background image

2

Tools Required . . .

Terminator-LN-Tool
(order separately)

3 mm
8 mm

28 mm
29 mm
33 mm

Item

Quantity

Description

1

1

Expediter Assembly 

    Grommet Compressor 

    Grommet 

    Support Base with O-Ring

2

1

Splice Cap

3

1

Banding Guide

4

1

Banding

Dimensions . . .

Terminator

TM

 ZS/ZE 

INSTALLATION PROCEDURES

Kit Contents . . .

1

2

4

3

2

4

3

5

Order Separately for End Termination
PETK Power and End Termination Kits (per cable)
PETK-1

for BSX, RSX, VSX

PETK-2

for KSX, HTSX,

PETK-3

for FP, HPT

Item

Quantity

Description

1

1

RTV Tube

2

1

Power Connection Boot

3

1

End Cap

4

1

Tape Strip Teflon 6" (PETK-3 only)

5

1

End Termination Caution Label

6

1

GRW-G Grommet (PETK-3 only)

1

2

4

3

5

Order Separately for Inline Splice
SCTK Splice Connection Termination Kits (per cable)
SCTK-1

for BSX, RSX, VSX

SCTK-2

for KSX, HTSX,

SCTK-3

for FP, HPT

Item

Quantity

Description

1

3

Splice Connection Boots

2

2

Small Crimps

3

1

Large Crimp

4

2

Small Crimp Insulators

5

2

Silicone Caps

6

3

Ground Sleeves

7

1

RTV Tube

6

1

Certifications/Approvals . . . 

1725           II 2 GD Ex eb IIC T4-T6, Ex tb IIIC T135°C-T85°C FM 10ATEX0058X

IP66 -60°C 

 Ta 

 +55°C 

Ordinary & Hazardous Locations

IECEx FMG 10.0022X Ex eb IIC T4-T6, Ex tb IIIC T135°C-T85°C 

Warnings . . .
•  Due to the risk of electrical shock, arcing and fire caused by 

product damage or improper usage, installation or mainte-
nance, a ground-fault protection device is required. 

•  Installation must comply with Thermon requirements and be 

installed in accordance with the regulations as per the norm 
EN IEC 60079-14 for hazardous areas (where applicable), or 
any other applicable national and local codes. 

•  Component approvals and performance ratings are based 

on the use of Thermon specified parts only.

•  De-energize all power sources before opening enclosure.

•  Keep ends of heating cable and kit components dry before 

and during installation.

•  Minimum bending radius of heating cable is 32 mm (except 

HPT is 57 mm and FP is 19 mm).

7

6

Содержание THERMON Terminator ZS-L-XP

Страница 1: ...mination Applications TerminatorTM ZS ZE In Line Splice End Termination Kit INSTALLATION PROCEDURES Tel 44 0 191 490 1547 Fax 44 0 191 477 5371 Email northernsales thorneandderrick co uk Website www heattracing co uk www thorneanderrick co uk ...

Страница 2: ...oots 2 2 Small Crimps 3 1 Large Crimp 4 2 Small Crimp Insulators 5 2 Silicone Caps 6 3 Ground Sleeves 7 1 RTV Tube 6 1 Certifications Approvals 1725 II 2 GD Ex eb IIC T4 T6 Ex tb IIIC T135 C T85 C FM 10ATEX0058X IP66 60 C Ta 55 C Ordinary Hazardous Locations IECEx FMG 10 0022X Ex eb IIC T4 T6 Ex tb IIIC T135 C T85 C Warnings Due to the risk of electrical shock arcing and fire caused by product dam...

Страница 3: ...hole 3 Slide expediter toward pipe and route cable through support base entry 7 Terminate cable with appropriate PETK termi nation kit Refer to PETK installation instruc tions 8 Push excess cable back through expediter Tighten cap securely Tape cable expansion loop to pipe 9 Connect bus wires using small crimps and connect ground wires using large crimp See page 9 for wiring details Trim excess wi...

Страница 4: ...ft latch mechanism and unscrew cap 1 Locate bus connection HPT and FP only and cable as shown Cut end of cable at angle to aid in piercing grommet Leave additional cable for expansion loop 2 Insert three cables into expediter 12 Tighten cap securely Three Cable Layout Tips 3 Mount expediter with three cables Do not band over cable TerminatorTM ZS ZE INSTALLATION PROCEDURES ...

Страница 5: ...5 In Line Splice Wiring Details T Splice TerminatorTM ZS ZE INSTALLATION PROCEDURES ...

Страница 6: ...onendkappen auf die Isolierkappen der Adernendhülsen 12 Schrauben Sie die Endkappe auf dem Standfuß mit der Hand auf 13 Stellen Sie sicher dass sich der Schließmechanismus in gesicherter Position befindet 14 Um die Endkappe zu entfernen riegeln Sie den Schließmechanismus auf und Schrauben Sie die Endkappe ab Español Kit empalme en línea empalme en T Instrucciones de instalación Terminator ZS XP pa...

Страница 7: ...n Dr PO Box 609 San Marcos TX 78667 0609 USA Phone 1 512 396 5801 European Headquarters Boezemweg 25 PO Box 205 2640 AE Pijnacker The Netherlands Phone 31 0 15 36 15 370 For the Thermon office nearest you visit us at www thermon com Tel 44 0 191 490 1547 Fax 44 0 191 477 5371 Email northernsales thorneandderrick co uk Website www heattracing co uk www thorneanderrick co uk ...

Отзывы: