X4 AC Drive User’s Manual
Chapter 4: Connections
1428D-0607
- 25 -
© 2007 TB Wood’s All Rights Reserved
4.6
Terminals Found on the X4 Control Board
4.6.1 Description of the Control Terminals
Figure 4-3 shows the control terminals found on the I/O board of the X4 AC drive. See page 6 for
specifications. Table 4-7 on page 26 describes the control terminals.
The drive’s control terminals are referenced to earth ground through a resistor / capacitor network.
Use caution when connecting analog signals not referenced to earth ground, especially if the
communications port (J3) is being used. The J3 port includes a common reference that can be
connected to earth ground through the host PLC or computer.
Figure 4-3: X4 Control Terminals
50150
11
120
71%
62
15,269
136%
50200
15
120
53%
62
15,269
102%
50250
18
120
42%
62
15,269
82%
50300
22
120
35%
62
15,269
68%
50400
29.8
60
53%
24
39,447
132%
50500
37.3
60
42%
24
39,447
106%
50600
45
60
35%
15
63,115
141%
50750
55
60
28%
15
63,115
113%
51000
75
60
21%
20
63,115
85%
51250
90
60
17%
10
94,672
102%
51500
110
60
14%
10
94,672
85%
52000
132
60
11%
10
94,672
63%
Table 4-6: X4 Dynamic Braking Capacity (Page 2 of 2) (* Note that the asterisked X4 model numbers cannot
have external braking added)
Model
KW
Standard
Resistance
Standard DB %
of Drive
Min. Allowed
Res.
Max. Peak
Watts
Max. Ext. DB %
of Drive