©Copyright Task Force Tips, Inc. 2008-2014
LIX-300 April 29, 2014 Rev18
7
3.3 INLETS AND OUTLETS
MODEL
INLET FITTING TYPE
OUTSIDE
DIAMETER
THICKNESS
BOLT HOLE
CIRCLES
NO. BOLT
HOLES
SIZE OF
BOLTS
TORQUE ON BOLTS
XFI-FL*
3” ANSI 150
(metric PN20)
7.5”
190mm
.75”
20mm
6.0”
152.5mm
4
4
5/8”
M16
76-80 FT-LBF
100-110 Newton Meters
XFI-FP*
4” ANSI 150
(metric PN20)
9.0”
230mm
94”
23mm
7.5”
190.2mm
8
8
5/8”
M16
76-80 FT-LBF
100-110 Newton Meters
XFIH-E1*A
3” ANSI 125/150
(metric DN8 PN20)
7.5”
190mm
.75"
20mm
6.0"
152.5mm
4
4
5/8"
M16
76-80 FT-LBF
100-110 Newton Meters
XFIH-E2*A
4" ANSI 150
(metric DN100 PN20)
9.0"
230mm
.94"
23mm
7.5"
190.2mm
8
8
5/8"
M16
76-80 FT-LBF
100-110 Newton Meters
XFIH-E4*A
metric DN80, PN16
200 mm
22 mm
160 mm
8
16 mm
100-110 Newton Meters
XFIH-E5*A
metric DN100, PN16
220mm
22 mm
180 mm
8
16 mm
100-110 Newton Meters
XFIH-*6*A
3" NPT Female
4.40" (111.8mm)
NA
NA
NA
NA
NA
XFIH-*7*A
4" NPT Female
5.40" (137.2mm)
NA
NA
NA
NA
NA
XFIH-*8*A
3" BSP Male
4.40" (111.8mm)
NA
NA
NA
NA
NA
XFIH-*9*A
4" BSP Male
5.40" (137.2mm)
NA
NA
NA
NA
NA
XFIH-*L*A
Extend-A-Gun RC3
3.94" (94.6mm)
NA
NA
NA
NA
NA
XFIH-*P*A
"Extend-A-Gun RC4 or
Valve Under Monitor"
4.94"
123.5mm
NA
NA
NA
NA
NA
XFIH-*Q*A
"4.5"" Quick Connect
(without inlet adapter)"
6.75"
(171.5mm)
NA
NA
NA
NA
NA
XFIH-*R*A
"4.5"" Quick Connect with
4""ANSI 150/DN100 PN16"
9.0"
230mm
.94”
23mm
7.5 / 7.09
190/180mm
8
8
5/8
16mm
76-80 ft-lbf
(100-110 Nm)
XFIH-*S*A
"4.5"" Quick Connect with
4""NPT female inlet adapter"
5.40"
137.2mm
NA
NA
NA
NA
NA
XFIH-*T*A
"4.5"" Quick Connect for
Extend-A-Gun RC3"
4.25"
108mm
NA
NA
NA
NA
NA
XFIH-*U*A
"4.5"" Quick Connect for
Extend-A-Gun RC4"
5.36"
136.1mm
NA
NA
NA
NA
NA
* These digits in the model number refer to exit thread size and type.
Fig 3.3A
Inlet Flange Size Specifi cations
The standard Hurricane RC Monitor inlet is CODE-RLF for direct connection to TFT’s Extend-A-Gun RC3. Monitor inlet CODE-RPF
is available for direct connection to Extend-A-Gun RC4. The standard outlet is 2-½”-7.5 National Hose male. Various other inlet and
outlet fi ttings are available as shown in Figure 3.3B.
2.5"-7.5 NH
(65mm) MALE
2.5"-11 BSP
(65mm) MALE
SPECIAL
THREADS
BASE INLET OPTIONS:
CODE-RLF (3"), CODE-RPF (4")
or 4.5" QUICK CONNECT
(see LIY-250 for options)
FEMALE PIPE THREAD
3.0" NPT (Y4440NL)
4.0" NPT (Y4450NP)
MALE BSP THREAD
3.0"BSP (Y4420A)
4.0"BSP (Y4430A)
FLANGE
3.0"ANSI 150 (Y4410A)
4.0"ANSI 150 (Y4415A)
DN80, PN16 (Y4423A)
DN100, PN16 (Y4425A)
VALVE UNDER
MONITOR
with CODE-RPM outlet
(see LIA-285 for options)
EXTEND-A-GUN RC3 or RC4
(see LIX-530 for options)
INLET ADAPTER
OPTIONS
Fig 3.3B
Inlets and Outlets