background image

VALVE INSTALLATION GUIDELINES AND COMPLIANCE

The valve must be installed so that it is readily accessible for commissioning and maintenance in accordance 
with the TMV2 scheme.  The valve must be installed with isolation valves on both the hot and cold water 

systems as close as possible to the valve; so as to allow the valve to be commissioned and tested correctly.    
The valve is fitted with integral check valve cartridges which command the water supply, therefore the 
thermostatic valve is protected against cross-flow due to unbalanced line pressures as required by the Water 
Supply (Water Fittings) Regulations 1999.

Most problems associated with the operation of thermostatic shower valves are caused by debris in the new 
pipe work getting into the thermostat. These problems are easily avoided by thoroughly flushing the pipe work 

BEFORE

 the shower valve is fitted.

WATER SUPPLY - (WATER FITTINGS) REGULATIONS 1999

This valve complies with the requirements of the above regulations and installation should be carried out in 

strict compliance with them.

MOUNTING BAR SHOWER VALVES

There are two methods of mounting the bar shower valve using the components supplied.  These methods are 
detailed on the following pages.  Please read the information below to determine the most suitable option for 
your installation:

Option 1 - Cranked connector

This option requires a 1/2” BSP female adapter (not supplied) to connect the cranked connectors to the pipe 
work.  This method is clip mounted and requires that the pipe work the valve is connected to be supported and 

be rigid.

Option 2 - Wall fixed connectors

This option requires a suitably strong wall construction to support the weight of the valve.  Suitable wall fixings 

must be used (not supplied).

COMMISSIONING

It is important that incoming water supplies conform to the requirements specified  for pressure and 

temperature. Assure that supply water conditions satisfy any guidance information for the control of bacteria 
and that the designation of the supplied valve suits the application.  Do not continue commissioning until 
supplies are correct and stable considering variation caused by other service users.

Use a calibrated thermometer for testing incoming and mixed water. 

1.

   Record temperature of the incoming hot and cold supply.

2.

   Record temperature of mixed discharge at maximum draw off rate.

3.

   Record temperature of mixed discharge at minimum draw off rate.

4.

   Isolate the cold water supply and measure the mixed water temperature as the cold water failure device 

reacts. This should deviate by no more than + 2°C of the initial maximum set point. Restore the cold supply 
and measure the stabilised mixed water temperature. This must not deviate by more than + / - 2°C of the 

initial set recorded result. Record these findings.

5.

   Record the measuring equipment used for the measurements.

The above records must be retained and updated during the service life of the TMV.

If there is a residual flow during the commissioning or the annual verification (cold water supply isolation test),
then this is acceptable providing the temperature of the water seeping from the valve is no more than 2oC

above the designated maximum mixed water outlet temperature setting of the valve.
Temperature readings should be taken at the normal flow rate after allowing for the system to stabilise. 
The sensing part of the thermometer probe must be fully submerged in the water that is to be tested.
Any TMV that has been adjusted or serviced must be re-commissioned and re-tested in accordance with the
manufacturers' instructions.

The installation of thermostatic mixing valves must comply with the requirements of the Water Supply (Water
Fittings) Regulations 1999.

IN SERVICE  TESTING & MAINTENANCE

It is a requirement that all TMV2 approved valves shall be verified against the original set temperature results 
once a year. When commissioning/testing is due the following performance checks shall be carried out.

Measure the mixed water temperature at the outlet.

The mixed water temperature at the terminal fitting must never exceed 46oC.
Carry out the cold water supply isolation test by isolating the cold water supply to the TMV, wait for five 
seconds if water is still flowing check that the temperature is below 46oC.
If there is no significant change to the set outlet temperature (±2°C or less change from the original settings) 
and the fail-safe shut off is functioning, then the valve is working correctly and no further service work is 
required.

 
Notes

If there is a residual flow during the commissioning or the annual verification (cold water supply isolation test), 
then this is acceptable providing the temperature of the water seeping from the valve is no more than 2oC 

above the designated maximum mixed water outlet temperature setting of the valve.
Temperature readings should be taken at the normal flow rate after allowing for the system to stabilise. 
The sensing part of the thermometer probe must be fully submerged in the water that is to be tested.
Any TMV that has been adjusted or serviced must be re-commissioned and re-tested in accordance with the 
manufacturers' instructions.
 

The installation of thermostatic mixing valves must comply with the requirements of the Water Supply (Water 
Fittings) Regulations 1999.

297mm

G1/2" BSP

129mm

150mm

KINETIC BOTTOM OUTLET BAR VALVE SHOWN

Содержание Kinetic SKN0601

Страница 1: ...for future reference KINETIC BAR SHOWER VALVE SKN0601 KINETIC BAR SHOWER VALVE SKN0706 TMV2 Buildcert Ref No RRTAV6 TMV2 Buildcert Ref No RRTAV7 REF KH TAV BSV10 07 10 V3 00 LOGIC BAR SHOWER VALVE SLG1302 LOGIC BAR SHOWER VALVE SLG1407 TMV2 Buildcert Ref No RRTAV13 TMV2 Buildcert Ref No RRTAV14 ...

Страница 2: ...nt deviation was recorded the test interval can be made equal to the maximum recorded interval to that point Note Check valve and strainer servicing must be conducted at each test interval If the recorded mixed water temperature is greater than 2 K from the initial recorded settings or the set point cannot be reached stabilised further action is required It is important to establish that the incom...

Страница 3: ...2 C of the initial maximum set point Restore the cold supply and measure the stabilised mixed water temperature This must not deviate by more than 2 C of the initial set recorded result Record these findings 5 Record the measuring equipment used for the measurements The above records must be retained and updated during the service life of the TMV If there is a residual flow during the commissionin...

Страница 4: ...es along with the filters are contained in the retaining nut The water supplies must be isolated remotely from the valve before removal To access the check valves unscrew the connecting nuts joining the mixer to the cranked connectors Unscrew the retaining nuts left hand thread from the mixer and check their conditions then reassemble and turn on water supply TMV2 approved valves shall be tested a...

Страница 5: ... threaded connector so the olive compresses and firmly locks the pipe in position Threaded connector Cranked connector Connecting nut Check valve Flow valve Retaining nut containing filters left hand thread KINETIC BOTTOM OUTLET BAR VALVE SHOWN KINETIC BOTTOM OUTLET BAR VALVE SHOWN ...

Страница 6: ...te the thermostat handle 5 until the desired hot water temperature is reached TMV2 regulations require a maximum temperature of no more than 44ºC 4 Replace the handle stop 4 with the stop lug positioned just to the right of the cartridge stop 6 See diagram below 5 Replace the handle 3 back onto the thermostat spindle 5 and secure via the handle arm 2 6 Test to ensure the desired maximum temperatur...

Отзывы: