TXC3150
Conventional Manual Call Point
Installation and Operation Manual
TANDA
Development
Copyright
©2015,
All
right
reserved.
Страница 1: ...TXC3150 Conventional Manual Call Point Installationand Operation Manual TANDA Development Copyright 2015 All right reserved...
Страница 2: ...are subject to change w ithout prior notice 2 Table of Content 1 General 3 2 Features 3 3 Technical Parameters 3 4 Structure features and operating principle 3 5 Installation and wiring 4 6 Testing 6...
Страница 3: ...ucture is installed easily and reliably 3 Technical Parameters 1 Operating voltage DC24V 12 28V 2 Operating current 1 Normal current 0mA 2 Alarm current 30mA 3 Output capacity rated DC30V 0 1A passive...
Страница 4: ...ndicator of fire alarm is on Fire alarm information is sent to the controller The controller displays fire alarm information 5 Installation and wiring Warning before installation cut off power supply...
Страница 5: ...ut terminal without polarity O1 and O2 cascade connection to the next equipment no polarity or connecting with 5 1K terminal resistance K1 and K2 normally on signal output terminal rated capacity 30V...
Страница 6: ...shall be cut off to avoid unnecessary alarm linkage 2 Press metal dome of manual button Red alarm indicator of manual button shall be on 3 After testing is over reset key is used to reset manual butt...
Страница 7: ...of manual button 2 This product is fire control product Regulations for on duty and duty shifting system shall be carried out Running records shall be made 3 Manual button shall be tested on alarm fu...