                                                              TXC3150 Conventional Manual Call Point 

Installation & Operation Manual 

                                 
 
 

                                                                    

                                                                                                                                           

Specifications are subject to change w ithout prior notice

 

5.2Removal method (as shown in Fig. 3) 

Plug-in type is used between base and upper cover of this manual button. A special key is inserted to 
remove the base and upper cover of the manual button.    

火警

按下报警

上盖

底座

 

 
 

5.3Terminal description (as shown in Fig. 4 ) 

O2

O1

I2

I1

K2 K1

O2

O1 I2

I1

 

 

 

I1 and I2: power supply  input terminal, without polarity. 

O1  and  O2: cascade connection to the next equipment (no polarity) or connecting with 5.1KΩ 

terminal resistance. 

K1 and K2: normally-on signal output terminal (rated capacity  30V/0.1A

). 

5.4Wiring requirements: 

In order to avoid wiring confusion, different colors shall be used for wiring; the  connection between 

wire and manual button base terminal shall be sealed (without exposed copper wire). 

Wiring method is as shown in Fig. 5. When wiring the base of manual button, do not tighten incoming 

Base 

Upper cover

 

Fig. 3 Removing diagram of manual button

 

Fig. 4 Terminal description

 

4050100458-Rev1.0-1017

 

TANDA

 

Содержание TXC3150

Страница 1: ...TXC3150 Conventional Manual Call Point Installationand Operation Manual TANDA Development Copyright 2015 All right reserved...

Страница 2: ...are subject to change w ithout prior notice 2 Table of Content 1 General 3 2 Features 3 3 Technical Parameters 3 4 Structure features and operating principle 3 5 Installation and wiring 4 6 Testing 6...

Страница 3: ...ucture is installed easily and reliably 3 Technical Parameters 1 Operating voltage DC24V 12 28V 2 Operating current 1 Normal current 0mA 2 Alarm current 30mA 3 Output capacity rated DC30V 0 1A passive...

Страница 4: ...ndicator of fire alarm is on Fire alarm information is sent to the controller The controller displays fire alarm information 5 Installation and wiring Warning before installation cut off power supply...

Страница 5: ...ut terminal without polarity O1 and O2 cascade connection to the next equipment no polarity or connecting with 5 1K terminal resistance K1 and K2 normally on signal output terminal rated capacity 30V...

Страница 6: ...shall be cut off to avoid unnecessary alarm linkage 2 Press metal dome of manual button Red alarm indicator of manual button shall be on 3 After testing is over reset key is used to reset manual butt...

Страница 7: ...of manual button 2 This product is fire control product Regulations for on duty and duty shifting system shall be carried out Running records shall be made 3 Manual button shall be tested on alarm fu...

Отзывы: