2
Tools Required . . .
Terminator-LN-Tool
(order separately)
3 mm
8 mm
28 mm
29 mm
33 mm
Item
Quantity
Description
1
1
Expediter Assembly
Grommet Compressor
Grommet
Support Base with O-Ring
2
1
Splice Cap
3
1
Banding Guide
4
1
Banding
Dimensions . . .
Terminator
TM
ZS/ZE
INSTALLATION PROCEDURES
Kit Contents . . .
1
2
4
3
2
4
3
5
Order Separately for End Termination
PETK Power and End Termination Kits (per cable)
PETK-1
for BSX, RSX, VSX
PETK-2
for KSX, HTSX,
PETK-3
for FP, HPT
Item
Quantity
Description
1
1
RTV Tube
2
1
Power Connection Boot
3
1
End Cap
4
1
Tape Strip Teflon 6" (PETK-3 only)
5
1
End Termination Caution Label
6
1
GRW-G Grommet (PETK-3 only)
1
2
4
3
5
Order Separately for Inline Splice
SCTK Splice Connection Termination Kits (per cable)
SCTK-1
for BSX, RSX, VSX
SCTK-2
for KSX, HTSX,
SCTK-3
for FP, HPT
Item
Quantity
Description
1
3
Splice Connection Boots
2
2
Small Crimps
3
1
Large Crimp
4
2
Small Crimp Insulators
5
2
Silicone Caps
6
3
Ground Sleeves
7
1
RTV Tube
6
1
Certifications/Approvals . . .
1725 II 2 GD Ex eb IIC T4-T6, Ex tb IIIC T135°C-T85°C FM 10ATEX0058X
IP66 -60°C
≤
Ta
≤
+55°C
Ordinary & Hazardous Locations
IECEx FMG 10.0022X Ex eb IIC T4-T6, Ex tb IIIC T135°C-T85°C
Warnings . . .
• Due to the risk of electrical shock, arcing and fire caused by
product damage or improper usage, installation or mainte-
nance, a ground-fault protection device is required.
• Installation must comply with Thermon requirements and be
installed in accordance with the regulations as per the norm
EN IEC 60079-14 for hazardous areas (where applicable), or
any other applicable national and local codes.
• Component approvals and performance ratings are based
on the use of Thermon specified parts only.
• De-energize all power sources before opening enclosure.
• Keep ends of heating cable and kit components dry before
and during installation.
• Minimum bending radius of heating cable is 32 mm (except
HPT is 57 mm and FP is 19 mm).
7
6