©Copyright Task Force Tips LLC 2010-2021
9
LIU-330 February 15, 2021 Rev09
7.1 NOZZLE COMPATIBILITY
The following tables list the compatibility between eductors and nozzles. A 75 psi (5 bar) nozzle will result in lower nozzle pressure and
shorter stream reach.
Table 7.1A
UE-060 EDUCTOR
60 GPM (225 L/min)
200 PSI (13.8 bar) Inlet Pressure
TFT
Nozzle Name
Nozzle Model #
Water Flow
Setting
Nozzle
Pressure
Low Expansion
Foam Attachment
Multi-Expansion
Foam Attachment
Twister
F2060, FS2060,
FS2060P
60 gpm
(230 L/min)
100 psi
(7 bar
NONE
FJ-MX-F
Bubble Cup
F2060BC,
FS2060BC,
FS2060BCP
60 gpm
(230 L/min)
100 psi
(7 bar)
BUILT-IN
BUILT-IN
Metro 0
ME0**
60 gpm
230 L/min)
100 or 75 psi
(7 or 5 bar)
FJ-U
FJ-LX-U
FJ-UMX
1.0”
Quadrafog
DQ60, DQS60,
DQS60P
5-10-24-40-
60
gpm
(20-40-90-150-
230
L/min)
100 psi
(7 bar)
FJ-DQ
FJ-MX-DQ
1.0”
G-Force
Selectable Flow
Fixed Pressure
15-30-45-
60
-75 gpm
(55-110-170-
230
-285 L/min)
100 or 75 psi
(7 or 5 bar)
FJ-GD
FJ-LX-U
FJ-UMX
1.0”
G-Force
Automatic Pressure
with Variable Flow
30-80 gpm
(110-300 L/min)
100 or 75 psi
(7 or 5 bar)
FJ-GD
FJ-LX-U
FJ-UMX
Ultimatic
B-*, BTO-*, BH-*,
BGH-*
10-125 gpm
(40-475 L/min)
100 psi
(7 bar)
FJ-U
FJ-LX-U
FJ-UMX
BL-*, BTOL-*, BHL-*,
BGHL-*
10-100 gpm
(40-400 L/min)
75 psi
5 bar)
Metro 1
ME1**
60 gpm
(230 L/min)
100 or 75 psi
(7 or 5 bar)
FJ-HM
FJ-LX-HM
FJ-MX-HM
1.5”
Quadrafog
FQ125**, FQS125**
30-
60
-95-125 gpm
(110-
230
-360-470 L/min)
100 or 75 psi
(7 or 5 bar)
FJ-LX-FQ
FJ-MX-FQ
QuadraCup
FQ125BC,
FQS125BC**,
FQCS**
30-
60
-95-125 gpm
(110-
230
-360-470 L/min)
100 or 75 psi
(7 or 5 bar)
BUILT-IN
BUILT-IN
1.5” G-Force
Selectable Flow
Fixed Pressure
30-
60
-95-125-150 gpm
(110-
230
-360-470-570 L/min)
100 or 75 psi
(7 or 5 bar)
FJ-LX-G
FJ-MX-G
1.5” G-Force
Automatic Pressure
with Variable Flow
60-150 gpm
(230-570 L/min)
100 or 75 psi
(7 or 5 bar)
FJ-LX-G
FJ-MX-G
Thunderfog
FT200*, FTS200*
30-
60
-95-125-150-200 gpm
(110-
230
-360-470-570-750 L/min)
100 or 75 psi
(7 or 5 bar)
NONE
FJ-MX-FT