Panel ID: Value - 00000001 to 99999999. Default value
00000001. Defines the 8 digit Panel ID, used for serial
communication on RS-232 Dedicated protocol, and for
further analysis of down-loaded data. The panel ID can be
changed and a new Panel ID can be saved only if all the
logged data is Erased from the EEPROM. This is to prevent
false data.
•
Erase Data for New ID: Yes and No.
It erases all the logged data in the EEPROM. The panel ID
can be changed and a new Panel ID can be saved only if all
the logged data is Erased from the EEPROM.
• Baud Rate: selectable.
4800bps, 9600bps, 19200bps, 57600 bps. The Baud rate
should match on both sides, TPF-56 & PC/HHU for
communication.
• Real Time Clock: Defines the Real Time Clock / Calendar
setting.
• Time: Defines Hours (24 Hours Clock), Minutes and
Seconds ( HH:MM:SS ) format.
• Date: Defines the date, month & year setting.
(DD:MM:YY) format.
The above applicable only after saying “Yes” to initialize
RTC, by pressing Up key.
• Initialize RTC: Yes and No.
Defining “Yes” initializes RTC (real time clock) to the
specified set values.
• Clear Battery fault: Yes and No.
Defining “Yes” clears Battery fault and/or NV RAM fault in
TPF-56.
•
Select LOG Time : 60 MIN , 30 MIN , 15 MIN ,
10 MIN . By pressing UP key it Define log data at 60
/30/15/10 MIN interval period.Default value is 60 min.
•
EraseData4LOGTime : Yes and No.
Defining “ Yes ” erase all previously logged data from the
EEPROM . Select LOG Time can be changed and new
Select LOG Time can be saved only if all logged data is
erased from the EEPROM. This is to maintain time
synchronization of data.
•
COM 2 Function : None, Mod-bus ASCII , Mod-bus RTU,
GSM. Option Mod-bus ASCII & Mod-bus RTU for RS485
communication and GSM for RS 232 communication for an
external GSM/GPRS MODEM.
Communication
Intelligent Power Factor Controller TPF-56
36 of 56
Version 1.1.5 22
nd
March, 2016
Select LOG Time
60 MIN :
EraseData4LOG Time
No :
COM 2 Function :
Modbus RTU :
#
OvrWrt INTER LOG
No :
OvrWrt EVENT LOG
Yes :
Panel ID
00000001
ErasData 4 NewID
No :
Set Date
DD:MM:YY
Baud Rate - COM1
57600 :
Set Time
HH:MM:SS
Clr Battery Flt
No :
Initialize RTC
No :