THERMOSTATIC SHOWER BAR VALVE

Installation & aftercare instructions

Please retain for future reference

KINETIC BAR SHOWER VALVE

SKN0601

KINETIC BAR SHOWER VALVE

SKN0706

TMV2 / Buildcert Ref No:  

RRTAV6

TMV2 / Buildcert Ref No:  

RRTAV7

REF:

  KH.TAV.BSV10  |  07.10  V3.00

LOGIC BAR SHOWER VALVE

SLG1302

LOGIC BAR SHOWER VALVE

SLG1407

TMV2 / Buildcert Ref No:  

RRTAV13

TMV2 / Buildcert Ref No:  

RRTAV14

Содержание Kinetic SKN0601

Страница 1: ...for future reference KINETIC BAR SHOWER VALVE SKN0601 KINETIC BAR SHOWER VALVE SKN0706 TMV2 Buildcert Ref No RRTAV6 TMV2 Buildcert Ref No RRTAV7 REF KH TAV BSV10 07 10 V3 00 LOGIC BAR SHOWER VALVE SLG1302 LOGIC BAR SHOWER VALVE SLG1407 TMV2 Buildcert Ref No RRTAV13 TMV2 Buildcert Ref No RRTAV14 ...

Страница 2: ...nt deviation was recorded the test interval can be made equal to the maximum recorded interval to that point Note Check valve and strainer servicing must be conducted at each test interval If the recorded mixed water temperature is greater than 2 K from the initial recorded settings or the set point cannot be reached stabilised further action is required It is important to establish that the incom...

Страница 3: ...2 C of the initial maximum set point Restore the cold supply and measure the stabilised mixed water temperature This must not deviate by more than 2 C of the initial set recorded result Record these findings 5 Record the measuring equipment used for the measurements The above records must be retained and updated during the service life of the TMV If there is a residual flow during the commissionin...

Страница 4: ...es along with the filters are contained in the retaining nut The water supplies must be isolated remotely from the valve before removal To access the check valves unscrew the connecting nuts joining the mixer to the cranked connectors Unscrew the retaining nuts left hand thread from the mixer and check their conditions then reassemble and turn on water supply TMV2 approved valves shall be tested a...

Страница 5: ... threaded connector so the olive compresses and firmly locks the pipe in position Threaded connector Cranked connector Connecting nut Check valve Flow valve Retaining nut containing filters left hand thread KINETIC BOTTOM OUTLET BAR VALVE SHOWN KINETIC BOTTOM OUTLET BAR VALVE SHOWN ...

Страница 6: ...te the thermostat handle 5 until the desired hot water temperature is reached TMV2 regulations require a maximum temperature of no more than 44ºC 4 Replace the handle stop 4 with the stop lug positioned just to the right of the cartridge stop 6 See diagram below 5 Replace the handle 3 back onto the thermostat spindle 5 and secure via the handle arm 2 6 Test to ensure the desired maximum temperatur...