Tank Aquator Скачать руководство пользователя страница 6

 

TD_IM_009 

 

Page 6 of 11  

Rev 3 

7. 

PIPING 

 

See Installation Manual for piping instructions. 
 
In addition, follow these instructions below: 
 
All piping must be properly sized and influent piping must be gravity-fed. 

Turbulence caused by improperly sized piping or pumping influent into the Aquator may damage 
the Aquator, reduce its efficiency or require flow conditioners to augment the system.

 

 

Make sure the diameters of the connecting pipework are no larger than the diameters of the inlet nozzle 
and the outlet nozzle. 

 

Install expansion joints on any inlet or outlet tee/elbow connections. 

 

All connections to the Aquator must be flexible.   Provisions must be made to accommodate 
movement and misalignment between the piping and the Aquator.   Failure to do this may damage 
the tank or surrounding property.

 

 

Slope the inlet pipework downward to the Aquator to establish a proper gravity flow. 
Slope the outlet pipework downward away from the Aquator according to job specifications (typically 
between 0.5

–2.0 %) to establish a proper gravity flow. 

 

Tank Solutions recommends installing a gross pollutant trap (GPT) large enough to collect debris (such as 
leaves, gravel, sand, rags, etc.) upstream of the Aquator. 

 

A valve can be installed upstream of the inlet tee / elbow connection. 
A valve can be installed downstream of the outlet tee / elbow connection. 
Make sure inlet valves have no valve seat or reductions and are the same size as the piping. 
 
To prevent debris from entering the Aquator, plug the inlet piping and outlet piping until the drainage site is 
paved and the GPT (if present) is installed. 

 

If valves are installed, keep the valves completely open during normal operation. 

 

 

8. 

VENTING 

 

See Installation Manual for venting instructions. In addition, follow these instructions: 
 
Vent the Aquator to atmospheric pressure to ensure proper operation. 
 
Vent the Aquator inlet and outlet pipework to atmospheric pressure to ensure proper operation. 
 
For instructions on venting an interstitial space (applicable in a double-wall Aquator), 
See the section in Installation Manual on Venting Interstitial Space. 
 
Provide flame arrestors when required by regulations and standards and when appropriate for safety 
reasons. 
 

 

 

Содержание Aquator

Страница 1: ...system shall be only installed on drainage systems where light liquids need to be separated from water and retained within the separator They shall not be installed on drain and sewer systems containing domestic wastewater The drainage of areas where light liquids are unlikely to occur such as roofs and grassed areas should not discharge through separators The connection of the separator system to...

Страница 2: ...ng port clean the drain channel Light liquid and sludge shall be removed as required Before putting in service the Aquator shall be filled with fresh water Note emptying is recommended when on half of sludge volume or 80 of the storage capacity of the separator is reached In exceptional circumstances when personnel need to enter the separator it shall be fully drained and thoroughly ventilated The...

Страница 3: ...o the Aquator Each Aquator requires a separate Tank Installation Checklist Consult your Tank Solutions representative or distributor if additional Tank Installation Checklist forms is needed The Aquator owner should retain a copy of the Tank Installation Checklist to facilitate any warranty claim Tank Solutions recommends that the installing contractor also retain a copy It is important that this ...

Страница 4: ...d isolates the retention chamber such that pollutants are prevented from discharging to the drains and therefore the surrounding environment Full Retention All liquid entering the Aquator is treated There is no by pass possible Retention Chamber The first chamber that the liquids enter where phase separation occurs Silt falls to the Silt Retention Chamber which reduces the Total Suspended Solids T...

Страница 5: ...ons on testing the Aquator tank on the job site 3 BACKFILL MATERIAL See Installation Manual for backfill instructions Do not exceed 50 C temperature in the Aquator or its contents Excessive heat in the Aquator may result in minor or moderate injury or in failure of or damage to the Aquator 4 EXCAVATION PARAMETERS See Installation Manual for excavation instructions 5 ANCHORING TANKS See Installatio...

Страница 6: ...0 5 2 0 to establish a proper gravity flow Tank Solutions recommends installing a gross pollutant trap GPT large enough to collect debris such as leaves gravel sand rags etc upstream of the Aquator A valve can be installed upstream of the inlet tee elbow connection A valve can be installed downstream of the outlet tee elbow connection Make sure inlet valves have no valve seat or reductions and are...

Страница 7: ...t the sensors and alarm unit be fitted tested and commissioned by a licensed electrician This is to ensure that the excessive oil probe is calibrated correctly raising an alarm when 90 of the oil storage volume is reached Should the oil level alarm fail to provide an early warning excessive oil could pass through the separator thus polluting the environment 12 OPERATING THE AQUATOR Operating the A...

Страница 8: ...nsuring the dirty water runs back into the drainage system leading to the Aquator Do not stand on the coalescing filter support grating This grating is not designed to accept loads and is slippery Sludge and debris should be removed from the Aquator using a vacuum truck Do not use picks axes hammers or other heavy tools or objects when breaking apart sludge in the Aquator Such tools may damage the...

Страница 9: ...e SECTION 10 in this manual INSPECTING THE AQUATOR Continue maintenance by performing the following inspections as usage and the site conditions require Inspect and clean the GPT Inspect the inside of the Aquator looking for sand trash sludge and oil build up Inspect effluent water for oils or other contaminants during or immediately after a heavy rainfall 14 REMOVING AND CLEANING THE COALESCER Ke...

Страница 10: ...rom the Aquator 16 OPERATING GUIDELINES See this manual and the Installation Manual for operating guidelines 17 LIMITED WARRANTIES Each product is covered by a product specific limited warranty which contain operating guidelines and parameters that should be reviewed as applicable Copies of the limited warranties are found in Tank Solutions product brochures and are available upon request 18 SELEC...

Страница 11: ...E WESTERN AUSTRALIAN WATER CORPORATION All Aquator installations in the Water Corporation network must be installed with a Trade Waste Sampling Point TWSP on the Aquator outlet pipework See Water Corporation drawing number HX33 11 30 for details An example arrangement is shown below ...

Отзывы: