OVERALL PERFORMANCE SPECIFICATION
Insulation Resistance at 1000V DC
The insulation resistance will not be less than 10M
Ω
between mains input to frame and all
isolated outputs, and all combinations of isolated output to isolated output.
Applied Voltage Test
Mains input to frame and all isolated outputs 2kV RMS for 1 minute.
All combinations of isolated output to isolated output Isolated output to frame 1.5kV RMS for 1
minute.
Accuracy of Instruments
Ammeter plus appropriate current transducer ±0.6% of reading 6 digits
Polarity
Zero phase shift occurs on the following:
Mains input - external loading unit (Terminal 1 = Neutral).