![TAS PowerTek TPF-56 Скачать руководство пользователя страница 40](http://html1.mh-extra.com/html/tas-powertek/tpf-56/tpf-56_user-manual_3630179040.webp)
Intelligent Power Factor Controller TPF-56
TPF-56 Controller fault indications and fault actions
Sr.No.
Status
Indications
on LCD
Display
Status / Fault Description
Programmable
Options
provided on
Fault
Fault description
Action taken
by TPF-56
controller
Status
appearing in
Data
Logging
Enable / Disable
/ Indicative /
Fast OFF
If Enabled
Yes / No
1
OK
Controller status is OK
Yes
2
ZV
Zero Voltage
Not
programmable
If voltage absent in any
one of the three phases
Fast OFF
Yes
3
OV
Over voltage
Not
programmable
(Fixed enable)
If voltage exceeds than
defined limit in any one
of the 3 P-N values
Fast OFF
Yes
4
UV
Under Voltage
Not
programmable
(Fixed enable)
If voltage reduces than
defined limit in any one
of the 3 P-N values
Fast OFF
Yes
5
VH
Voltage over-harmonics
THD%
Enable / Disable
If V-THD exceeds than
defined limit , in any one
of the 3 P-N values
Fast OFF
Yes
6
IH
Current over-harmonics
THD%
Enable / Disable
If I-THD exceeds than
defined limit, in any one
of the 3 P-N values
Fast OFF
Yes
7
BF
Battery for RTC faulty
Not
programmable
Battery checked as un-
usable
Stops data
logging
Yes
8
ZC
Zero current
Not
programmable
Load Current less than
1.5% in any one of the
three phases
Fast OFF
Yes
9
OB
Out of Banks
Enable / Disable Insufficient bank kvar
Indicative
Yes
10
OT
Over temperature
Fast off / Disable
Indicates
temperature inside
the APFC controller
Fast OFF
Yes
11
UF
Under frequency
Not
programmable
If reduces below 47Hz
(limit)
Fast OFF
Yes
12
OF
Over frequency
Not
programmable
If exceeds 53Hz (limit)
Fast OFF
Yes
13
UL
Under Load
Enable / Disable
If KW reduces than
defined limit, in any one
of the 3 P-N values
Fault OFF
(only normal
banks off)
Yes
14
OC
Over current
Enable / Disable
Load Current exceeds
than defined limit, in any
one of the 3 P-N values
Indicative
Yes
15
Battery Low!!!
Low battery
Not
programmable
Battery Voltage drops
below 2.6 V
Indicative
Yes
16
NF
Neutral Fault
Not
programmable
Shifting of neutral voltage
away from balanced
condition
Fast OFF
Yes
40 of 56
Version 1.1.5 22
nd
March, 2016