First Operation 

 

Open the water source and inlet maintenance valve and check for leaks.

 

 

Perform 2-3 flushing cycles as outlined below. 

 

Filter is ready for use. 

 

Flushing the filter 

 

The disc element needs to be cleaned when the 
head loss across the filter reaches 0.5-0.7 bar and 

the red pin is pushed out from the pressure 
indicator (Picture E). 

 

Turn the handle ¼+ of a turn until the stop 

(Picture F). 

 

Wait 15

30 seconds. 

 

Turn the filter handle back (Picture F). 

 

Open the valve 1/2" for 10 seconds and close 

(Picture G). 

 

Please note

: the strength required to turn the handle 

may vary according to water pressure, the water 

quality and its source.

 

 

 

 

 

 

 
 

 
 

 

 

 

 
 

 
 

 
 

 
 

 
 

 

               

 
              

 
 
 

 
 

 

 

 

 

 

 

Picture F 

Picture E 

Picture G 

Содержание TDS

Страница 1: ...Pg 3 TDS 2 1 action Installation and maintenance instructions Pg 5 TDS 1 action filters Periodic maintenance Pg 7 TDS 3 2 action Installation and maintenance instructions Pg 8 TDS 2 2 action Installat...

Страница 2: ...ize 2 3 Max working pressure 10 bar Max flow rate o 2 25 m3 h o 3 45 m3 h Available in 40 140 mesh Flushing flow rate o 2 bar 9 0 m3 h o 3 bar 12 m3 h Filtration area 1025 cm2 Construction materials o...

Страница 3: ...o 6 mm elbow to the threaded couplers 1 4 F o Connect 1 4 F to 6 mm elbow to the bottom of the indicator upstream high pressure o Connect 1 4 F to 6 mm adaptor to side of the indicator downstream low...

Страница 4: ...he head loss across the filter reaches 0 5 0 7 bar and the red pin is pushed out from the pressure indicator Picture E Turn the handle of a turn until the stop Picture F Wait 15 30 seconds Turn the fi...

Страница 5: ...1 4 F to 6 mm elbow to the bottom of the indicator upstream high pressure o Connect 1 4 F to 6 mm adaptor to side of the indicator downstream low pressure o Press fit the indicator to the sockets on...

Страница 6: ...he head loss across the filter reaches 0 5 0 7 bar and the red pin is pushed out from the pressure indicator Picture E Turn the handle of a turn until the stop Picture F Wait 15 30 seconds Turn the fi...

Страница 7: ...hereafter or if the flush cycle does not reduce the head loss filter does not flush effectively Open the tightening ring Picture H 2 counterclockwise pull it down and put aside Release the filter cup...

Страница 8: ...Connect two threaded couplers 1 4 F to filter body top 1 4 outlets o Connect two 1 4 M to 6 mm elbow to the threaded couplers 1 4 F o Connect 1 4 F to 6 mm elbow to the bottom of the indicator upstrea...

Страница 9: ...0 7 bar and the red pin is pushed out from the pressure indicator Picture E Open the bottom valve 2 Picture M Turn the handle of a turn until the stop Picture F Wait 15 30 seconds Turn the filter han...

Страница 10: ...t assembly o Connect two adaptors 1 4 F to 6 mm to filter body top 1 4 outlets o Connect 1 4 F to 6 mm elbow to the bottom of the indicator upstream high pressure o Connect 1 4 F to 6 mm adaptor to si...

Страница 11: ...5 0 7 bar and the red pin is pushed out from the pressure indicator Picture E Open the bottom valve 2 Picture M Turn the handle of a turn until the stop Picture F Wait 15 30 seconds Turn the filter ha...

Страница 12: ...hereafter or if the flush cycle does not reduce the head loss filter does not flush effectively Open the tightening ring Picture H 2 counterclockwise pull it down and put aside Release the filter cup...

Страница 13: ...rnal screen see Periodic Maintenance Secondary flush port cleaning outlined below o Clean discs manually see Periodic Maintenance Discs manual cleaning outlined below Filter handle is not turning o Ch...

Страница 14: ...hite or grey in color Combination of several deposits Perform cleaning in a properly ventilated area and use gloves safety glasses and protective clothes 6 1 Preparing the solution for immersing the d...

Страница 15: ...15 Ver_2 08 22 Step 1 Step 2 Release the filter clamp Remove the filter cup and then remove the O ring carefully Step 3 Step 4 Remove the dics Place the discs in HCL solution...

Страница 16: ...16 Ver_2 08 22 Step 5 Reassemble the filter After installing the discs back in the filter perform several flushing cycles...

Отзывы: