Fig.84A Screen of the mixer operation (heater, floor) in the manual mode

!

Manual operation is restricted in time. It ends automatically after 2 mins since last pressing

the F1 button

Icon of
MIXER and
MANUAL screen

Time to end of
manual
operation

Direction
of valve
movement

F2=end of
manual
operation

F1=change of
direction of valve
movement

Icon of
additional
data

9.6 Screen of setting the parameters

On the first screen of the parameters the text "Level of Parameters" is shown. The text has a value of
"0" that means the parameters are not available. After changing the level to "1","2" or "3" the
following screens show parameter values. The last screen includes "****" after which the setting of
the parameters ends and the return to the normal operation follows.

Fig.86 Screen of setting the parameters

Parameter
name

Unit

Parameter value
(/-)

Upper and
lower change

limit

!

!

THE PARAMETERS ADJUST THE CONTROLLER TO THE FEATURES

OF THE BOILER AND THE CH SYSTEM. THEIR CHANGE SHOULD BE
CONSULTED WITH THE PRODUCER OF THE BOILER OR THE
INSTALLER. INCAUTIOUS CHANGES MAY CAUSE UNSTABLE AND
INEFFICIENT OPERATION OF THE SYSTEM

The parameter number plays an additional role. It explicitly identifies the

name e.g. for different language versions.

Demonstration change of the <51>

TmaxWAW

parameter

that defines the maximum

temperature of the WAW container(level of parameters 1).
Press:

*press repeatedly CHOOSE till the

Level of Parameters 0

parameter setting screen

shows up.

*

CONFIRM

button >

0

starts blinking

* Button

+

->

1

blinks

*

CONFIRM

button ->

1

stops blinking (Level of Parameters 1 was chosen)

*repeatedly

CHOOSE

button -> till the <51>

TmaxWAW

parameter shows up

*

CONFIRM

button -> actual value to be changed begins blinking

*

+

/

-

-> setting a new value

*

CONFIRM

-> confirming the new value

*repeatedly

CHOOSE

button till the

***

parameter end setting screen appears.

Содержание RT-14

Страница 1: ...thermostat 94 C 230V 50Hz Power consumption without load 4W Max connection power 750W Operation conditions 0 50 C humidity10 90 no condensation Housing protection class IP41 Fuse 6 3A 250V P of blower...

Страница 2: ...ILER 45min the temperature doesn t increase then the blower turns off an The given temperatures relate to the situation when the sensor of the flue gas is inactive After connecting the flue gas sensor...

Страница 3: ...r our sole responsibility that the product Controller of the Heating System model RT 14 PN EN 55022 2011 EMC IT devices Characteristics of radioelectric noises Acceptable levels and measurement method...

Страница 4: ...TimeStopPumpCH o o The controller protects the system from freezing automatically switches on the circulating pump if themeasuredtemperatureisbelow The controller realizes an after season rundown of t...

Страница 5: ...the WAW pump afterloadingthecontainercausesthenormaloperationoftheCH pumptocomeback the pumps run as in PRIO mode Additionally during loading the container the presettemperatureoftheboileris raisedto6...

Страница 6: ...ents onthecontrolpanel fig 8 The operation state is presented on the graphic display 2 The screens inform about the operation of devices temperature of sensors they make it possible to change the para...

Страница 7: ...21 TempALARM_BOILER 61 TempALARM FLOOR o 9 2 Screen of boiler operation Thescreenfeaturescurrenttemperatureof theboilerandrotationof theblower Fig 82 Screen of boiler operation 18 WARNING WE INFORM T...

Страница 8: ...ler in case of the room thermostat operation TempBOILER TempTHERMOSTAT 17 PASSWORD 9999 HAS CONSIDERABLE MEANING IT CAUSES THE REACTIVATION OF THE PREVIOUS PASSWORD IF PRESENT WITHOUT IT BEING DISCLOS...

Страница 9: ...he cyclical run After that time the CH pump runs for 45secs Temperature hysteresis of turning on off the pumps The temperature difference between turning on and turning off the pumps It prevents often...

Страница 10: ...60min 45min The time of keeping up the low boiler temperature after which the transition to the stop state follows 3X blower DEFAULT boiler 30 ADJUSTABLE 31 10 100 100 32 1 10 o C 2 o C 38 2 10 o C 5...

Страница 11: ...ways when the controller is on Switching off the backlighting means it gets the value defined by the next parameter 15 Minimum LCD backlighting it s valid at the negative LCD The value 0 means a full...

Страница 12: ...t Parameter value change Upper and lower change limit THE PARAMETERS ADJUST THE CONTROLLER TO THE FEATURES OF THE BOILER AND THE CH SYSTEM THEIR CHANGE SHOULD BE CONSULTED WITH THE PRODUCER OF THE BOI...