5

6. The WAW pump

The WAW priority and the summer mode

The mixing valve (mixer)

The controller controls the pump loading the WAW container. The cycle of loading starts if the WAW
temperature sensor indicates a temperature below

At the lack of the temperature sensor of the WAW container (T2) the loading is realized at a wild

guess. The WAW pump switches on if water temperature in the water jacket of the stove reaches the
preset value or is above 50 C (

).

The controller realizes an after-season rundown of the pump. The pump switches on for a minute if

it doesn

t run for a week.

The controller controls a typical mixing valve (drive 230V/50Hz, integrated limit switches), keeping
up the preset temperature set by a user at the output of the valve.

Independent of the selected mode the additional parameters (<68> and <69>) allow the behavior

of the mixer drive to be individually adjusted.

The controller realizes an after-season rundown of the pump and the drive of the mixer.

If they don

t operate for a week the pump switches on for a minute and after it turns off the drive runs

for a minute.

50 C (

and ends if the

temperature is above 60 C (

). After finishing loading the WAW container the

pump runs still for a minute (

<46> TimeRunDownPumpWAW

), which prevents the temperature in

the jacket of the boiler from rising especially in summer time when the CH pump doesn

t run.

The loading is restricted to 2hours if the minimal temperature has been reached <52>.
The WAW pump operation is stopped if the following requirements are not met: water temperature
in the boiler is below the preset threshold 42 C (

) or water temperature in the

boiler is not higher by 5 C than in the WAW container(

).

The controller has different strategies for loading the WAW container as follows:

the WAW pump is off. The CH pump can run.

turning off the heating system in summer time (the CH pump doesn

t run,

mixer operation - see Ch.6/page 4). The fireplace operates only in the function of preparing
the WAW.

- normal operation (parallel operation of the pumps) without favoring the WAW circuit

- faster reaching the readiness of the WAW container by restricting the reception of

the heat by the heating system. The CH pump run cyclically. Turning off the WAW pump
after loading the container causes the normal operation of the CH pump to come back.

the pumps run as in PRIO mode. Additionally during loading the container the

preset temperature of the boiler is raised to 65 C (

).

The mixer can operate in one of the modes: off mode, floor mode and safety of the boiler return

temperature mode (

):

- the mixer maintains the preset temperature in the range of 20

40 C of the

floor system (<62p>

), additionally the alarm turns on and the pump turns off after

exceeding 40 C of the floor system (<61>

). Damage of the sensor of the

mixer causes the valve closed and the pump of the mixer switches off (P3). In SUMMER mode the
mixer is closed and its pump is off.

-the mixer is disabled and its pump is off.

- the mixer controls the flow of the return water to the boiler in order to keep

up the minimum return temperature set by the <62>

.parameter.

Damage of the sensor of the mixer causes the valve opened. The SUMMER mode has no effect

on the operation of the mixer.

o

o

o

o

o

o

o

<52> TminWAW”)

<51> TmaxWAW

<42> T.onPumpWAW

<54> DeltaWAW

<53> TLoadWAW

<60> ModeMIXER

TempFLOOR

„TempALARM-FLOOR”

TempMIXER

!

!

!

o

<52> TminWAW

5.1

7

OFF-
SUMMER-

ON
PRIO

SPEC-

FLOOR mode

OFF mode

RETURN mode

?

?

?

?

?

?

?

?

Za

łą

czony przeka

ź

nik STEROWANIE

Wskazanie górnego czujnika CWU

Wskazanie dolnego czujnika CWU

Wskazanie czujnika kominka

CO

*

KOM

?

CWU

80

o

73

o

68

o

20

POWER SUPPLY 230V/50Hz:

OUTPUTS 230V/50Hz:

VALVE DRIVE OUTPUT 230V/50Hz:

TEMPERATURE SENSORS:

The controller is to be connected to the mains protected by an appropriate fuse for the used
pumps and blower (typically 6,3A/230V):
L-

2 terminals L connected in the controller

N-

2 terminals N connected in the controller

PE-

2 safety terminals PE connected in the controller

L-DM- blower (200W max)
L-P1-

CH pump (200W max)

L-P2-

WAW loading pump (200W max)

L-P3-

mixer pump (200W max)

L-M+

valve drive - opening (brown or black depending on the valve mounting)(200W max)

L-M-

valve drive - closing (black or brown depending on the valve mounting)(200W max)
valve drive - connect the common output (blue) to N
valve drive - connect the safety cable (green-and-yellow) to PE

TB-

safety sensor of the boiler STB (in case of not using STB, apply the jumper)

T1-

boiler sensor (KTY81)

T2-

sensor of the WAW container (KTY81) (in case of not mounting the WAW,
leave unconnected)

T3-

sensor of the mixer (KTY81)(in case of not mounting the mixer, leave unconnected)

T4/TP- room thermostat (in case of not mounting the thermostat, leave unconnected)
T5-

available

T6-

temperature sensor of the flue gas (PT1000)

Содержание RT-14

Страница 1: ...thermostat 94 C 230V 50Hz Power consumption without load 4W Max connection power 750W Operation conditions 0 50 C humidity10 90 no condensation Housing protection class IP41 Fuse 6 3A 250V P of blower...

Страница 2: ...ILER 45min the temperature doesn t increase then the blower turns off an The given temperatures relate to the situation when the sensor of the flue gas is inactive After connecting the flue gas sensor...

Страница 3: ...r our sole responsibility that the product Controller of the Heating System model RT 14 PN EN 55022 2011 EMC IT devices Characteristics of radioelectric noises Acceptable levels and measurement method...

Страница 4: ...TimeStopPumpCH o o The controller protects the system from freezing automatically switches on the circulating pump if themeasuredtemperatureisbelow The controller realizes an after season rundown of t...

Страница 5: ...the WAW pump afterloadingthecontainercausesthenormaloperationoftheCH pumptocomeback the pumps run as in PRIO mode Additionally during loading the container the presettemperatureoftheboileris raisedto6...

Страница 6: ...ents onthecontrolpanel fig 8 The operation state is presented on the graphic display 2 The screens inform about the operation of devices temperature of sensors they make it possible to change the para...

Страница 7: ...21 TempALARM_BOILER 61 TempALARM FLOOR o 9 2 Screen of boiler operation Thescreenfeaturescurrenttemperatureof theboilerandrotationof theblower Fig 82 Screen of boiler operation 18 WARNING WE INFORM T...

Страница 8: ...ler in case of the room thermostat operation TempBOILER TempTHERMOSTAT 17 PASSWORD 9999 HAS CONSIDERABLE MEANING IT CAUSES THE REACTIVATION OF THE PREVIOUS PASSWORD IF PRESENT WITHOUT IT BEING DISCLOS...

Страница 9: ...he cyclical run After that time the CH pump runs for 45secs Temperature hysteresis of turning on off the pumps The temperature difference between turning on and turning off the pumps It prevents often...

Страница 10: ...60min 45min The time of keeping up the low boiler temperature after which the transition to the stop state follows 3X blower DEFAULT boiler 30 ADJUSTABLE 31 10 100 100 32 1 10 o C 2 o C 38 2 10 o C 5...

Страница 11: ...ways when the controller is on Switching off the backlighting means it gets the value defined by the next parameter 15 Minimum LCD backlighting it s valid at the negative LCD The value 0 means a full...

Страница 12: ...t Parameter value change Upper and lower change limit THE PARAMETERS ADJUST THE CONTROLLER TO THE FEATURES OF THE BOILER AND THE CH SYSTEM THEIR CHANGE SHOULD BE CONSULTED WITH THE PRODUCER OF THE BOI...