![T&D RTR-500DC Скачать руководство пользователя страница 41](http://html2.mh-extra.com/html/tandd/rtr-500dc/rtr-500dc_manual_3072275041.webp)
Communication Functions
41
Downloading Data from a selected Remote Unit
Wireless Communication:[
Gather Data]
1.
In the Main Menu, open [WL Gather Data].
2.
Open [Specify Remote Unit] and then select the Group and
Remote Unit from which you wish to download data.
3.
Select the Download Mode in the [Execute] window.
[COM Route] : Select route of communication
[Direct] : Communicate directly without Repeaters
[As Set]: Communicate according to Wireless Route Settings.
As the RTR-500DC is a hand held portable Base Unit, it is recommended to set to
[Direct] so as to shorten communication time.
[Period] : Period for Download Settings
[1 hour] to [47hours]: in units of 1 hour
[2 Days] to [300Days]: in units of 1 day
[All Data]: all of the data stored in the Remote Unit will be downloaded.
4.
Adjust the arrow to [Execute] and press the Operation Dial to
search for Remote Unit and start the downloading.
Pressing the Operation Dial during a download session or while searching for a
Remote Unit will cancel the operation.