background image

                                                                                                       TX7322 Addressable Sounder Base 

 

 

        Installation & Operation Manual  

1 Introduction  

 

1.1 Overview  

The TX7322  Addressable Sounder Base  is  an  alarm warning device used  to  notify  persons in the 

vicinity of the occurrence fire emergency in order the person to take appropriate measures. The unit 

adopt multi-application device starting from the types, parameters and wiring layout in single unit. 

The TX7322 Addressable Sounder Base  is powered by the communication  bus.  The TX7322  can 

change into different encoding modes such as non-coding mode, single-encoding mode and dual-

encoding  mode  using  a  programming  tool.

 

And  it has different starting modes.  In  addition,  the 

alarm tone can be configured according to the requirement from 17 different tones.  

The unit manufactured base on the requirement of EN 54 part 3, European Standard. The unit is 

aesthetically pleasing with unobtrusive design that will complement modern building designs and its 

plug-in type assembles make installation and maintenance more convenient to the installer. The unit 

is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel, produced by single 

manufacture T&A, to avoid addressable communication compatibility problem.  

1.2 Feature and Benefits  

 

EN54-3 compliance 

 

Built-in MCU processor and digital addressing  

 

17 tones Programmable sound output  

 

Encoding  modes such as Non-coding  Mode,  Single-encoding  Mode  and  Dual-encoding 

Mode 

 

Programmable Evacuate or Pre-alarm/Evacuate signal  

 

Be started directly by a detector 

 

Onsite adjustable parameters 

 

Loop power input  

 

Aesthetically pleasing design 

 

Universal mounting with fix base for simple installation 

 

1.3 Technical Specification  

 

Listed   

 

 

  

LPCB Pending 

 

Compliance     

 

 

EN54-3 

 

Input Voltage   

 

 

Loop Power: 24VDC [16V to 28V] 

  

 

Current Consumption   

 

Standby: 

0.8mA, Alarm: 

4mA 

 

 

 

 

Protocol/Addressing    

 

T&A, Value range from 1 to 254 

 

Address Sequence 

 

 

non-coding mode: Alarm tone 

Single Address: Alarm tone  

Dual Address: 1

st

 warning tone / 2

nd

 Alarm tone 

 

Material / Colour  

 

 

ABS / White Glossy finishing  

 

Dimension / Height 

 

 

Diameter 140mm / 59.1mm (with a cover)  

 

Weight  

 

 

 

194g (with a cover)/176g (without a cover) 

 

Class   

 

 

 

Type A, Indoors 

 

Operating Temperature 

 

-10°C to +55°C 

 

Ingress Protection Rating 

 

IP30 

 

Humidity 

 

  

 

0 to 95% Relative Humidity, Non condensing 

2 Installation   

 

2.1 Installation Preparation 

This alarm warning device must be installed, commissioned and maintained by a qualified or factory 

trained service personnel. The installation must be installed in compliance with all local codes having 

                                                                                                                               4050100446-Rev1.0-0917                                                                      

 

 

    TANDA UK  

                                                                                                                                           

Specifications are subject to change without prior notice 

      

 

Содержание TX7322

Страница 1: ...TX7322 Addressable Sounder Base Installation and Operation Manual TANDA UK Technology Copyright 2017 All right reserved...

Страница 2: ...Union directive 2012 19 EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your loca...

Страница 3: ...on and Wiring 5 3 Addressable Sounder Base Configuration 6 3 1 Preparation 6 3 2 Parameter setting 6 3 3 Encoding Mode Setting 7 3 4 Tone Setting 8 3 5 Read Configuration 10 4 General Maintenance 10 5...

Страница 4: ...tibility problem 1 2 Feature and Benefits EN54 3 compliance Built in MCU processor and digital addressing 17 tones Programmable sound output Encoding modes such as Non coding Mode Single encoding Mode...

Страница 5: ...als connection diagram as shown in Figure 1 2 The bottom structure of the Addressable Sounder Base as shown in Figure 2 Install the Addressable Sounder Base on the TX3980 type base with the installati...

Страница 6: ...Terminal Base Warning Disconnect the loop connection whilst connecting to the handheld programmer 3 2 Parameter setting 1 Connect the programming cable to Z1 and Z2 terminals as shown in Figure 5 Pre...

Страница 7: ...s such as non coding mode single encoding mode and dual encoding mode Different encoding modes correspond to different ways of operation It can be change the encoding mode by a programming tool Non en...

Страница 8: ...ding mode setting Fig 12 Success to setting Fig 13 Fail to setting Note The programming tool can still read the address of the Addressable Sounder Base in non coding mode But the controller can not ch...

Страница 9: ...5s 0 25s off 17 17 78 9 800Hz 1s off 1s on Pre alarm 1 Attach the programming tool to 1 and 6 Terminals of Addressable Sounder Base Press Power to switch on the unit 2 Switch on the programmer then pr...

Страница 10: ...cting the maintenance and make sure to enable the alarm warning device and confirm if up and running 6 Perform the maintenance on semi annually or depending on the site conditions 5 Troubleshooting Gu...

Страница 11: ...0 7 77 4 75 5 45 71 1 69 8 75 1 72 7 75 70 6 73 9 76 3 77 8 105 71 2 70 1 74 1 75 4 135 72 0 70 4 77 5 72 3 165 70 7 70 8 74 7 76 3 Limitation of Addressable Sounder Base The alarm warning device cann...

Страница 12: ...other components of the system must be repaired and or replaced immediately as they fail This product is not approved to EN54 23 Beacon Functionality and must not be used as a visual alarm device or...

Отзывы: