                                                              TXC3150 Conventional Manual Call Point 

Installation & Operation Manual 

                                 
 
 

                                                                    

                                                                                                                                           

Specifications are subject to change w ithout prior notice

 

line and wire for cascading connection to the next base of manual button onto one terminal.  

5.5Metal dome reset of manual button  

  After metal dome of this manual  button is pressed, only a special reset key is used to reset it. If 
manual button is to be reset after action, first open reset hole cover and then insert the key into key 
hole and rotate it by  90° clockwise. Reset diagram as shown in Fig.5   

 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 

6. Testing 

Warning: after all equipment is installed, power on.

 

1.Before manual button is tested, related management department shall be notified that the system 

will be maintained and the work will stop temporarily. At the same time logic control function of 

area  or system  to be maintained shall be  cut off to avoid unnecessary  alarm linkage.   

2.Press metal dome of manual button. Red alarm indicator of manual button shall be  on.   

3.After testing is over, reset key is used to reset manual button and related management department 

is notified that the system  restores  normally.   

4.During the course of test, check if wiring of unqualified manual button is normal. Then test it again. If 

it does not pass the test, it shall be returned for repair.   

7. Operation 

  This manual button is non-encoded type, and not required to make encode setting. It is used 
according  to wiring type in Fig. 4.   

8 Transportation and  storage 

  The equipment shall be packed for transportation, handling and storage. During the course of 

loading and unloading, handle with care to prevent from being damaged.  Storage environment 
shall be  ventilated and dry.  Do not store it in open air.   

9. Notes 

按片

钥匙插孔

此处用辅助片上取下的

螺钉插入固定前盖

火警

按下报警

The screws removed from auxiliary 
plates are inserted to fix front 
cover 

Key hole 

Press here 

Fig. 5 Reset diagram of metal dome

 

4050100458-Rev1.0-1017

 

TANDA

Содержание TXC3150

Страница 1: ...TXC3150 Conventional Manual Call Point Installationand Operation Manual TANDA Development Copyright 2015 All right reserved...

Страница 2: ...are subject to change w ithout prior notice 2 Table of Content 1 General 3 2 Features 3 3 Technical Parameters 3 4 Structure features and operating principle 3 5 Installation and wiring 4 6 Testing 6...

Страница 3: ...ucture is installed easily and reliably 3 Technical Parameters 1 Operating voltage DC24V 12 28V 2 Operating current 1 Normal current 0mA 2 Alarm current 30mA 3 Output capacity rated DC30V 0 1A passive...

Страница 4: ...ndicator of fire alarm is on Fire alarm information is sent to the controller The controller displays fire alarm information 5 Installation and wiring Warning before installation cut off power supply...

Страница 5: ...ut terminal without polarity O1 and O2 cascade connection to the next equipment no polarity or connecting with 5 1K terminal resistance K1 and K2 normally on signal output terminal rated capacity 30V...

Страница 6: ...shall be cut off to avoid unnecessary alarm linkage 2 Press metal dome of manual button Red alarm indicator of manual button shall be on 3 After testing is over reset key is used to reset manual butt...

Страница 7: ...of manual button 2 This product is fire control product Regulations for on duty and duty shifting system shall be carried out Running records shall be made 3 Manual button shall be tested on alarm fu...

Отзывы: