6. Operation Check

 

 

6-1 Power-On 

 

     

When the detector is powered on, the Power Indicator LED and the 7-segment LED light up. (Refer to Drawing 12.) 

           

In the case that the LED does not light up, the detector may be out of order. Power off the detector promptly and contact 

the manufacturer.   

 

                                                                Drawing 12 Power-On Operation 

6-2 Check for Break Detection Function

 

 

1) 

After powering off the detector

, remove the water leakage sensor from the trunk terminal block and then 

power on the detector. 

           

             

2) The buzzer sounds, the Alarm Indicator LED flashes and the contacts (for break detection) function.             
3) The 3-digit, 7-segment LED indicates “---“.(Refer to Drawing 13.) 
4) After the operation check, 

power off the detector

 and then connect the sensor to the terminal block again. 

 

Drawing 13 Indication in the Case of Break Detection 

6-3 Check for Water Leakage Detection Function 

 

 

1) Drop tap water into the water leakage sensor. 
2) The buzzer sounds, the Alarm Indicator LED lights up and the contacts (for water leakage detection) function.

 

3) The 7-segment LED indicates as shown in Drawing 14. 

 

Example: in the case in which a sensor with a length of 250 meters connected and a point at 120 meters wetted.   

4) Wipe the tap water dropped on the sensor with dry rags, etc. and check that the water leakage status returns to 

normal. 

 

Drawing 14 Indication in the Case of Water Leakage Detection 

-7- 

Lighting  up 

Lighting  up 
 

Flashing:  The  water  leakage  location  is  indicated.   
Lighting  out:  The  sensor  length  isindicated. 

Sensor  length 

Lighting 

Lighting

 

Lighting

 

Lighting

 

Flashing 

Lighting  up 

Indication  of  the 

out 

Water  leakage 

location  indication 

Lighting 

out 

Alarm  LED  status 
 

out 

out 

out 

Содержание AD-AS-1LCM-A

Страница 1: ...TTS KS W5010 1 Water Leakage Location Detector AD AS 1LCM A Operation Manual TATSUTA Electric Wire Cable Co Ltd Electronics Division System Department...

Страница 2: ...arranty Before the delivery this product is subjected to strict quality control and inspection In the event of spontaneous failure resulting from defective manufacturing we will repair or replace it a...

Страница 3: ...r Water Leakage Detection Function 7 Operation Chart 7 8 7 1 Standard Operation Chart 7 2 Operation Chart When Alarm Hold Setting is Activated 8 Indication of Detector Number 9 9 Detection Sensitivity...

Страница 4: ...ght up when a break is detected Described on page 6 and 7 Alarm Cancel Switch Used for canceling alarm when the alarm hold setting is activated for indication or the control output contacts Buzzer Sto...

Страница 5: ...AD LS Sensor This will cause serious errors in the location detection function So pls make sure not to use or use together with any sensor other than AD LS sensor 2 2 Handling Precautions 1 Use the de...

Страница 6: ...power voltage outside the range of use may cause malfunctions and failure of the detector so care should be taken 5 2 Ground Connection Be sure to ground for interference prevention 3 Water leakage l...

Страница 7: ...onfiguration Element Configuration Electrode 1 0 33 mm 2 tinned soft copper wire covered with red plastic braided thread Electrode 2 0 5 mm 2 tinned soft copper wire insulated with green plastic Elect...

Страница 8: ...age and Break Contact Operation Alarm hold Turning the Operation switch 3 ON activates the alarm hold setting Refer to Drawing 8 1 2 3 4 6 7 8 5 Drawing 8 Alarm Hold Setting for Water Leakage and Brea...

Страница 9: ...ibed below Check the facilities Detector Wiring connection among external analog input devices is broken or the input resistance for external analog input devices is more than 500 The internal power i...

Страница 10: ...the terminal block again Drawing 13 Indication in the Case of Break Detection 6 3 Check for Water Leakage Detection Function 1 Drop tap water into the water leakage sensor 2 The buzzer sounds the Alar...

Страница 11: ...uzzer Stop Switch Buzzer sounding Control output contact water leakage COM NO Control output contact break COM NO Water leakage location indication Sensor length indication Water leakage location data...

Страница 12: ...larm indicator LED Buzzer Stop Switch Buzzer sounding Alarm cancel switch Control output contact water leakage COM NO Control output contact break COM NO Water leakage location indication Water leakag...

Страница 13: ...ctor Number Setting Switch and select a number that you want to indicate Refer to Attached Drawing 19 The detector number is indicated on the leftmost 7 segment LED 1 9 A B C D E F The factory setting...

Страница 14: ...rounding Check Subsection 11 2 control output contact specifications Sensor applied voltage AC5 5V max Working ambient temperature 0 C to 50 C no icing Working ambient humidity 35 RH to 85 RH no conde...

Страница 15: ...level etc Buzzer Average sound pressure 90 dB 10 cm sample value by manufacturer Control output contact Contact Configu ration Contacts For specifications refer to Section 3 3 Water leakage 1 for 1a B...

Страница 16: ...5 180 RESET BUZZER STOP POWER ALARM 35 Attached Drawing 1 Approved by Prepared by Scale Unit Prepared on Tatsuta Electric Wire Cable Co Ltd Water Leakage Location Detector mm 2010 04 Name Drawing No A...

Страница 17: ...h Terminal block M3 Detector number indication Sensor length and water leakage indication Power source indication LED Alarm indication LED Alarm cancel switch Buzzer stop switch Power AC85V AC264V E G...

Страница 18: ...Operation between Contact a and Contact b for break relay Itihyouji OFF Contact a ON Contact b 4 20mA operation OFF in the case of water leakage detection 6 0 03 water leakage location indication m mA...

Страница 19: ...f Water leakage detection Indicating sensor length Lighting out Lighting out Lighting out Flashing Lighting out Lighting out Alarm LED status Indicating the water leakage location Under normal sensor...

Страница 20: ...ber of each detector when multiple detectors are used together Turn the Detector Number Setting Switch to select a number that you want to indicate The detector number is indicated on the leftmost 7 s...

Отзывы: