X4 AC Drive User’s Manual
Chapter 5: Programming with the X4 Keypad
1428D-0607
- 32 -
© 2007 TB Wood’s All Rights Reserved
Program mode is entered by stopping the X4 drive and pressing the Program (PROG) key for
Level 1 access; or holding down SHIFT while pressing PROG for Level 2 access. Pressing and
holding the Enter key and then pressing the Program key will show only those parameters that have
been changed from the factory defaults. Table 5-2 describes the function of the keys in Program
mode.
Table 5-2: Function of Keys in Program Mode
Press this key to have the drive enter Program mode and have Level 1 parameters available. (To
access Level 2 parameters, hold down SHIFT while pressing this key; to access Macro mode, hold
down the PROG key for more than 3 seconds.) Once Program mode is active, pressing this key at
any time returns the drive to the Operation mode. If an Access Code has been programmed, it must
be entered to proceed with programming. See Parameter
NOTE: To see what parameters have changed from the factory default, press ENTER + PROG. If the display flashes
“Factory Defaults,” no parameters have changed.
In the Program mode, pressing this key scrolls forward through the parameters. If the P indicator is
flashing, it increases the value of the parameter. To change the scroll rate, hold the SHIFT key at
the same time to increase the scroll rate; release the SHIFT key to return to the normal scroll rate.
Press the ENTER key to store the new value.
In the Program mode, pressing this key scrolls backward through the parameters. If the P indicator
is flashing, it decreases the value of the parameter. To change the scroll rate, hold the SHIFT key
at the same time to increase the scroll rate; release the SHIFT key to return to the normal scroll rate.
Press the ENTER key to store the new value.
NOTE: If the P indicator on the keypad display is flashing, momentarily pressing and releasing both the UP
and DOWN arrows at the same time restores the parameter to the factory default value. Press ENTER to store
the new value.
Pressing this key while a parameter is displayed allows that parameter to have its value changed by
use of the UP and DOWN arrow keys. The P indicator flashes to show that the parameter can be
programmed. See also the descriptions for the UP and DOWN arrows above to see how they work
with the SHIFT key.
This key must be pressed after the value of a parameter has been changed to store the new value.
The display will show “stored” for one second indicating that the new value has been entered into
memory.
NOTE: The X4 unit allows you to view only those parameters that have changed. If you press keypad keys ENTER
and PROGram simultaneously, only those parameters that have been changed from the factory defaults will be
shown.
Table 5-3: Function of Keys in Fault Mode
In Fault mode, pressing the UP and DOWN keys allows the operator to view the drive’s status
immediately before the fault occurred. Use the UP and DOWN arrows to scroll through the status
parameters. Press the STOP (Reset) key to return to normal operation.
See “Chapter 8: Troubleshooting” on page 83 for information about viewing Advanced Fault Codes
and understanding error codes.
The red STOP indicator functions as a reset button when in Fault mode. If the drive has stopped
because of a fault, this light flashes to call attention to the display.