TapFlo CTM Series Скачать руководство пользователя страница 6

 

10 

Instruction manual CTM mag drive pumps 

  

IOM manual Tapflo PE & PTFE series pumps 

11 

 

2. OPERATION

2.1 

Start-up

-  Check manually that the motor is free to turn, moving the motor cooling fan.

-  Make sure that the piping is not clogged and is free from residues or foreign objects. Make sure that 

the liquid flows regularly into the pump.

-  The pump and piping connected to it, at least the suction pipe, must be full of liquid. Any air or gas 

must be carefully released. In case of suction with negative head, fill the suction piping and check how 
the bottom valve works. It must guarantee that the liquid must not flow back, emptying therefore 
the suction pipe with consequent disconnection of the pump.

-  The suction shutoff valve (if any) must be completely open. 

-  The shutoff/regulation valve on the discharge side must be almost completely closed.

-  The motor must turn in the same direction as the arrow shown on the pump. The direction of rotation 

is always clockwise looking at the pump from the motor side; check by starting briefly, then looking at 
the direction of rotation of the motor fan through the fan lid. If it is wrong, the motor must be stopped 
immediately. Change the connection to the terminals of the electric motor (chapter 1.7) and repeat 
the procedure described above.

-  Any auxiliary connections must all be connected.

2.1.1 

Starting the pump

Start the electric motor and open the discharge adjustment/shutoff valve gradually until the desired 
output has been reached. The pump must not turn more than two or three minutes with discharge closed. 
A longer operation in these conditions can damage the pump seriously.

If the pressure shown on the pressure gauge on the discharge piping does not increase, turn off the pump 
immediately and release pressure carefully.  Repeat the connection procedure.

If there are changes of flow-rate, head, density, temperature or viscosity of the liquid, stop the pump and 
get in touch with our technical service.

2.1.2 

Re-starting after power shutoff

In case of accidental stopping, make sure that the non-return valve has prevented backflow and check 
that the motor cooling fan has stopped.  Start the pump again following the instructions of chapter 2.1.1 
”Starting the pump”.

If the pump intakes from a lower level, it can unprime during the standstill and therefore you must check 
again before starting that the pump and the suction piping are full of liquid.

2.2 

Stopping the Pump

It is advisable to close the discharge adjustment/shutoff valve gradually and stop the motor immediately 
after. The reverse sequence is not recommendable, especially with larger pumps or longer delivery piping.  
That is to avoid any problems due to water hammering.  If a suction shutoff valve has been installed, it 
is advisable to close it completely.

!

STOP

!

!

!

!

 

3. MAINTENANCE

Maintenance work on electrical installations must be performed by qualified personnel 
and only when the power supply has been shutoff. Follow the local and national safety 
regulations.

3.1 

Maintenance schedule

The CTM range pumps have been designed and tested to run for 5000 hours in ideal working conditions.  

Please note that is a conservative figure since the actual duty point of your pump can substantially modify 
such value.  Additional factors such as intermittent operation, type of pumped liquid and installation in 
the plant may affect the life of components subject to wear.

In any case, Tapflo advises to service pumps every year of service, even when used in ideal operating 
conditions.

3.2 

Trouble shooting

The following tables help to identify the causes of any problems during operation or failures of the pump.  
By consulting table ”A” identify on the left column (symptoms) the problem encountered on the right 
column (causes) the number relevant to the possible causes of malfunctioning.  Table ”B”, by excluding 
the causes not applicable to the case being examined, allows to identify the causes of  the problem.

Содержание CTM Series

Страница 1: ...this instruction manual carefully before you install and operate the pump IOM MANUAL Instructions for installation operation and maintenance Mag drive centrifugal pumps Pump models CTM 20 7 CTM 25 8...

Страница 2: ...sembly and disassembly 13 3 3 1 Disassembly of the pump 13 3 3 2 Wear Parts Replacement 14 3 4 Assembly 14 3 4 1 Screws recommended locking torque 14 4 SPARE PARTS 15 4 1 Spare part drawing CTM pumps...

Страница 3: ...ce of high intensity magnetic fields This signal stands at points in this instruction manual of particular importance for compli ancewithregulationsanddirectives forcorrectworkflowandforthepreventiono...

Страница 4: ...llation place it in a clean location Do not remove the pro tective covers from the suction discharge and air connections which have been fastened to keep pump internals free of debris Make sure to cle...

Страница 5: ...mance and the conditions of the pump installed we recommend using the following instruments a pressure vacuum gauge on the suction piping a pressure vacuum gauge on the delivery piping The pressure in...

Страница 6: ...mperature or viscosity of the liquid stop the pump and get in touch with our technical service 2 1 2 Re starting after power shutoff In case of accidental stopping make sure that the non return valve...

Страница 7: ...e too high 25 Liquid temperature too low 26 Insufficient pressure or bushes flushing lubrication 27 Shaft is not straight 28 Static and rotating parts rubbing 29 Damaged impeller 30 Inner bushes worn...

Страница 8: ...TM 25 10 Screws and nuts M6 9 111 CTM 25 10 Screws M6 9 4 SPARE PARTS CTM 25 8 CTM 25 10 CTM 20 7 4 1 Spare part drawing CTM pumps 4 2 Spare part list CTM pumps Pos Description Pump model qty Material...

Страница 9: ...n Qty 1511 Rotating bushing front 1 1512 Rotating bushing rear 1 1521 Static bushing front 1 1522 Static bushing rear 1 Kit of O rings 1 O rings 18 1811 1812 1821 1822 4 4 Pump code The model number o...

Страница 10: ...Tapflo operative manuals Tapflo does not guarantee that the product will meet the precise needs of the Customer except for those purposes set out in any invitation to render documents or other documen...

Страница 11: ...grade the products from their normal purpose as described in the products operative manual without the prior written consent of Tapflo 8 Installation including electric and other connections to utilit...

Страница 12: ...22 Instruction manual CTM mag drive pumps IOM manual Tapflo PE PTFE series pumps 23 NOTES NOTES...

Страница 13: ...e perfect choice for your pumping needs Tapflo Fluid Handling India Private Limited Office No 207 Amar Neptune Baner Pune 411045 INDIA Phone 91 20 65000215 E mail ad tapflo in Web www tapflo in Kung l...

Отзывы: