Attached Drawing-4
Indication under normal sensor conditions
Lighting out
Indication in th ecase of break detection
Lighting up
Lighting out: sensor
length indicated
Flashing: water leakage
location indicated
Indication in th ecase of water leakage detection
Indication for abnormal water leakage data output
In the following cases, an indication of “E01” is added:
①
Detector:Wiring conncetion between external analog input
devices is broken, or the input resistance for the external
analog input devices is more than 500Ω.
②
The internal power source inside the detecot for
4-20mA output is out of order.
Under normal sensor conditions
Indicating the
sensor length
Alarm LED status
Lighting
out
In the case of break detection
Indication for
break
Alarm LED status
Lighting
up
In the case of
Water leakage detection
Indicating
sensor length
Lighting
out
Lighting
out
Lighting
out
Flashing
Lighting
out
Lighting
out
Alarm LED status
Indicating the water
leakage location
Under normal
sensor conditions
Indicating the
sensor length
Lighting
out
Lighting
out
Lighting
out
Lighting
out
Lighting
out
Lighting
out
Alarm LED status
Indication for
error
In the case of break detection
Indication for
break
Lighting
out
Lighting
out
Indication for
error
Lighting
up
Lighting
up
Lighting
up
Lighting
up
Alarm LED status
In the case of
water leakage detection
Indicating the
sensor length
Lighting
out
Lighting
out
Lighting
out
Lighting
out
Lighting
out
Lighting
out
Lighting
out
Lighting
out
Alarm LED status
Water leakage
location indication
Indication for
error
Approved by Checked by Prepared by
Scale
Unit
Prepared on
-
/
-
mm
2010.04
N
am
e
D
ra
w
ing
N
o.
Water Leakage Location Detector
AD-AS-1LCM-A
Tatsuta Electric Wire & Cable Co., Ltd.
TTS-KS-W3288-0
Indication instruction-1
Flashing