offset are applied (where 100.00% = 10000).
Note: The % of analog input after span and offset can be read in parameter 912, Vin2 Status.
100
Low Analog Current Threshold - The active sequencer state lasts until the current signal applied to
Cin terminals is < a value programmed into “Seq Count X.” The value programmed into “Seq Count
X” should be the percentage of input after span and offset are applied (where 100.00% = 10000).
Note: The % of analog input after span and offset can be read in parameter 911, Cin Status.
101
High Analog Current Threshold - The active sequencer state lasts until the current signal applied to
Cin terminals is > a value programmed into “Seq Count X.” The value programmed into “Seq Count
X” should be the percentage of input after span and offset are applied (where 100.00% = 10000).
Note: The % of analog input after span and offset can be read in parameter 911, Cin Status.
110
Digital Comparison - The active sequencer state lasts until the binary value of digital inputs
configured to Seq1, Seq2, and Seq3 is equal to the value programmed into "Seq Count X."
Note: For this option to work, "DIx Configure" parameters must be set to "Seq1," "Seq2," and "Seq3.”
Seq Count
Digital Input Terminals
Description
Seq1
Seq2
Seq3
0
0
0
0
No input active
1
1
0
0
Seq1 active
2
0
1
0
Seq2 active
3
1
1
0
Seq1 & Seq2 active
4
0
0
1
Seq3 active
5
1
0
1
Seq1 & Seq3 active
6
0
1
1
Seq2 & Seq3 active
7
1
1
1
Seq1, Seq2, Seq3
active
111
The sequencer will never advance if this option is selected.